background image

Attached accessories.

INDOOR UNIT

OUTDOOR UNIT

If an awning is built over the unit to prevent 
direct sunlight or rain, be careful that heat 
radiation from the condenser is not obstructed.

There should hot be any animal or plant which 
could be affected by not air discharged.

Keep the spaces indicated by arrows from wall, 
ceiling, fence or other obstacles.

Do not place any obstacles which may cause a 
short circuit of the discharged air.

If piping length is over 10m, additional 
refrigerant should be added as shown in the 
outdoor unit lable.

There should not be any heat source or steam 
near the unit. 

There should not be any obstacles blocking the 
air circulation.

A place where air circulation in the room is 
good.

A place where drainage can be easily done.

A place where noise prevention is taken into 
consideration.

Do not install the unit near the door way.

Ensure the spaces indicated by arrows from 
the wall, ceiling, fence or other obstacles.

Recommended installation height for indoor 
unit shal be at least 2.3m.

SAFETY PRECAUTIONS

ENGLISH

Read the following "SAFETY PRECAUTIONS"  carefully before installation.
Electrical work must be installed by a licensed electrician. Be sure to Use the correct rating of the power plug and main circuit for the model to be installed.
The caution items stated here must be followed because these important contents are related to safety. The meaning lf each indication used is as below. 
Incorrect installation due to ignoring of  the instruction will cause harm or damage, and  the seriousness  is classified by the following indications.

This indication shows the possibility of causing death or serious injury.

WARNING

The items to be followed are classified by the symbols:

Symbol with background white denotes item that is PROHIBITED from doing.

Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and maintenance as 
stated in instructions. Please remind the customer to keep the operating instructions for future reference.

WARNING

1)  Use qualified installer and follow careful this instructions. Otherwise it will cause electrical shock, water leakage, or esthetic problem.

2)  Install at a strong and firm location which is able to withstand  the set's weight. If the strength is not enough or installation is not properly done, the set will drop and 

cause injury.

3)  For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single outlet must be used. If 

electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.

4)  Use the specified cable and  connect tightly for indoor/outdoor connection. Connect tightly and clamp the cable so that no external force will be acted on the terminal. 

If connection or fixing is not perfect, it will cause heat-up or fire at the connection.

5)  Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause heat-up at connection 

point of terminal, fire or electrical shock.

6)  When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle. Otherwise, it will cause lower 

capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.

7)  Do not damage or use unspecified power supply cord. Otherwise, it will cause fire or electrical shock.

8)  Do not modify the length of the power supply cord or use of the extension cord, and do not share the single outlet with other electrical appliances. 

Otherwise, it will cause fire or electrical shock.

9)  This equipment must be earthed. It may cause electrical shock it grounding is not perfect.

10)  Do not install the unit at place where leakage of flammable gas may occur. Incase gas leaks and accumulates at surrounding of the 

unit, it may cause fire.

11)  Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.

ATTENTION

2)  Power supply connection to the room air conditioner. 
     Connect the power supply cord of the room air conditioner to the mains using one of the following method.
      Power supply point shall be the place where there is ease for access for the power disconnection in case of emergency.
      In some countries, permanent connection of this room air conditioner to the power supply is prohibited.
      1) Power supply connection to the receptacle using a power plug.

   Use an approved 10A power plug with earth pin for 2.1-3.6kW and 15A for 5.0kW for the connection to the receptacle.

      2) Power supply connection to a circuit breaker for the permanent connection. Use an approved 10A circuit breaker for 

 and 15A for 5.0kW for the 

permanent connection. It must be a double pole switch with a minimum 3mm contact gap.

2.1-3.6kW

5)  Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.

4)  Installation work.
     It may need two people to carry out the installation work.

3)  Do not release refrigerant.
     Do not release refrigerant during piping work for installation, reinstallation and during repairing a refrigeration parts. Take care of the liquid refrigerant. it may cause 

frostbite.

1)  Selection of the installation location.
     Select a installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance.

Required tools for Installation Works

7. Knife
8. Gas leak detector
9. Measuring tape
10. Thermometer
11. Megameter
12. Multimeter

13. Torque wrench

18 N

m (1.8 kgf.m)

35 N

m (3.5 kgf.m)

55 N

m (5.5 kgf.m)

14. Vacuum pump
15. Gauge manifold

(for R-410A)

1. Screw driver
2. Electric drill, hole core drill
    (   60 mm)
3. Hexagonal wrench
4. Spanner
5. Pipe cutter
6. Reamer

New Refrigerant Air Conditioner Installation

THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER. 

R410A refrigerant is apt to be 

affected by impurities such as water, oxidizing membrane, and oils because the working pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. 
Accompanied with the adoption of the new refrigerant, the refrigeration machine oil has also been changed. Therefore, during installation work, be sure that water, 
dust, former refrigerant, or refrigeration machine oil does not enter into the new type refrigerant R410A air conditioner circuit. 
To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging port on main unit and installation tools are different from 
those used for the conventional refrigerant units. Accordingly, special tools are required for the new refrigerant (R410A) units. For connecting pipes, use new and 
clean piping materials with high pressure fittings made for R410A only, so that water and/or dust does not enter. Moreover, do not use the existing piping because 
there are some problems with pressure fittings and possible impurities in existing piping.

Changes in the product and components

In air conditioners using R410A, in order to prevent any other refrigerant from being accidentally charged, the service port diameter size of the outdoor unit control 
valve (3 way valve) has been changed. (1/2 UNF 20 threads per inch)

 In order to increase the pressure resisting strength of the refrigerant piping, flare processing diameter and 

     opposing flare nuts sizes have been changed. (for copper pipes with nominal dimensions 1/2 and 5/8)

INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT)

CAUTION

 Incidentally, the "refrigerant cylinder" comes with the refrigerant designation (R410A) and protector coating in the U.S's ARI specified rose color (ARI color

    code: PMS 507).

 Also, the "charge port and packing for refrigerant cylinder" requires 1/2 UNF 20 threads per inch corresponding to the charge hose's port size.

