The Flow-Line heater is factory set to accept input water from the left and exiting on the right, this can be 
reversed by rotating the flow switch 180° (i.e.  ½ turn).  

Warning! 

The flow switch paddle can be damaged when reversing the flow direction if it is lifted by 

more than 5-mm from its housing and turned with force. If the flow switch has been rotated it is important 
to ensure that it is finally locked down in the correct orientation perpendicular (at right angles) to the flow 
of water.  
The flow rate of water entering the heater 

must not 

exceed 13,000-litres per hour (2,860 Imp Gallons per 

hour. A higher flow rate 

will

 require the installation of a by-pass to prevent damage to the heating elements. 

The heater will not operate with a flow rate of less than 1,000-litres per hour (220 Imp Gallons per hour). 

E

LECTRICAL

 C

ONNECTION

 

The heater must be installed in accordance with the country / regional requirements & regulations. In any 
event the work must be carried out by a qualified electrician who will provide a certificate of conformity 
upon completion of the work. The power supply 

must

 be fitted with a RCD. 

The heating element(s) in the Flow-Line heater are pre-wired to the main terminal block and are ready to be 
connected via a contactor. 

P

OWER

 R

EQUIREMENTS

 

Power Output  Single Phase 

Voltage 

Amp 

2-kW 

230V 

3-kW 

230V 

13 

4.5-kW 

230V 

20 

6-kW 

230V 

27 

9-kW 

230V 

40 

12-kW 

230V 

53 

Power Output 

3 Phase 
Voltage 

Amp 

6-kW 

400V 

9-kW 

400V 

13 

12-kW 

400V 

18 

15-kW 

400V 

22 

18-kW 

400V 

26 

C

ONTACTOR

 C

ONTROL

 C

IRCUIT

 

The pre-wired control circuit is terminated within the electrical enclosure, all control circuit components 
have been factory pre-wired and provide a single volt free switch output (see wiring diagram attached). 
Control Components Include: 

Quantity 

Description 

0˚C to 40˚C Control Thermostat  

55˚C Pre-Set High Limiting Manual Reset Thermostat  

Flow Switch Pre-Set 1,000-litres per hour (220 Imp Gallons per hour). 

Control Circuit Important Electrical Data: 

Limited by the flow switch (reed switch)  
Contact Rating - 90.0 W/VA 
Switching Current MAX - 1.0 Amp 
Switching Voltage MAX - 230V AC 
 
The control circuit includes a transil spike voltage protection 