Page 14 (40)
Rev 1
2018-03-21
www.elcon.se
Go to INDEX.
CLOSE
OPEN
CLOSE-OPEN
Pressing any of the operation buttons "CLOSE" or "OPEN" will get you back to monitoring mode where new operations
and measurements can be done.
After static resistance measurement
Result will display
R =
Resistance measured in micro ohm.
I =
Current measured in Amperes.
U =
Voltage measured in millivolt.
Note!
To prevent overheating of the unit and depletion of the batteries. A timer in the top right corner counts down until
next resistance measuring can be performed.
Contact times Close
A 51.52 ms 2.8A^
B 51.50 ms
C 51.48 ms
Contact times Open
A 42.66 ms 2.7A^
B 42.64 ms
C 42.62 ms
Contact times C-O
A 45.10 ms 2.8A^
B 45.08 ms
C 45.06 ms
Resistance 12s
R = 100.0
µ
Ω
I = 205.5 A
U = 20.55 mV