2007/6/22  -  A 

 

Alarm Silence 

 

Once the alarm is sounding, pressing the Test button will put the Smoke Detector into Alarm Silence 
mode for 10 min. and the alarm will be stopped. 

 

During this 10-min. Alarm Silence period, the LED will flash once per second.   

 

After this 10-min. period is over, the Smoke Detector will sound a 2-tone beep and then returns to 
normal operation mode. If the Smoke concentration is still over the set threshold value, the Smoke 
Detector will sound the warning alarm again. 

Taking New Reference Value 

As the operation condition of the smoke detector may vary after being installed for some time, you may wish to 
take a new reference value to ensure the best use of the smoke detector. To do this: 

 

Press 10 seconds on the TEST button and hold until the LED start to flash. The SDA-9 will sound 2 short 
beeps then follow the process described in calibration process to take the new reference value   

 

Every time re-insert the batteries, the SDA-9 will also take the new reference value following the 
warming and calibration process. 

Installation Note 

It is recommended that the installation site be in the center area of the ceiling and only to be 
used indoors. The operational temperature range for the device is 10 – 40°C.   

Do not locate the detector in the following locations: 

 

The Kitchen – Smoke from cooking might cause an unwanted alarm. 

 

Near a ventilating fan, florescent lamp or air-conditioning equipment – air drafts 
from them may affect the sensitivity of the detector. 

 

Near ceiling beams or over a cabinet – stagnant air in these areas may affect 

 

  the sensitivity of the detector.   

 

In the peak of an “A” frame type of ceiling.   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for SDA-9

Page 1: ...2007 6 22 A SDA 9 OWNERS MANUAL A Ar rt t 3 36 6 3 32 27 75 5...

Page 2: ...are inserted and the Smoke Detector is in warming and calibration process the LED will flash for 8 22 min 2 Test Button The Test Button is pressed in the following situations Learning In the Smoke Det...

Page 3: ...transmitting 3 If the Control Panel successfully receives the signal the panel will respond accordingly to indicate the completion of the learning in process Please refer to the manual of the panel N...

Page 4: ...not received the signal from the Smoke Detector for a preset period of time the Control Panel will indicate it on its display to show that particular Smoke Detector is experiencing an out of signal pr...

Page 5: ...10 seconds on the TEST button and hold until the LED start to flash The SDA 9 will sound 2 short beeps then follow the process described in calibration process to take the new reference value Every t...

Page 6: ...4 Monteringsh l 5 Monteringsplatta 6 H llare Batterier Anv nd 3st AA Alkalibatterier Dessa batterier har en livsl ngd p ca fyra r Vid l g batteriniv skickar r kdetektorn regelbundet signaler till larm...

Page 7: ...essen r avslutad steg 4 5 N r uppstartnings och inst llningsperioden r avslutad st ll in Larm Panelen p Testa Sensorer tryck OK Best m en l mplig plats f r montering av r kdetektorn tryck d rifr n ned...

Page 8: ...r kdetektorn manuellt med testknappen r referensv rdet h gre en normalt kommer din r kdetektor forts tta att skicka ut larmsignaler varannan minut Denna tv minuts period avslutas automatiskt s snart r...

Page 9: ...inte r kdetektorn enligt f ljande I K ket R k fr n din matlagning kan orsaka falsklarm R kdetektorn k nslighet kan p verkas om du installerar den I n rheten av en fl kt lysr r eller i n rheten av luf...

Page 10: ...ot ovat loppumassa savutunnistin l hett tavallisten toimintasignaalien lis ksi my s tietoa alhaisesta pariston tilasta ohjauspaneelille LED valo vilkkuu joka 30 sekunnin aikav lein ja hiljainen piippa...

Page 11: ...i lyhyit piippauksia Poista t ll in tunnistimesta paristot ja aloita 30 sekunnin odotuksen j lkeen uudelleen askeleesta 1 Tiedotus Kalibroinnin aikana Testi n pp imen toiminto on estetty Jos kolmannen...

Page 12: ...paneelille Kun signaali on l hetetty SDA 9 summeri soi ja LED valo vilkkuu 10 sekunnin aikana T m n 10 sekunnin aikajakson j lkeen SDA 9 tarkistaa uudelleen ilman savupitoisuuden Jos savunpitoisuus yh...

Page 13: ...aan paristot uudelleen SDA 9 ottaa uuden viitearvon k ynnistys ja kalibrointiaskelien j lkeen Asennussuositukset On suositeltavaa ett laite asennetaan katon keskelle l asenna tunnistinta seuraaville p...

Page 14: ...t 3 Skru fast braketten i taket minimum 0 7 meter fra vegg Sett hoveddelen p braketten og vri mot klokken for feste 4 G til sentralenheten sl kode for pne programmeringsmenyen Gj res ved trykke 1234 1...

Page 15: ...r 50 m neder I tillegg til lokalt signal fra detektoren vil lavt batteri vises p sentralenhet samt at signal vil bli overf rt til vaktsentral dersom sentralenheten er tilknyttet en slik tjeneste Utl s...

Page 16: ...2007 6 22 A TECHNICAL DATA Power 3st AA 1 5V LR6 Battery Life 4 years Range 15m to 20m through walls and ceilings Frequency 868 MHz Dimensions 110mm L 110mm W 570mm H Art nr 36 3275...

Page 17: ...pskrav och vriga relevanta best mmelser som framg r av direktiv 1999 5 EG och RoHs 2002 95 EG Intyg f r Norge DSB 235 0209 CE 0678 At the end of it s life those products should NOT be disposed of in h...

Reviews: