ELCOS SRL 

- Parma  - CAM-432 - MAN - EN

1

AUTOMATIC GENSET CONTROL UNIT WITH 

DIESEL OR PETROL ENGINE 

TYPE CAM-432

COMPLETE WITH:

• three-phase voltmeter check a three-phase mains  a two-phase genset

• texts in 6 languages: Italian, English, French, German, Spanish and Portuguese.

• automatic supervision of faults

• glow plugs control

• starter control

• remote commands with contacts (startup- stop - test)

• EJP-functions

• easy programming  by dip switches

• available input for anomaly

• clock for programming the start up or stopping of the genset

• programmable weekly selftest

• anomaly historical record (including data from the last 100 anomalies)

• automatic battery charger(1A)

• serial port RS232

This carries out the control and command function of a generator set, maintains the charge of the starter 

battery and operates the contactors of the mains and of the generator so that power can be supplied to the 

power users. It is constructed solely for built-in installation on an electric switchboard and to be connected 

to other components (contactors, fuses, overload switches, etc...) that the installer will have prepared to 

complete the system.

INS

TRUC

TION   AND  USER  MANU

AL

COMPLETE WITH DISPLAY TO

SHOW:

• useful signals for

  generator set management.

• 

Instruments:

   3 mains voltmeters

   Generator voltmeter (TWO-PHASE)

   3 ammeters main/genset 

   generator frequency meter

   total hour meter 

   partial hour meter

   battery voltmeter

   fuel level indicator

Summary of Contents for CAM-432

Page 1: ...ast 100 anomalies automatic battery charger 1A serial port RS232 This carries out the control and command function of a generator set maintains the charge of the starter battery and operates the contactors of the mains and of the generator so that power can be supplied to the power users It is constructed solely for built in installation on an electric switchboard and to be connected to other comp...

Page 2: ...ATING MODE FLASHES WHEN ENGINE OVERLOAD IS TRIGGERED PRESS TO SHOW THE INSTRUMENTS AVAILABLE FAULT STOPPING DUE TO OVERFREQUENCY MAINS VOLTAGE IS PRESENT MAINS IS CONNECTED TO THE USER GENERATOR IS PLUGGED TO THE USER GENERATOR VOLTAGE IS PRESENT PRESS TO SELECT THE FUNCTIONS OF AUT OFF MAN TEST THE ENGINE IS RUNNING STOPPING DUE TO ENGINE OVERHEATING STOPPING DUE TO INSUFFICIENT OIL PRESSURE KEY ...

Page 3: ...adjustable The COOLING TIME programmed to 120 sec then allows the engine to be cooled easily before it is stop ped Press button until the warning led comes on The engine cannot be started in any way and if running the engine is stopped without carrying out engi ne cooling The mains contactor stays closed The LEDs and the instruments are active On pressing key up the lighting we obtain the engine s...

Page 4: ...e P1 of the voltage and frequency of the battery charger alter nator PERMANENT MAGNETS or PRE EXCITATION and from the frequency and residual voltage of the generator When detection has been made it disconnects the starter motor and lights the LED By pressing the key the protection devices and all the stopped functions are re activated Blocks the start cycle if the motor is not started after the wh...

Page 5: ...HOUR METER The emergency stop can be activated in all working conditions by mounting one or more click down push button The stop is immediate without engine cooling enables the general alarm and is shown on the display Do not use the emergency push button linked to a stop system that is not energized when the unit is running EMERGENCY STOP REMOTE CONTROLS START OR TEST STOP EMERGENCY EJP FUNCTION ...

Page 6: ...mer ENGINE TYPE STOP SYSTEM SELEC TION WEEKLY SELF TEST GENERA TOR FRE QUENCY MAINS AND GENERA TOR VOLTAGE Connect the jumper 5E 6E if the emergency button is not fitted 1 5mm MIN 5m MAX Colour bridge Black When you connect terminal remove the BLACK bridge MAINS DETECTION Colour bridge Red Remove to deactivate the internal mains detection ENGINE RUNNING DETECTION NEVER INSTALL THE EMERGENCY PUSH B...

Page 7: ...See CHOOSING THE NUMBER OF AMMETERS on page 8 of the PROG manual ENGINE RUNNING THRESHOLD ADJUSTMENT Adjustment is not normally neces sary If it is necessary perform the following opera tions Start the engine manually and bring it down to minimum speed Turn the potentiometer anti clockwise until the indicator lights up TEST REMOTE CONTROLS 50m max CALL STARTING Shown by the START on the display 1 ...

Page 8: ...oltage failure undervoltage and overvoltage When voltage in three phases is detected with value within the preset limits after the mains ACCEPPTANCE DELAY programmed to 40 sec the generator set stops for the starting and stopping procedures see automatic operation on page 3 When voltages in the two phases of the running generator set are detected with values within the preset limits after the GENE...

Page 9: ...ELCOS SRL Parma CAM 432 MAN EN 9 REMARKS ...

Page 10: ...ELCOS SRL Parma CAM 432 MAN EN 10 REMARKS ...

Page 11: ... stressing the electronic board Do not allow pieces of copper wire or other metal residues to fall onto the control unit Never disconnect the battery terminals with the engine running Strictly avoid using a battery charger for emergency starting the control unit may get damaged To protect the safety of people and equipment disconnect the terminals of the electrical system from the battery poles be...

Page 12: ...range 50 253Vac Generator ammeter Max 1000A precision 2 operating range 0 02 20ma 6A Frequency meter Precision 0 1 Hz frequency range 45 85Hz Hour meter 4 digits Degree of protection Front panel IP 64 Rear panel IP00 Temperature range 20 50 º C Dimensions LxHxP mm 243x170x62 Hole mm 227x155 Weight 710g DECLARATION OF CONFORMITY We ELCOS s r l declare under our sole responsibility that the control ...