DK50
SM-DK50-EN-1-08-2014-MD
08/2014
6. SWITCHING THE COMPRESSOR ON
(Fig.5)
Switch on the compressor at the pressure switch (2) by turning the knob (3)
to position “I.”, The compressor sends pressurized air to the air tank. As
the compressed air is used, the pressure in the air nozzle drops to a preset
level, the compressor switches on and the air nozzle files with compressed
air. After reaching the cutoff pressure the compressor turns off
automatically and the cycle is repeated. Check the value of switching-on
and switching-off pressure on pressure gauge. The values may be within a
tolerance of
10%. Air pressure in air chamber must not exceed maximal
permitted operation pressure.
Never tamper with the pressure switch (2). Adjustments are not allowed. The pressure
switch (2) has been set by the manufacturer and further setting of switching on and off
pressure may be carried out only by a qualified expert trained by the manufacturer.
MAINTENANCE
7. MAINTENANCE SCHEDULE
Notice!
The operating entity is obliged to ensure that all tests of the equipment are carried out repeatedly at
least once within every 24 months (EN 62353) or in intervals as specified by the applicable national
legal regulations. A report must be prepared on the results of the tests (e.g.: according to EN 62353,
Annex G), including the measurement methods used.
Time interval
Maintenance that must be performed
Chapter Performed
by
1 x day
Release condensate
- At high air humidity
- Compressor without air drier
Compressors with air drier
Compressors with condensation unit :
- from filter
- from pressure vessel
8.1
operating staff
1 x week
1 x year
Check safety valve
8.2
qualified
technician
Replacement of filter element in filter and
micro-filter
8.4
8.5
operating staff
Replacement of filter in condensation unit
8.6
qualified
technician
Check tightness of joints
Overall examination of device
Service
documentation
qualified
technician
1 x 2 years
Perform “Repeated Test” according
to EN 62353
7
qualified
technician
1 x 4 years or after 8000 hours
Replacement of input filter
8.3
qualified
technician
8. MAINTENANCE
Repair work beyond normal maintenance can be performed only by qualified personnel or
the manufacturer’s representative.
Use only spareparts and accessories approved by the manufacturer.
Prior to any maintenance or repair work, switch off the compressor and disconnect it from
the mains (pull out the mains plug).
TO ENSURE THAT THE COMPRESSOR WORKS CORRECTLY, PERFORM THE FOLLOWING
MAINTENANCE TASKS AT REGULAR INTERVALS (CHAPTER 7).:
Fig.5
3
5
2
1
4