P
D
M
_
OpM
a
P
rof
i_04_us
.F
M
page 14
field bus PROFIBUS-DP
PacDrive™ M
4 Diagnosis
Ko
rr
ek
tu
ra
us
dr
uc
k
4.2
Example for a Diagnosis Message
The diagnosis message 4731 „automatic bus deactivation“ is
shown.
Meaning of the diagnosis message:
class 4 error
diagnosis code 731
The meaning of the diagnosis code is further explained in the Pro-
gramming Manual - Reference - as shown below.
731 automatic bus deactivation
The Auto Clear bit in the master is set and at least one slave is
not exchanging cyclic I/O data. The error code entered after
"Err=" is equivalent to the error code of the parameter ErrorCode.
Cause:
Handling:
Slave was switched off.
Reactivate slave.
Cause:
Handling:
Faulty configuration of at least one slave.
Check configuration.
Cause:
Handling:
Wiring error: Cable problem in the bus.
Check cable
Cause:
Handling:
Wiring error: Faulty bus topology.
Check terminations,stubs, ...