New tools for R410A

As the working pressure is high, it is impossible  to measure the working pressure 
using conventional gauges. In order to prevent any other  refrigerant from being 
charged, the port diameters have been changed.

In order to increase pressure resisting strength, hose materials  and port sizes have 
been changed (to 1/2 UNF 20 threads per inch).  When purchasing a charge hose, 
be sure to confirm the port size.

As working pressure is high and gasification speed is  fast, it is difficult to read the 
indicated value by means of charging cylinder, as air bubbles occur.

The size of opposing flare nuts have been increased.  Incidentally, a common 
wrench is used for nominal diameters 1/4 and 3/8.

By increasing the clamp bar's receiving hole size, strength  of spring in the tool 
has been improved.

Used when flare is made by using conventional flare  tool.

Connected to conventional vacuum pump. It is necessary to  use an adapter to 
prevent vacuum pump oil from flowing back into the  charge hose. The charge 
hose connecting part has two ports -- one for  conventional refrigerant (7/16 
UNF 20 threads per inch) and one for R410A.  If the vacuum pump oil (mineral) 
mixes with R410A a sludge may occur and damage  the equipment.

Exclusive for HFC refrigerant.

New tools for R410A

Applicable to R22 model

Changes

Gauge manifold

Charge hose

Electronic balance for 
refrigerant charging

Torque wrench (nominal 
dia. 1/2, 5/8)

Flare tool (clutch type)

Gauge for projection 
adjustment

Vacuum pump adapter

Gas leakage detector

SELECT THE BEST LOCATION

Indoor/Outdoor Unit Installation Diagram

Length of power supply cord

About 1.0 m

About 2.0 m

Piping direction

Right

Right Rear

Right Bottom

Left Rear

Left

(Front side)

This illustration is for explanation purposes only.
The indoor unit will actually face a different way.

30

 cm

or

more

10 cm

or more

10 cm

or mo

re

100

 cm

or more

Vinyl tape

Insulation of piping connections

Carry out insulation after
checking for gas leaks
and secure with
vinyl tape.

Saddle

Connecting cable -
heavier cord

Additional drain hose

Liquid piping

Gas piping

Bend the pipe as closely on
the wall as possible, but be
careful that it doesn't break.

5 cm

or more

10cm

or

 more

Attention not to bend up
drain hose

No.

Accessories part

Qty. No.

Accessories part

Qty.

1

6

1

1

2

3

5

6

1

2

1

Installation plate

Installation plate 
fixing screw

Remote control

Operation and 
installation
instructions

Drain elbow 

Air purifying filter (optional)

4

7

8

1

2

Installation carton board

Unit support

I

N

D

O

O

R

U

N

I

T

SELECT THE BEST LOCATION

(Refer to "Select the best location" section)

1

HOW TO FIX INSTALLATION

PLATE

2

The mounting wall is strong and solid enough to prevent it 
from the vibration.

1.FOR THE RIGHT REAR PIPING

Pull out the Indoor piping

Install the Indoor Unit

Secure the Indoor Unit

Pull out the Indoor piping

Install the Indoor Unit

Install the connecting cable and pipe

Secure the Indoor Unit

3.FOR THE LEFT AND LEFT BOTTOM

Collaborate the piping

Secure the Indoor Unit

3

INDOOR UNIT INSTALLATION

2. FOR THE RIGHT AND RIGHT 
    BOTTOM PIPING

Install the Indoor Unit

Secure the Indoor Unit

1. Tape the extra power supply cord in a bundle and keep it behind 
    the chassis.
       Ensure that the power supply cord is not clamped  in between the unit's 
       hook (2 positions) and installation plate.

2. Take away the two installation support from the indoor unit.

3. Press the lower left and right side of the  unit against the installation 
    plate until hooks engages with their slots (sound click).

Gas side 
piping

Liquid side 
piping

70 cm

Cable

Connecting
cable

Gas side
piping

Liquid side
piping

Drain hose

Rear view for left piping installation

To take out the unit, pull  the 
marking at the bottom unit, and pull it 
slightly towards you to disengage the 
hooks from the unit.

marking

1. Hook the indoor unit onto the upper 

portion of installation plate (Engage the 
indoor unit with the upper edge of the 
installation plate). ensure the hooks are 
properly seated on the installation plate 
by moving in left and right.

2. Used two installation support that 

supply in the accessory bag to support 
the indoor unit in a angle about 25", 
than connected the piping and power 
supply cord.

3. Length of connecting cable.

Connecting cable

Drain hose

Adjust the piping slightly downwards.

Collaborate the piping

50mm
min

50mm
min

100mm min

pipe hold(L)

pipe hold(R)

Screw

The edge of installation carton board should be at more 
than 200mm at right and left of the wall.

The distance from installation carton board edge to 
ceiling should more than 100mm;

1. Conglutinate the installation carton board on the wall 

in a horizontal position where you should installation 
the indoor unit; you could estimate the installation 
board if in the horizontal bases on the level gauge 
that on the carton board;

2. Drill four holes to accommodate the dowels to mount 

the installation plate, the four holes have in the 
installation carton board;

3. Drill the piping hole at either right or left with    60mm 

hole-core drill, and the holes hold be slightly slanted 
to the outdoor side, the piping hold has in the 
installation carton board;

4. Take away the carton board and mount the 

installation plate on the wall with four screws or more.

Install the Indoor Unit

INSTALLATION OF AIR PURIFYING FILTERS

4

1. Open the grille.

2. Remove the air filters.

3. Put air purifying filter into place as shown in illustration at right.

O

U

T

D

O

O

R

U

N

I

T

SELECT THE BEST LOCATION

(Refer to "Select the best location" section)

1

INSTALL THE OUTDOOR UNIT

2

CONNECTING THE PIPING

3

Align center of piping to valves and then tighten with torque wrench to the specified 
torque as stated in the table.

Connecting The Piping To Indoor Unit

Connecting the Piping To Outdoor Unit

Connect the piping

Align the center of piping and 
sufficiently tighten the flare nut with 
fingers.
Further tighten the flare nut with 
torque wrench in specified torque as 
stated in the table.

