Ekinex EK-HA1-TP Manual Download Page 2

 

Page 2

 

•  1 Out with monostable relay (5A/230Vac) SPST type 

single pole single throw,  to control the valve of 
the ,thermal battery. Contact without voltage(EK-
HC1-TP version) 

•  Current consumtion KNX bus:< 10 mA 
•  Plastic container 
•  Installatio type : board on EN 60715 DIN rail 
•  Protection rating: IP 20 in according   with EN 60529                   
•  Climate and mechanics classification : 3K5 and 3M2  

in according EN50491-2 

•  Protection class  III in according with EN 60664-1 
•  Pollution 2 in according with  IEC 60664-1 
•  Dimension : 72 x 90 x 60 mm (LxHxP) 
 
Enviromental Conditions

 

•  Operating temperature: - 5 ... + 45°C 
•  Storage Temperature: - 25 ... + 55°C 
•  Transport Temperature: - 25 ... + 70°C 
•  Relative Humidity : 95%  
 

Switching, display and connection elements 

 

All  devices  are  equipped  with  a  button  ,  a  LED  pro-
gramming,  KNX  terminals  for  connecting  the  outputs, 
additional line voltage and KNX bus line. 
The  EK-HC1-TP  version  is  equipped  with  membrane 
buttons and LEDs. 

 

 

  

 
 

 1 ) Input and output terminals 

 

 2 ) membrane buttons for manual activation of the outputs 

 

 3 ) LED status indicators manual output 
 4 ) LED indicator was manually entered  
 5 ) Button  insertion manually  
 6 ) Programming button 
 7 ) LED indication of programming mode  
 8 ) Terminal KNX bus line  
 9 ) Terminal for auxiliary power supply 230 Vac  
10 ) LED indication of alarm 

 
Command Elements 
•  Pushbutton (6) for switching between the normal 

operation mode and programming 

•  Membrane pushbutton (5) for switching between the 

operating modes forced ( buttons on the front 
active ) or automatic ( buttons on the front non-
active ) 

•  Membrane pushbuttons (2) for forcing the fan speed 
 
Thanks to the lever switches located on the front of the 
device, the connected loads can be manually controlled 
in the absence of voltage on the KNX bus or when the 
programming has not yet been carried out. 
 

 

Note

For the version with membrane keyboard  

EK- HC1 - TP , the manual control of the terminal is possi-
ble if the voltage is present both on the KNX bus that the 
mains voltage

 

.

 

 
Display elements 
•  Red LED (7)for displaying the active operating 

mode of the device (on = programming, off = normal 
operation) 

•  Red LED (4) for indicating the operating mode ( on 

= forced operation , off = automatic)                  

•  Green LEDs for status indication of the speed set 

manually for the fan and for the manual setting of 
the output valves 

•  Red LED (10) to give the status of alarm 

 

Mounting 

The  device  has  degree  of  protection  IP20,  and  is 
therefore suitable for use in dry interior rooms.  
The  housing  is  made  for  rail  mounting  according  to      
EN  60715  in  boards  or  cabinets  for  electrical 
distribution.  
The  installation  is  in  horizontal  position,  the  correct 
position is when the KNX bus terminal is located at the 
bottom and the terminals for the outputs are located at 
the top. 
 For the installation of the device on the rail proceed as 
follows: 
 
•  with the aid of a tool bring the locking device in the 

fully lowered position (1); 

•  place the upper edge of the rear inner profile on the 

upper edge of the rail (2); 

•  rotate the device towards the rail (3);  
•  push the locking device upward until it stops (4). 
 

 

 

 

 

 

 

 

 

 

 

 

 

 
Before  removing  the  device,  be  sure  the  inputs  have 
been  disconnected  and  the  bus  terminal  has  been 
extracted from its slot. Use a screwdriver to slide down 
the locking device and remove the device from the rail. 
 

 

Note.  For  the EK-HC1-TP version it is recommended that 
the  installation  of  the  device  always  ensure  the  full 
accessibility  of  the  front  side  to  allow  the  operation  of  the 
pushbuttons 

 

 
 

 

1

 

2

 

3

 

4

 

5

 

6

 

7

 

8

 

9

 

10

 

DC
E

K

HX
1

TP

 

In

se

rir

e

 c

o

dice

 im

m

a

g

in

e

 

Reviews: