EIPL BD75P Owner'S Manual Download Page 2

 

 

 

 

Page 2 of 12 

Drawing   : - TPC476 
Issue 

: - 2 

Date 

: - 11/04/19 

INTRODUCTION 

 

Designed for a wide range of applications, the RM75P is a rugged, industrial 
unit,  which  utilizes  an  energy-efficient  compressor  and  a  compact  portable 
design to provide easy efficient drying. 
 
The fan draws the moist air through the cold evaporator coil, which cools the 
air below its dew point.  Moisture forms on the evaporator coil and is collected 
in the condensate tray, which is equipped with a permanent drain.  The cooled 
air then passes through the hot condenser coil where it is reheated using the 
same  energy  removed  during  the  cooling  phase,  plus  the  additional  heat 
generated  by  the  compressor.    The  air  is,  therefore,  discharged  from  the 
dehumidifier  at  a  slightly  higher  temperature  with  a  lower  absolute  humidity 
than  that  which  entered.    Continuous  circulation  of  air  through  the 
dehumidifier gradually reduces the relative humidity within the area. 
 
The RM75P dehumidifier is a rugged, reliable drying unit designed to operate 
effectively  over  a  broad  range  of  temperature  and  humidity  conditions.    An 
active  hot  gas  defrost  system,  controlled  by  an  electronic  timer,  guarantees 
positive de-icing, thereby optimizing operation at low temperatures. 
 
The  unit  incorporates  a  rotational  moulded  polyethylene  shell  resilient  to 
damage caused by rough handling. 
 
The unit also incorporates an integral pump which will remove the condensate 
from the unit.  
 
 
 

Summary of Contents for BD75P

Page 1: ...Page 1 of 12 Drawing TPC476 Issue 2 Date 11 04 19 BD75P INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Page 2: ...phase plus the additional heat generated by the compressor The air is therefore discharged from the dehumidifier at a slightly higher temperature with a lower absolute humidity than that which entered...

Page 3: ...al GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the p...

Page 4: ...e the evaporator coils through the rear grille to confirm frost formation or weeping If the air temperature is below 25 C an even coating of frost should cover the entire evaporator coil If the air te...

Page 5: ...ng accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiring connections including mains cable for damage or loose connections 5 In order t...

Page 6: ...he refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing...

Page 7: ...fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass va...

Page 8: ...019712 1 5 Capillary 3014251 1 64ft 6 Solenoid valve 3020836 1 7 Filter dryer 3020937 1 8 Solenoid coil 3030452 1 9 On Off switch 3035914 1 10 Fan Motor 3947013 1 11 Fan Blade 3947014 1 12 Castor 3050...

Page 9: ...to Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407...

Page 10: ...Page 10 of 12 Drawing TPC476 Issue 2 Date 11 04 19...

Page 11: ...Page 11 of 12 Drawing TPC476 Issue 2 Date 11 04 19...

Page 12: ...ww eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www eba...