Before communication can start between the 

g!

 system and the MAXSYS panel, there are several fields 

that need to be changed in the panel configuration.  You will need the installer access code to enter the 
programming mode.  The default code is 5555 for new installations. 

To enter programming mode, press [*] + [8] + [Installers Code]. 
 

Step Instructions 

Comments 

Press [*] + [8] + [Installers Code] 

Enter programming mode 

Press [Scroll R] + [Scroll R] + [*] 

Goes to 

Module Hardware

 

3 Press 

[*] 

Goes to 

Enroll Module

 

Press [Scroll R] + [*] 

Selects the 

PC44XX RS232

 for enrolling 

Open and close the Tamper circuit on 
the PC4401 

The transition from secure to violated enrolls the 
module: the keypad should display the module 
number and confirm enrollment 

Press [#] [*] [8] [Installers Code] 

Returns to main menu (keypad displays 

System 

Area

Press [*] 

Go into System Area settings 

Press [Scroll R] several times 

Scroll until 

PC44XX Options

 appears 

9 Press 

[*] 

Module Options

 appears in the display 

10 

Press [*] 

PC44XX RS232 #01 appears in the display 

11 

Press [*] 

Module Functions appears in the display 

12 

Press [*] 

The current function is displayed 

13 

Press [Scroll L] or [Scroll R] 

Scroll to select 

DataLink

 

14 

Press [*] 

Saves your setting, shows Module Function in display 

15 

Press [Scroll R] + [*] 

Goes to Baud Rate, shows the current baud rate 

16 

Press [Scroll R] or [Scroll L] 

Scroll to select 

1200 Baud

 

17 

Press [*] 

Saves your setting, returns to Module Function 

18 

Press [#] several times 

Exits from programming mode 

 

 