10
1.
Introduction
1.4.Water Pump
Operation status
When the circulator is running, LED 1 is green. The
four
yellow
LEDs
indicate the current power
consumption (P1) as shown in the table below. See fig.
1. When the operation mode is active, all active LEDs
are constantly on in order to differenti
ate this mode
from the select setting mode. If the circulator
is
stopped by an external signal, LED 1 flashes green.
Alarm status
If the circulator has detected one or more alarms, the
bi-
colored LED 1 switches from green to r
ed. When
an alarm is active, the LEDs indicate the alarm type as
defined in the table below. If multiple alarms are active
at the same time, the LEDs only show the error
with
the highest priority. The priority is defined by the
sequence of the table.
When there is no active alarm anymore, the user
interface switches back to operation mode.
Display
Indication
Pump operation
Counter action
One red LED
+
one yellow LED
(
LED 5
)
One red LED
+
one yellow LED
(
LED 4
)
One red LED
+
one yellow LED
(
LED 3
)
Rotor is
blocked.
Supply
voltage too
low.
Electrical
error.
Trying to start
again every 1.33
seconds.
Wait or block
the shaft.
Only warning,
pump runs.
Pump is stopped
because of low
supply voltage or
serious failure.
Control the
supply voltage.
Control the
supply voltage /
Exchange the
pump.
Display
Indication
Performance in % of
P1 MAX
One green
LED (flashing)
Standby (only externally
controlled)
0
One green
LED + one
Low performance
0-25
yellow LED
One green
LED
+
two
Medium low performance
25-50
yellow LED
One green
LED + three
Medium high performance
50-75
yellow LED
One green
LED + four
High perf
ormance
75-100
yellow LED
Navigation
Key lock function
The purpose of the key lock function is to avoid
accidental change of settings and misuse.
When the key lock function is enabled, all long key
presses will be ignored. This prevents the user from
entering the "select setting mode" area and allows the
user
to
see
the
"
show
setting
mode
"
area
.
If you press the key lock for more than 10 seconds,
you can toggle between enabling/disabling the key
lock function. When doing so, all LEDs, except for the
red LED, will fl
ash for a second indicating that lock is
toggled.
User interface control modes for
UPM3 HYBRID variants
You can manage all UPM3 HYBRID variants with a
single push button and a LED interface.
You can select the following operation modes with the
push button.
The user interface shows the flashing LEDs in the
combination which is described in the tables below.
UPM3 FLEX AS
This circulator
is for either external PWM profile A
signal
control
or
speed
selection
.
You can define the maximum curve of the pump
operation range. With PWM signal, the circulator runs
at the corr
esponding speed. Without PWM signal, the
circulator runs at maximum speed.
P
WM profile A (heating)
*
The circulator is factory-set to start in this control mode.
UPM3 xx-70
LED1
LED2
LED3
LED4
LED5
[
m
]
red
yellow
yellow
yellow
yellow
4
5
6
7
*
10S.