Before communication can start between the
g!
system and the MAXSYS panel, there are several fields
that need to be changed in the panel configuration. You will need the installer access code to enter the
programming mode. The default code is 5555 for new installations.
To enter programming mode, press [*] + [8] + [Installers Code].
Step Instructions
Comments
1
Press [*] + [8] + [Installers Code]
Enter programming mode
2
Press [Scroll R] + [Scroll R] + [*]
Goes to
Module Hardware
3 Press
[*]
Goes to
Enroll Module
4
Press [Scroll R] + [*]
Selects the
PC44XX RS232
for enrolling
5
Open and close the Tamper circuit on
the PC4401
The transition from secure to violated enrolls the
module: the keypad should display the module
number and confirm enrollment
6
Press [#] [*] [8] [Installers Code]
Returns to main menu (keypad displays
System
Area
)
7
Press [*]
Go into System Area settings
8
Press [Scroll R] several times
Scroll until
PC44XX Options
appears
9 Press
[*]
Module Options
appears in the display
10
Press [*]
PC44XX RS232 #01 appears in the display
11
Press [*]
Module Functions appears in the display
12
Press [*]
The current function is displayed
13
Press [Scroll L] or [Scroll R]
Scroll to select
DataLink
14
Press [*]
Saves your setting, shows Module Function in display
15
Press [Scroll R] + [*]
Goes to Baud Rate, shows the current baud rate
16
Press [Scroll R] or [Scroll L]
Scroll to select
1200 Baud
17
Press [*]
Saves your setting, returns to Module Function
18
Press [#] several times
Exits from programming mode