33
Initial Startup
Parameterization
8400 I Compressor 1 K1
-
OFF ON
-
8401 I Compressor 2 K2
-
OFF ON
-
8402 I Electr. immers. heater flow K26
-
OFF ON
-
8403 I Source pump Q8 / fan K19
-
OFF ON
-
8405 I Condenser pump Q9
-
OFF ON
-
8410 E Return temperature HP
°C 0
140 -
8411 E HP setpoint
°C 0
140 -
8412 E Flow temperature HP
°C 0
140 -
8415 I Hot gas temperature 1
°C 0
140 -
8416 I Hot gas temperature max
°C 0
140 -
8417 I Hot gas temperature 2
°C 0
140 -
8420 I Coolant temperature, liquid
°C 0
140 -
8425 I Temp. spread condenser
°C -50
140
-
8426 I Temp. spread evaporator
°C -50
140
-
8427 E Source input temperature
°C -50
50
-
8428 I Source input min
°C -50
50
-
8429 E Source output temperature
°C -50
50
-
8430 I Source output min
°C -50
50
-
8440 I Rest level 1 standstill time min
min (0)
1
255
---
8441 I Rest level 2 standstill time min
min (0)
1
255
---
8442 I Rest level 1 run time min
min (0)
1
255
---
8443 I Rest level 2 run time min
min (0)
1
255
---
8444 I Rest time limit source temp min
min (0)
1
65535 ---
8445 I Rest time auto reset
h (0)
1
255 ---
8446 I Compressor sequence
- 1-2,
2-1 ---
8450 F Op hours compressor 1
h 0
65535 0
8451 F Start counter compressor 1
- 0
199999 0
8470 I Fan K19
-
OFF ON
---
8471 I Process reversal valve Y22
-
OFF ON
---
8475 I Evaporator temperature
°C -50
50
0
8477 I Temp. diff. defrost actual value
°C -50
50
0
8478 I Temp. diff. defrost setpoint
°C -50
50
0
8480 I Rest time defrost block
min 0
255 0
8481 I Rest time forced defrost
h/min 00:00
07:00 00:00
8485 I No. of defrost cycles
- 0
10 0
8510 I Collector temperature 1
°C -28
350
-
8511 I Collector temperature 1 max
°C -28
350 200
8512 I Collector temperature 1 min
°C -28
350 -28
8513 I dT collector 1 / PWH
°C -28
350
0
Generator
diagnosis
C
o
n
tro
l lin
e
C
o
n
tro
l lev
e
l
Functi
o
n
Un
it
Mi
n
Ma
x
Fac
to
ry
setti
n
g