9
6. INSTALLATION MODE
When entering Installation mode, the chilling device and pump will immediately be turned off (if they are
on) and will not be permitted to be turned on while the controller remains in any of the setup menus. On
exiting the ‘Installation’ mode the controller will revert to the ‘Normal’ mode and follow the same procedure
as if first entering that mode, the display will reflect this.
•
LANGUAGE (English, French, German, Spanish and Russian)
•
UNITS (temperature units; centigrade or Fahrenheit)
•
CLOCK (set current time)
•
TIMER (four-time settings for switching the chilling device
‘On’
and
‘Off’
)
•
PROBE CAL (Temperature calibration adjustment)
•
MODBUS (Set Baud rate, address and parity for BMS connection)
•
FACTORY (Access restricted)
•
EXIT
6.1 Language Setup
Enter the
‘INSTALLATION’
mode by touching the ‘M’ button key repeatedly until
‘INSTALLATION’
appears at the top of the display then touch the
‘O.K’
button key.
Touch the
‘UP’ / ‘DOWN’
button keys until the desired language is displayed then touch the
‘O.K’
button
key to select