After selecting the best 
location, start 
installation according 
to Indoor/Outdoor Unit 
Installation Diagram.

1. Fix the unit on 

concrete or rigid frame 
firmly and horizontally 
by bolt nut (    8 mm).

2. When installing at roof, 

please consider strong 
wind and earthquake. 
Please fasten the 
installation stand firmly 
with bolt or nails.

Spanner
or wrench

Torque
wrench

1. Please cut using pipe cutter and then remove the burrs.

2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be 

caused. Turn the piping end down to avoid the metal powder entering the pipe.

3. Please make flare after inserting the flare nut onto the copper pipes.

4. If you used the piping kit,  you could connect the piping directness and no need 

do the procedure 1 to 3.

CUTTING AND FLARING THE PIPING

Model

Piping size

Gas

Liquid

2.1-3.6 kW

5.0 kW

1/2" (60 N m)

1/4"(20 N m)

1/4"(18 N m)

3/8" (45 N m)

EVACUATION OF THE 

REFRIGERATION TUBES 

AND THE INDOOR UNIT

After connection the unions of the indoor and outdoor units, 

purge the air from the tubes and indoor unit as follows:

1. Connect the charging hoses with a push pin to the low and 

high sides of the charging set and the service port of the 
suction and liquid valves. Be sure to connect the end of the 
charging hose with the push pin to the service port.

2. Connect the center hose of the charging set to a vacuum pump.

3. Turn on the power switch of the vacuum pump and make sure 

that the needle in the gauge moves from 0MPa (0cm Hg) to -
0.1 MPa (-76cm Hg). Let the pump run for fifteen minutes.

4. Close the valves of both the low and high sides of the charging 

set and turn off the vacuum pump. Note that the needle in the 
gauge should not move after approximattely five minutes.

5. Disconnect the charging hose from the vacuum pump.

6. Tighten the service port caps from both valves.

7. Remove the valve caps from both valves, and open them using 

a hexagonal Allen wrench.

8. Remount valve caps onto both of the valves.

9. Check for gas leaks from the four unions and from the valve 

caps. Test with electronic leak detector or with a sponge 
immersed in soapy water for bubbles.

NOTE

For additional charge of  various tubing lengths, 
refer to outdoor unit  nameplate.

1

2

3

4

5

6

7

8

9

10

11

12

1. Charging set

2. Vacuum pump

3. OUTDOOR UNIT

4. Service valve

5. Cap

6. Suction valve

7. Service valve*

8. Cap

9. Liquid valve

10. INDOOR UNIT

11. Suction flare connection

12. Liquid flare connection

*In some models only

When properly flared, the internal
surface of the flare will evenly shine
and be of even thickness. since the
flare part comes into contact with the
connections, carefully check the flare
finish.

1. To cut

   2. To remove burrs

 3. To flare

Improper flaring

Bar

Clamp handle

Handle

Yoke

Core

Red arrow mark

Bar

0-0.05 mm

Copper
pipe

Inclined

Surface
damaged

cracked

Uneven
thickness

Pipe

Reamer

Point down

CONNECT THE CABLE TO THE 
INDOOR AND OUTDOOR UNIT

5

If you used the piping kit, you can 
connected the cable with the 
connecter that in the cable.

To connect the indoor unit to the outdoor unit use the following electrical cables, protected for 
outdoor use:

1. Indoor unit terminal
2. Ground wire
3. Indoor twin wire cable
4. Indoor coil
5. Resistor

6. Twin wire cable
7. Multiple wire cable
8. Cable clamp
9. Outdoor twin wire 
    terminal

Cooling and heating model:
Multiple wire cable

2

5 wires x 1.0 mm  2.1-3.6kW

2

5 wires x 1.5 mm 5.0kW

2

2 wires x 0.5 mm  - for low voltage

Cooling only models:
Multiple wire cable

2

4 wires x 1.0 mm  2.1-3.6kW

2

4 wires x 1.5 mm 5.0kW

1. Prepare the multiple wire(7)cable 

ends for connection.

2. Open the grille, take away the 

terminals cover screw and open 
the terminals cover, take away the 
cable clamp screw and turn over 
the cable clamp.

3. Connect the cable ends to the 

terminals of the indoor and outdoor 
units.

4. Shape a loop and connect the 

yellow/green ground wire (2) to 
ground terminal screw of the indoor 
unit.

6

PIPE INSULATION

1. Please carry out insulation at pipe connection portion as mentioned in Indoor/ 

Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent 
water from going inside the piping.

2. If drain hose or connecting piping is in the room (where dew may form). please 

increase the insulation by using POLY-E FOAM with thickness 6 mm or above.

Please follow the steps below to take out front grille if necessary such as when 
servicing.

1. Set the vertical airflow direction louver to the horizontal position.

2. Slide down the three caps on the front grille as shown in the illustration at 

right, and then remove the three mounting screws.

3. Pull the lower section of the front grille towards you to remove the front grille.

HOW TO TAKE OUT FRONT GRILLE

When reinstalling the front grille , first
set the vertical airflow direction louver
to the horizontal position and then
carry out above steps 2-3 in the
reverse order.

Cap

Screw

(Move the vertical
vane to horizontal)

Vertical airflow
deflection louver

DISPOSAL OF OUTDOOR UNIT DRAIN WATER

If a drain elbow is used, the unit should be placed on a stand which is taller than 
3 cm.

CHECK THE DRAINAGE

Drain tray-
styr of oam

Open front panel and remove air filters.
(Drainage checking can be carried out without removing the front 
grille.)
Pour a glass of water into the drain tray-styrofoam.
Ensure that water flows out from drain hose of the indoor unit.

EVALUATION OF THE PERFORMANCE

Operate the unit at cooling operation mode for fifteen minutes or 
more.
Measure the temperature of the intake and discharge air.
Ensure the difference between the intake temperature and the 

o

discharge  is more than 8 C.

CHECK ITEMS

Is there any gas leakage at flare nut connections?

Has the heat insulation been carried out at flare nut 
connection?

Is the connecting cable being fixed to terminal 
board firmly?

Is the connecting cable being clamped firmly?

