Application manual
Presence detectors KNX EK
-
Dx2
-
TP (x = B, C, D, E)
Release 1.01
-
Update: 05/2014
MAEKDx2TP_EN
© SBS S.p.A.
–
All rights reserved
Page 13
5.2
Illuminazione
-
Commutazione
Parameters:
Light
-
Switching
Operating mode of the
detector
Sets the detector’s operating mode as
Fully automatic
or
Semi
-
automatic
.
The default value is
Fully automatic
.
Green LED
When presence / movement detection occurs, the LED can be set to flash
(value:
When motion
) or remain off (value:
OFF
).
The default value is
When motion
.
Delay time
The switch
-
off delay of the lighting channel (duration of lighting) can be set to
a value ranging from
1 s
to
4 h
.
The default value is
5 min
.
Brightness below which the
sensor is active
Allows to set the value of the light
–
dark threshold that activates detector’s
operation (with decreasing ambient light).
Values range from
10 Lux
to
2000 Lux
or
ALWAYS.
The default value is
300 Lux
.
Important:
if the lighting channel is meant to always remain active (even
with ambient brightness above 2000 Lux) choose the “
ALWAYS”
setting.
Brightness switch
-
off level
Allows to set the maximum brightness value above which detector operation
stops (with increasing ambient light); this is effective even if the switch
-
off
delay is not expired yet.
Values range from
10 Lux
to
2000 Lux
or
OFF.
The default value is
OFF
.
Forced control object or
disabled object
Sets the type of communication object 3.
See also: Object 3 (Input
-
Light
–
Forced control / Disable) in section 6.1.6
.
The selection
Disable object
enables two additional parameters as follows:
The default value is
Forced control object
.