Chapter 3 Deployment
3-10
Project engineering
For project engineering a DP master engineering tool can be used like the
Siemens SIMATIC manager. Here you assign the according Profibus DP
slave modules to the DP master.
A direct assignment takes place via the Profibus address that you set at the
DP slave address selector.
By installing the corresponding GSD file the FS2-GW-DP00 is listed at the
hardware catalog as "ELCO FS2-GW-DP00 (DP-V0 or DP-V1)".
You'll find this at:
Profibus DP
>Additional Field devices>I/O>
For every Profibus slave from ELCO there is a GSD file available. This file
may either be found on the supplied storage media or at the download area
of www.elco-holding.com.cn.
The assignment of the GSD-file to your slave is shown in the following
table:
ELCO order number
GSD-file
ELCO FS2-GW-DP00(DP-V0) FS200V0.gsd
ELCO FS2-GW-DP00(DP-V1) FS200V1.gsd
Please install the required files into your configuration tool. Details on the
installation of the GSD and/or type files are available from the manual
supplied with your configuration tool.
After the installation of the GSD file you will find this entry e.g. the DP-V1
slave in the hardware catalog from Siemens at:
•
Mount your Profibus system.
•
Start your project engineering tool with a new project.
•
Configure a master system and create a new Profibus subnet.
•
For the project engineering of the FS2-GW-DP00 take the "ELCO FS2-GW
-DP00 (DPV0)" or "ELCO FS2-GW-DP00 (DPV1)" for each functionality from
the hardware catalog and drag it to the DP master subnet.
•
Enter a Profibus address between 1 and 125 into the properties of the
DP slave and set the same address at the address lever.
•
Parameterize the DP slave (see parameters).
•
Transfer your project to the PLC.
General
GSD- file
Project
engineering
Manual ELCO Intelligent I/O-FS200
ELCO_FS200
Profibus DP >Additional field devices > I/O >
ELCO_FS200>
ELCO FS2-GW-DP00(DPV1)