Is the drainage ok?
(Refer to "Check the drainage" section)

Is the earth wire connection properly done?

Is the indoor unit properly hooked to the installation 
plate?

Is the power supply voltage complied with rated 
value?

Is there any abnormal sound?

Is the cooling operation normal?

Is the thermostat operation normal?

Is the remote control's LCD operation normal?

5. Disconnect the resistor (5) from the indoor unit twin wire cable (3) and connect the twin wire 

cable (6) connector instead.

6. connect the other end of the twin wire cable (6) to the outdoor unit twin wire terminal (9).

7. Secure the multiple wire power cable with the  cable clamps.

8. Fasten the twin wire cable to the power cable  with cable ties.

4

2.1 kW

403

110

10

10

248

472

145

10

10

237

2.5  3.6 kW

500

150

10

10

293

5.0 kW

8

9

3(N)

4

5

6

A

1

4

5

3

6

7

B

2

4

5 6

3
N

-

N

Outdoor Unit

Indoor Unit

Discharge air

Unit's
hook

Installation
plate

Indoor unit

Hooks at
installation
plate

Piping

Drain hose

Cover for the 
right piping 

Cover for the 
bottom piping

Cover for the
left piping

Pull out the piping and hose

Piping

Drain hose

Move the drain hose near to 
arrow mark and tape it with 
piping in a position as mentioned 
in Fig. below

Sleeve for 
piping hole

Drain
hose

Piping

More than approx. 95 cm

Connecting
cable

Install the indoor unit

7

Drain elbow

Hose

Install the hose at
an angle so that
the water smoothly
 flows out.

Air filter

Air purifying filter

6

4

1

8

Summary of Contents for Alpha 12

Page 1: ...Service Manual Alpha Series REFRIGERANT R410A COOLING ONLY HEAT PUMP JANUARY 2005 Indoor Units Outdoor Units Alpha 7 CON 7 Alpha Alpha 9 GCN 9 Alpha Alpha 12 GCN 12 Alpha...

Page 2: ...iginal and changed pages are Original 0 15 December 2004 Total number of pages in this publication is 93 consisting of the following Page No Revision No Page No Revision No Page No Revision No Title 0...

Page 3: ...1 4 OUTLINE DIMENSIONS 4 1 5 PERFORMANCE DATA PRESSURE CURVES 5 1 6 SOUND LEVEL CHARACTERISTICS 6 1 7 ELECTRICAL DATA 7 1 8 WIRING DIAGRAMS 8 1 9 ELECTRICAL CONNECTIONS 9 1 10 REFRIGERATION DIAGRAMS 1...

Page 4: ...1 2 Main Features The Alpha series bene ts from the most advanced technological innovations namely R410A models Microprocessor control Infrared remote control with liquid crystal display Indoor large...

Page 5: ...ptional Active carbon lter optional 1 5 Control The microprocessor indoor controller and an infrared remote control supplied as standard provide complete operating function and programming For further...

Page 6: ...For low ambient working conditions in cooling an ASK can be installed inside the outdoor unit This kit allows cooling operation down to outdoor temp of 10 C by gradually controlling the outdoor fan s...

Page 7: ...et units 36 Stacking height units 9 levels OUTDOOR Refrigerant control Capillary tube Compressor type model Rotary TOSHIBA PA82X1C 4DZDE Fan type quantity Propeller direct x 1 Fan speeds H L RPM 850 A...

Page 8: ...OUTDOOR Refrigerant control Capillary tube Compressor type model Rotary TOSHIBA PA108X1C 4FZDE Fan type quantity Propeller direct x 1 Fan speeds H L RPM 750 Air ow H L m3 hr 1370 Sound power level H...

Page 9: ...ng height units 9 levels OUTDOOR Refrigerant control Capillary tube Compressor type model Rotary TOSHIBA PA145X2C 4FT Fan type quantity Propeller direct x 1 Fan speeds H L RPM 830 Air ow H L m3 hr 145...

Page 10: ...ts and EN 14511 Cooling Indoor 27o C DB 19o C WB Outdoor 35 o C DB Heating Indoor 20o C DB Outdoor 7o C DB 6o C WB 3 1 Operating Limits 3 1 1 R410A Indoor Outdoor Cooling Upper limit 32o C DB 23o C WB...

Page 11: ...4 1 OUTLINE DIMENSIONS Revision Y05 01 Service Manual ALPHA 4 OUTLINE DIMENSIONS 4 1 Indoor Unit Apha 7 9 4 2 Indoor Unit Alpha 12...

Page 12: ...4 2 OUTLINE DIMENSIONS Revision Y05 01 Service Manual ALPHA 4 3 Indoor Unit Alpha 17 4 4 Outdoor Unit CON 7 Alpha...

Page 13: ...4 3 OUTLINE DIMENSIONS Revision Y05 01 Service Manual ALPHA 4 5 Outdoor Unit GCN 12 Alpha AI R O U TLET AI R I N TAKE...

Page 14: ...1 43 1 53 1 62 1 59 1 63 PI 0 56 0 57 0 57 0 58 0 58 30 TC 1 87 2 01 2 17 2 26 2 34 SC 1 36 1 47 1 58 1 55 1 61 PI 0 61 0 62 0 62 0 63 0 63 35 TC 1 72 1 87 2 05 2 15 2 23 SC 1 28 1 39 1 52 1 50 1 56...

Page 15: ...13 0 50 1 09 0 54 1 04 0 56 7 1 21 0 52 1 17 0 54 1 13 0 57 2 1 29 0 52 1 25 0 55 1 20 0 59 2 1 57 0 55 1 51 0 58 1 44 0 62 6 2 21 0 59 2 15 0 63 2 07 0 67 10 2 41 0 62 2 34 0 66 2 28 0 71 15 2 60 0 6...

Page 16: ...28 30 32 34 36 38 15 20 25 30 35 40 46 Outdoor Temp DB o C Discharge Pressure Bar g 15 21 WB DB C 17 24 WB DB C 19 27 WB DB C 21 29 WB DB C 23 32 WB DB C Suction Pressure VS Outdoor Temp 6 5 7 0 7 5 8...

