voltages, both DC and AC. 
 

 

Vmin 

Vmax 

Vac 

24 

Vdc 

12 

35 

 

 

 

 

 

 

Important!  In  case  of  DC  power  supply,  DO  NOT 
reverse the terminal blocks polarity!

 

 

KNX connection

 

Connection  to  KNX  bus  is  made  via the supplied  KNX 
terminal block. The terminal block must be inserted into 
the slot located on the lower front side of the device. 
 
KNX terminal block features

 

•  Conductors’ spring clamping 
•  4 conductors’ location for each polarity 
•  Suitable for KNX bus cables with single-wire 

conductors (diameter between 0.6 and 0.8 mm) 

•  Recommended wire stripping: 5 mm 
•  Color code: red = bus con (positive), black = 

bus conductor – (negative) 

 

 

 

 

 

RS485 Modbus connection

 

 

 

 

 
In order to terminate the RS485 network and balance the 
line impedance, you must enter the terminating resistor 
(120 Ω), by setting ON the 1-way microswitch B. 
 
The maximum extension of the RS485 network is 1200 
m. 

Below are some recommended cable codes for wiring 
the RS485 line: 
•  Belden  code  8132.  2x  28AWG  twisted  pairs  of 

cond foil shi shielding mesh; 

•  Belden  code  82842.  2x  24AWG  twisted  pairs  of 

cond foil shi shielding mesh; 

•  Tasker code C521. 1x 24AWG twisted wire pair + foil 

shi shielding mesh; 

•  Tasker  code  C522.  2x  24AWG  twisted  pairs  of 

cond foil shi shielding mesh. 

 

Configuration and commissioning 

Configuration  and  commissioning  of  the  ekinex® 
gateway  must  be  performed  using  the  application 
program  CGEKBH1TP485,  available  for  download  at 
www.ekinex.com. 
 
System requirements for configuration software 
•  Desktop o laptop PC with Ethernet IEEE 802.3 port. 
•  32/64 bit operating system, Microsoft Windows® XP, 

7, 8.0, 8.1 e 10. 

 

 

 
Note.
 .NET Framework 4.0 system library installation is 
required.

 

 
The ekinex® configuration software CG-EK-BH1-TP-485 
allows you to perform the following operations: 
•  Selection of physical parameters of the RS485 serial 

communication; 

•  Selection of physical address of the device over the 

KNX TP network; 

•  Selection  of  Ethernet  parameters  (for  configuration 

download only); 

•  KNX network: communication objects definition and 

relative  group  addresses  to  be  acquired; 
communication objects definition and relative group 
addresses to be sent over the KNX network; 

+

 

-

 

Alimentazione

 

Failure

KNX

Modbus

Device state

EK-BH1-TP-485

Modbus Master RS485 RTU
/ KNX TP Converter

1

2

8...24 Vac

+V

0V

POWER S.

12...35 Vdc

3

4

5

RT-

Com

RS485

ETHERNET

Dev.

Line

Area

RT+

+

 

-

 

Bus

 

KNX

 

Failure

KNX

Modbus

Device state

EK-BH1-TP-485

Modbus Master RS485 RTU
/ KNX TP Converter

1

2

8...24 Vac

+V

0V

POWER S.

12...35 Vdc

3

4

5

RT-

Com

RS485

ETHERNET

Dev.

Line

Area

RT+

RT+

 

RT-

 

Com

 

Failure

KNX

Modbus

Device state

EK-BH1-TP-485

Modbus Master RS485 RTU
/ KNX TP Converter

1

2

8...24 Vac

+V

0V

POWER S.

12...35 Vdc

3

4

5

RT-

Com

RS485

ETHERNET

Dev.

Line

Area

RT+

E

L

1

E

K

B

H1T

P

4

8

5

 

E

L

3

E

K

B

H1T

P

4

8

5

 

E

L

2

E

K

B

H1T

P

4

8

5

 

Reviews: