Chapter 3 Deployment
3-23
The module status gives you detailed information about the error that
occurred at a module.
The module status can be activated via the parameterization and has the
following structure:
Module status
Byte
Bit 7 ... Bit 0
X
Bit 5 ... 0: 001100 (fix) Length of the Module status
Bit 7 ... 6: 00 (fix) Code for Module status
X+1
82h (fix) Status type Module status
X+2 00h
(fix)
X+3 00h
(fix)
X+4
Follow bits indicates the status of the modules from slot 1 ... 32
00: Module ok - valid data
01: Module error - invalid data (Module defective)
10: Incorrect module - invalid data
11: No module - invalid data
Bit 1, 0: Module status module slot 1
Bit 3, 2: Module status module slot 2
Bit 5, 4: Module status module slot 3
Bit 7, 6: Module status module slot 4
X+5
Bit 1, 0: Module status module slot 5
Bit 3, 2: Module status module slot 6
Bit 5, 4: Module status module slot 7
Bit 7, 6: Module status module slot 8
X+6
Bit 1, 0: Module status module slot 9
Bit 3, 2: Module status module slot 10
Bit 5, 4: Module status module slot 11
Bit 7, 6: Module status module slot 12
X+7
Bit 1, 0: Module status module slot 13
Bit 3, 2: Module status module slot 14
Bit 5, 4: Module status module slot 15
Bit 7, 6: Module status module slot 16
X+8
Bit 1, 0: Module status module slot 17
Bit 3, 2: Module status module slot 18
Bit 5, 4: Module status module slot 19
Bit 7, 6: Module status module slot 20
X+9
Bit 1, 0: Module status module slot 21
Bit 3, 2: Module status module slot 22
Bit 5, 4: Module status module slot 23
Bit 7, 6: Module status module slot 24
X+10
Bit 1, 0: Module status module slot 25
Bit 3, 2: Module status module slot 26
Bit 5, 4: Module status module slot 27
Bit 7, 6: Module status module slot 28
X+11
Bit 1, 0: Module status module slot 29
Bit 3, 2: Module status module slot 30
Bit 5, 4: Module status module slot 31
Bit 7, 6: Module status module slot 32
X+12
Bit 1, 0: Module status module slot 33
Bit 3, 2: Module status module slot 34
Bit 5, 4: Module status module slot 35
Bit 7, 6: Module status module slot 36
continued ...
Module status
Manual ELCO Intelligent I/O-FS200