Page 17: ...arge Pressure VS Outdoor Temp 18 20 22 24 26 28 30 32 34 36 10 5 0 5 10 15 20 Outdoor Temp WB o C Discharge Pressure Bar g 25 DB C 20 DB C 15 DB C Suction Pressure VS Outdoor Temp 4 0 5 0 6 0 7 0 8 0...

Page 18: ...90 1 95 PI 0 72 0 73 0 73 0 74 0 74 30 TC 2 40 2 59 2 80 2 90 3 01 SC 1 63 1 76 1 90 1 86 1 93 PI 0 78 0 79 0 80 0 81 0 81 35 TC 2 22 2 40 2 64 2 77 2 88 SC 1 53 1 67 1 82 1 80 1 87 PI 0 84 0 86 0 87...

Page 19: ...49 0 74 1 43 0 79 1 37 0 83 7 1 60 0 76 1 54 0 80 1 49 0 85 2 1 70 0 77 1 64 0 82 1 58 0 86 2 2 07 0 81 1 98 0 86 1 90 0 91 6 2 91 0 87 2 83 0 93 2 73 0 99 10 3 17 0 92 3 08 0 98 3 00 1 05 15 3 42 0 9...

Page 20: ...28 30 32 34 36 38 15 20 25 30 35 40 46 Outdoor Temp DB o C Discharge Pressure Bar g 15 21 WB DB C 17 24 WB DB C 19 27 WB DB C 21 29 WB DB C 23 32 WB DB C Suction Pressure VS Outdoor Temp 6 5 7 0 7 5 8...

Page 21: ...ressure VS Outdoor Temp 20 22 24 26 28 30 32 34 36 38 40 10 5 0 5 10 15 20 Outdoor Temp WB o C Discharge Pressure Bar g 25 DB C 20 DB C 15 DB C Suction Pressure VS Outdoor Temp 3 0 4 0 5 0 6 0 7 0 8 0...

Page 22: ...58 2 65 PI 0 96 0 97 0 98 0 98 0 99 30 TC 3 19 3 43 3 71 3 85 3 99 SC 2 21 2 38 2 57 2 52 2 62 PI 1 04 1 05 1 07 1 07 1 08 35 TC 2 94 3 19 3 50 3 68 3 82 SC 2 08 2 26 2 47 2 44 2 54 PI 1 12 1 14 1 16...

Page 23: ...4 35 1 38 20 4 82 1 24 4 71 1 35 4 57 1 45 LEGEND TH Total Heating Capacity kW PI Power Input kW WB Wet Bulb Temp o C DB Dry Bulb Temp o C ID Indoor OD Outdoor 5 6 Capacity Correction Factor Due to T...

Page 24: ...6 28 30 32 34 36 38 15 20 25 30 35 40 46 Outdoor Temp DB o C Discharge Pressure Bar g 15 21 WB DB C 17 24 WB DB C 19 27 WB DB C 21 29 WB DB C 23 32 WB DB C Suction Pressure VS Outdoor Temp 6 0 6 5 7 0...

Page 25: ...Pressure VS Outdoor Temp 20 22 24 26 28 30 32 34 36 38 10 5 0 5 10 15 20 Outdoor Temp WB o C Discharge Pressure Bar g 25 DB C 20 DB C 15 DB C Suction Pressure VS Outdoor Temp 3 0 4 0 5 0 6 0 7 0 8 0...

Page 26: ...e Level Spectrum Measured as Figure 1 Alpha 7 Alpha 9 BAND CENTER FREQUENCIES Hz APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 OCTAVE BAND SOUND PRESSURE LE...

Page 27: ...HEARING FOR CONTINUOUS NOISE NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 OCTAVE BAND SOUND PRESSURE LEVEL dB re 0 002 MICRO BAR BAND CENTER FREQUENCIES Hz APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOIS...

Page 28: ...CENTER FREQUENCIES Hz APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 OCTAVE BAND SOUND PRESSURE LEVEL dB re 0 002 MICRO BAR BAND CENTER FREQUENCIES Hz APPRO...

Page 29: ...6 5 7 7 Circuit Breaker A 10 10 10 Power Supply Wiring No X Cross Section mm2 3x1 0 mm2 3x1 0 mm2 3x1 0 mm2 Interconnecting Cable RC Model No X Cross Section mm2 5x1 0 mm2 2x0 5 mm2 OCT senser 5x1 0 m...

Page 30: ...8 1 WIRING DIAGRAMS Revision Y05 01 Service Manual ALPHA 8 WIRING DIAGRAMS 8 1 Indoor Unit Alpha 7 9 12...

Page 31: ...8 2 WIRING DIAGRAMS Revision Y05 01 Service Manual ALPHA 8 2 Outdoor Unit CON 7 8 3 Outdoor Unit CON 7 with easy connection kit...

Page 32: ...8 3 WIRING DIAGRAMS Revision Y05 01 Service Manual ALPHA 8 4 Outdoor Unit GCN 9 12 8 5 Outdoor Unit GCN 9 12 with easy connection kit REV 03...

Page 33: ...9 1 ELECTRICAL CONNECTIONS Revision Y05 01 Service Manual ALPHA 9 ELECTRICAL CONNECTIONS 9 1 Alpha 7 9 12...

Page 34: ...OOLING MODE Service Outdoor coil Sensor Capillary tube Strainer Check valve OUTDOOR UNIT valve Reverse tube Capillary Compressor Outdoor coil Sensor tube Capillary Reverse Strainer valve Compressor tu...

Page 35: ...AGRAMS Revision Y05 01 Service Manual COMPACT 10 2 Cooling Only Models 10 2 1 Alpha 7 9 12 Outdoor coil Strainer Capillary tube Compressor Service port OUTDOOR UNIT connection Valves Flared Indoor coi...

Page 36: ...11 13 11 13 1 Valve Protection Cap end 2 Refrigerant Valve Port use Allen wrench to open close 3 Valve Protection Cap 4 Refrigerant Valve 5 Service Port Cap 6 Flare Nut 7 Unit Back Side 8 Copper Tube...

Page 37: ...n is designed for service applications and is common to the following groups of air conditioners ST RC group Cooling only cooling and heating by heat pump SH group Cooling and heating by heat pump and...

Page 38: ...3 Medium High Water Level LEVEL4 Over ow Level Max Maximum Min Minimum min Minute time NA Not Applicable OCP Outdoor Condensation Pump OCT Outdoor Coil Temperature RT3 sensor OF OFAN Outdoor Fan OPER...

Page 39: ...ONTROL SYSTEM Revision Y05 01 Service Manual ALPHA 12 3 Main PCB Controller 12 3 1 COMPACT 7 12 LEXAN COMPACT 7 22 Display PCB STBY LED IR RECIVER MODE BUTTON OPR LED STBY LED OPR LED IR RECIVER MODE...

Page 40: ...interval between IFAN speed change in H M L Mode is 1 sec IFAN speed in Heat Cool Autofan Mode is determined according to the following table T IFAN Speed T 2 HIGH 2 T 1 MED 1 T LOW where in Heat Mode...

Page 41: ...s below 30o c b Thermistor is shorted The thermistor reading is over 75o c c Thermistor Temp reading doesn t change irrelevant for RT1 i This test is performed only once after a unit is switched from...

Page 42: ...The same is also applied to the OCT fault ii RAT thermistor is disconnected or shorted The RAT will be derived from the ICT by using the equations Heat Mode RAT ICT 2 3 Cool Mode RAT ICT 4 Notes In ca...

Page 43: ...ted by RAT in normal operation or RCT R C sensor in I FEEL mode 2 The resolution of RT is 1o c RT is activating COMP WVL if RT SPT and RT is stopping COMP WVL if RT SPT 3 Indoor Coil Temp is detected...

Page 44: ...el On or Off Control function Maintains room temp at desired level by comparing RT and SPT RT SPT o c 3 2 1 0 1 2 ON OFF ON OFF USER FAN SPEED ON OFF COMP WVL OFAN IFAN RV Note 1 IFAN is always runnin...

Page 45: ...Autofan Mode Cool Auto at cooling Temp Selected desired temperature Fan Auto Timer Any I Feel On or Off Control function Maintains room temp at desired level and controls the IFAN speed for optimal co...

Page 46: ...e COMP is switched ON In this case the IFAN will be started at low speed Notes 1 In SH or RC group if HE is set to OFF due to low ICT IFAN will be switched to LOW and will be turned OFF after 30 sec 2...

Page 47: ...ICT 45o c In SH or RC group HE operation is limited by the following graph Back up mode for SH group After COMP has been working for 5 minutes HE IFAN are activated even if the ICT is still below 35o...

Page 48: ...ode Heat Auto at heating Temp Selected desired temperature Fan HIGH MED LOW Timer Any I Feel On or Off Control function Maintains room temp at desired level by comparing RAT or RCT to SPT RT SPT o c 2...

Page 49: ...Autofan Mode Heat Auto at heating Temp Selected desired temperature Fan Auto Timer Any I Feel On or Off Control function Maintains room temp at desired level by controlling COMP IFAN and OFAN RT SPT...

Page 50: ...TEM Revision Y05 01 Service Manual ALPHA 12 6 6 OFAN operation is controlled by the graph below when 1 RAT SPT 2o c AND 2 ICT 45o c AND 3 COMP is ON Otherwise OFAN runs together with COMP OCT o c 3 2...

Page 51: ...at low speed The proper Auto Heat mode or Auto Cool will be started whenever the RT reaches SPT 1o c or SPT 1o c respectively For RC SH units Mode change between Auto Heat Auto Cool Modes is possible...

Page 52: ...Any Timer Any I Feel On or Off Control function Maintains room temp at desired level by selecting between cooling and heating modes RT SPT o c 3 2 1 0 1 2 3 ON OFF ON OFF H M L OFF L OFF ON OFF ON OFF...

Page 53: ...ery 15 min of continuous COMP operation When Dry is OFF the COMP is forced ON for 6 min longer than the 3 min Min COMP On time after every 15 min of continuous COMP OFF time When Dry is changed from O...

Page 54: ...OFAN stop for 10 min minimum Notes When J7 is closed connected OFAN cycling is cancelled and the set temperature for COMP OFAN cut out and cut in are changed COMP OFAN are forced OFF when ICT 6o c and...

Page 55: ...N IFAN OPER LED 52 55 61 66 L COMP is forced OFF OFAN is forced ON IFAN forced to LOW 68 OFAN follow operation of COMP COMP is forced OFF OFAN is forced ON For all models except WAX P2000 For WAX P200...

Page 56: ...ng COMP RV operation Scope This new deicer is designed to operate at extreme temp conditions The deicing cycle could be triggered from 1 OCT temp and time between two consecutive deicing cycles 2 Dete...

Page 57: ...o Low Speed BLINK ON OPER LED Notes At the rst COMP activation after SB or OFF if OCT 0o c then DI 10 min else DI 40 min In the following Deicing cycles the time interval between two Deicing cycles ac...

Page 58: ...force Off COMP is forced OFF For all models except WAX For WAX model ON BLINK OPER LED Notes IFAN HE1 and HE2 will be activated according to the relevant Heating Mode Sect In case of any malfunction...

Page 59: ...ndicator is blinked to indicate the situation The LED keeps blinking until the timer settings can be reloaded from a R C message Note If all timers are inactive the system will not be forced OFF after...

Page 60: ...re according to the following table Forced operation mode Pre set Temp for WMZ WMF WNG models Cooling 22 C Heating 28 C Note While under the forced operation the temperature compensation schedule The...

Page 61: ...ER function Therefore the TIMER LED is activated similar to TIMER function 12 12 1 Adjustment in Sleep Mode 1 in cool auto cool or dry modes the SPT adjustment is positive from 0 to 3o c 2 In heat or...

Page 62: ...to the starting of Sleep the Sleep time is extended And instead of going to SB at the 7th hour the A C will work until reaching the Off time Case 3 is an exception to case 2 The Sleep Mode will not be...

Page 63: ...E BUTTON INDOOR FAN SPEED TEST SELF TEST FLOW CHART Step 1 Step 2 Step 3 FOR CONTROLLER VERSION 4V5 OR HIGHER COOL HEAT COMPRESSOR OUTDOOR FAN R V LOW MEDIUM HIGH TIMER OPERATE STANDBY BUZZER TEST ONE...

Page 64: ...ode LOW IFAN no I FEEL Sleep or any other timer settings Uncover the remote control IR transmitter and change the temperature settings If the display indoor unit receive the settings properly the foll...

Page 65: ...automatically f STEP 6 FREQUENCY TESTING If the frequency measuring process fails the COOL LED will turn ON In order to move to the next step press ON OFF button on the remote control g STEP 7 INPUT T...

Page 66: ...for 60 sec Values of Sensors Temperature VS Voltage DC Temp C Voltage V Temp C Voltage V Temp C Voltage V Temp C Voltage V 20 4 554 2 3 744 24 2 555 46 1 487 19 4 529 3 3 695 25 2 5 47 1 447 18 4 502...

Page 67: ...to announce that a R C infrared signal has been received and stored Blinks continuously during OCT High Pressure Protection Mode ICT High Pressure Protection Mode Deicing in Heating Mode Water Over F...

Page 68: ...A C STATE before clock is changed CLOCK STATE before clock is changed CLOCK ACTION clock is changed A C NEW STATE after clock is changed ON 1 0 OFF OFF 0 1 ON OFF by interrupt 1 1 0 OFF ON by interru...

Page 69: ...the main P C B If there is voltage replace capacitor or motor 5 The outdoor fan does not function correctly Check the voltage between out door fan terminals on the main P C B There is voltage between...

Page 70: ...or faulty Motor windings are shorted Check voltage repair wiring if necessary Check fan wheel if it is tight enough on motor shaft tighten if necessary 13 Partial limited air supply at indoor unit Lac...

Page 71: ...14 1 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y05 01 Service Manual ALPHA 14 EXPLODED VIEWS AND SPARE PARTS LISTS 14 1 Indoor Unit Alpha 7 9 12 5 6 7...

Page 72: ...7 453070700 Coil Assy 1 8 126233 Nut brass 1 4 1 9 434530 Nut brass 3 8 1 10 4523526 Beraing Assy 1 11 4523523 Fan Assy Plastic 1 12 4523505 Motor IOD 7 1 4527112 Motor IOD 9 1 4526649 Air Outlet Ass...

Page 73: ...3058200 Coil Assy 1 8 126233 Nut brass 1 4 1 9 434530 Nut brass 3 8 1 10 4523526 Beraing Assy 1 11 4527111 Fan Assy Plastic 1 12 4527112 Motor IOD 12 1 4527187 Air Outlet Assy Israel market 1 45278440...

Page 74: ...14 4 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y05 01 Service Manual ALPHA 14 4 Outdoor Unit CON 7 RC 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 2 33 32 31 29 30 28 20 21 22 23 24 27 25 26...

Page 75: ...13 453056700 Rubber grommet base plate 4 14 452964500 Compressor Assy PA82X1C 4DZDE R410A GMCC 1 15 4510677 Nut With Flange M8 D 24 GB6187 86 3 16 4524278 Wire assy 1 17 4516637 Out sensor Black 1 18...

Page 76: ...14 6 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y05 01 Service Manual ALPHA 14 6 Outdoor Unit CON 7 ST 3 5 4 6 7 8 9 10 11 12 13 14 15 16 17 18 2 32 31 30 28 29 27 19 20 21 22 23 26 24 25...

Page 77: ...ubber grommet base plate 4 13 452964500 Compressor Assy PA82X1C 4DZDE R410A GMCC 1 14 4510677 Nut With Flange M8 D 24 GB6187 86 3 15 4524278 Wire assy 1 16 453183600 Discharge Pipe Assy 1 17 453045400...

Page 78: ...ODED VIEWS AND SPARE PARTS LISTS Revision Y05 01 Service Manual ALPHA 14 8 Outdoor Unit CON 7 RC with easy connection kit 3 5 4 6 7 8 9 10 11 12 13 14 15 16 17 18 19 29 2 33 32 31 30 20 21 22 23 24 28...

Page 79: ...er grommet base plate 4 13 452964500 Compressor Assy PA82X1C 4DZDE R410A GMCC 1 14 4510677 Nut With Flange M8 D 24 GB6187 86 3 15 453112800 Power Cord Compressor 1 16 453122600 Discharge Pipe Assy 1 1...

Page 80: ...4 10 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y05 01 Service Manual ALPHA 14 10 Outdoor Unit CON 7 ST with easy connection kit 3 5 4 6 7 8 9 10 11 12 13 14 15 16 17 18 19 2 32 31 21 20 22 23 24 2...

Page 81: ...13 453056700 Rubber grommet base plate 4 14 452964500 Compressor Assy PA82X1C 4DZDE R410A GMCC 1 15 4510677 Nut With Flange M8 D 24 GB6187 86 3 16 453112800 Power Cord Compressor 1 17 4516637 Out sens...

Page 82: ...14 12 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y05 01 Service Manual ALPHA 14 12 Outdoor Unit GCN 9 12 RC...

Page 83: ...022 Cap Clip 1 14 201130 Nut For Capacitor 1 15 203008 Washer For Capacitor 1 16 455000108 Double patch Capacitor for fan motor 2uF 1 17 455000502 Compressor Capacitor With Screw 25uF CBB65 1 18 45309...

Page 84: ...Cap Clip 1 14 201130 Nut For Capacitor 1 15 203008 Washer For Capacitor 1 16 455000108 Double patch Capacitor for fan motor 2uF 1 17 455000504 Compressor Capacitor With Screw 35uF CBB65 1 18 4526452...

Page 85: ...14 15 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y05 01 Service Manual ALPHA 14 15 Outdoor Unit GCN 9 12 ST...

Page 86: ...lip 1 13 4518022 Cap Clip 1 14 201130 Nut For Capacitor 1 15 203008 Washer For Capacitor 1 16 455000108 Double patch Capacitor for fan motor 2uF 1 17 455000502 Compressor Capacitor With Screw 25uF CBB...

Page 87: ...ip 1 13 4518022 Cap Clip 1 14 201130 Nut For Capacitor 1 15 203008 Washer For Capacitor 1 16 455000108 Double patch Capacitor for fan motor 2uF 1 17 455000504 Compressor Capacitor With Screw 35uF CBB6...

Page 88: ...14 18 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y05 01 Service Manual ALPHA 14 18 Outdoor Unit GCN 9 12 RC with easy connection kit...

Page 89: ...8 Wire Clip 1 15 453080600 Terminal Socket Alpha Controller 1 16 201130 Nut For Capacitor 1 17 203008 Washer For Capacitor 1 18 453054400 Fixing plate Terminal plate 1 19 455001002 Combinated Capacito...

Page 90: ...Terminal Block 1 14 4511168 Wire Clip 1 15 453080600 Terminal Socket Alpha Controller 1 16 201130 Nut For Capacitor 1 17 203008 Washer For Capacitor 1 18 453054400 Fixing plate Terminal plate 1 19 455...

Page 91: ...14 21 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y05 01 Service Manual ALPHA 14 21 Outdoor Unit GCN 9 12 ST with easy connection kit...

Page 92: ...oles Terminal Block 1 14 4511168 Wire Clip 1 15 453080600 Terminal Socket Alpha Controller 1 16 201130 Nut For Capacitor 1 17 203008 Washer For Capacitor 1 18 453054400 Fixing plate Terminal plate 1 1...

Page 93: ...e Clip 1 15 453080600 Terminal Socket Alpha Controller 1 16 201130 Nut For Capacitor 1 17 203008 Washer For Capacitor 1 18 453054400 Fixing plate Terminal plate 1 19 455001001 Combinated Compressor Ca...

Page 94: ...16 1 APPENDIX A Revision Y05 01 Service Manual ALPHA APPENDIX A INSTALLATION AND OPERATION MANUAL INSTALLATION AND OPERATION MANUAL ALPHA 7 9 12...

Page 95: ...TALIANO ENGLISH AIR CONDITIONER SPLIT WALL MOUNTED CLIMATIZADOR SPLIT MURAL ESPANOL M A N U A L E D I U T I L I Z Z O E D I P R O G R A M M A Z I O N E FRANCAIS 5 CLIMATISEUR SPLIT MURAL M A N U E L D...

Page 96: ...AIR CONDITIONER SPLIT WALL MOUNTED PROGRAMMING AND OPERATING...

Page 97: ...tion with auto fan mode Auto cooling heating operation Dry operation Selecting the temperature Sleep function Timer operation Automatic vertical air swing Turning off the air conditioner Current clock...

Page 98: ...nditoning installer observing good regrigeration practice Electrical connections and power cord replacement should only be made by authorized electricians and in accordance with electrical regulations...

Page 99: ...ators and on unit control 5 Horizontal air flow defecting louvers 6 Suction line 7 Liquid line 8 Power cable 9 Control wire 10 Condensate tube 11 Outdoor unit air intake 12 Outdoor unit air outlet 13...

Page 100: ...KEEP In HEATING and in AUTO FAN the fan will be turned off when the compressor is not in operation and will not be restarted unless the indoor coil reaches adequate temperature This HOT KEEP feature...

Page 101: ...OPERATION The air conditoner can be aturned ON for COOLING or HEATING or be turned OFF directly form the indoor unit display panel without the use of the remote control The air louvers is automaticall...

Page 102: ...INGERTIPS Aim at the infrared signal receiver on the room air conditioner when operating The remote control signal can be received at a distance of up to about 7m Be sure that there are no obstruction...

Page 103: ...n or turn off for COOLING or HEATING without the use of remote control OPERATION INDICATOR Lights up during operation Blinks once to announce that the remote control infrared signal has been received...

Page 104: ...OOL HEAT DRY FAN FAN SPEED and AUTO FAN button Room temperature UP button Room temperature DOWN Button SLEEP button Airflow direction AUTO CONTROL button TIMER button TIMER UP button TIMER DOWN button...

Page 105: ...nction The fan will be turned off when the indoor coil temperature is not sufficiently hot to prevent uncomfortable cold air drafts AUTO ON OFF MODE MODE MODE MODE 8 OPERATION PROCEDURE Select the ven...

Page 106: ...ither horizontal air delivery for cooling or to vertical air delivery for heating At start the air conditioner will select its mode of operation according to the room temperature and the temperature s...

Page 107: ...respectively Press Set button 13 to activate the timer Operation stops at 18 00 IV CLEAR Use this mode to cancel timer operation Press CLEAR button 14 timer operation will terminate and the LCD displ...

Page 108: ...he remote control LCD will display the clock time The last operating set up will be kept for the next operation CURRENT CLOCK TIME SET Clock setting is performed when batteries are inserted The remote...

Page 109: ...reezing conditions Resumes operation automatically High outdoor temperature Outdoor coil overheating Stops compressor when approaching over heating conditions Resumes operation automatically Operating...

Page 110: ...cedure is used for replacing the active carbon filter when supplied DO NOT OPERATE THE UNIT WITHOUT FILTERS Wipe the unit with a soft dry cloth or clean it using a vacuum cleaner Do not use hot water...

Page 111: ...osed directly to air drafts During prolonged operation ventilate the room occasionally by opening a window from time to time In a power failure the microprocessor memory is retained When restarted ope...

Page 112: ...er Do not insert any objects in the air outlet of the indoor or outdoor units Do not splash water on the air conditioner IF NOISE IS HEARD There may be hissing sound during operation or just after shu...

Page 113: ...remote control command Check for obstruction between unit and remote control Clear if needed Get closer to unit Dim lights fluorecents especially IR signal does not reach unit Distance between remote...

Page 114: ...SELECT THE BEST LOCATION Refer to Select the best location section 1 HOW TO FIX INSTALLATION PLATE 2 The mounting wall is strong and solid enough to prevent it from the vibration 1 FOR THE RIGHT REAR...

Reviews: