background image

4

4

4

4    

1

-800-497-4524                   EIC SOLUTIONS, INC

.

                       215-443-5190 

2.  INSTALLATION 

2.1 CHOOSING A LOCATION ON YOUR ENCLOSURE 

When choosing a mounting location for your unit, be sure to keep air flows of both the interior and exterior 

heatsinks  and  fans  in  mind.    Adequate  clearance  between  the  fans/heatsinks  and  nearby  surfaces  is  required  for 
unrestricted air flows which will ensure optimal performance and long, trouble free operation.  The general rule is to 
allow  a  minimum  of  two  inches  between  the  fans  or  heatsinks  and  any  surface.    Refer  to  figure  1.1  for  an  air  flow 
diagram.   

Other  considerations  in  deciding  on  a  mounting  location  include;  allowing  access  to  thermostat  (this  will  be 

inside the enclosure) if frequent adjustments are to be made; allowing access to the hot side heat sinks (this will be on 
the outside of the enclosure) for cleaning if the unit will be used in a harsh, dirty environment.    

2.2  ORIENTATION 

Your AC unit can be mounted either vertically on the front, rear or side of your enclosure or horizontally on the 

top of your enclosure.  See Figure 2.1 and 2.2. 

Vertically mounted (mounted on the side of an enclosure) 3500 BTU units are always mounted with the exposed 

heatsink fins facing left and right. (Fig. 2.1)  

The unit cannot be mounted vertically and turned 90 degrees with the 

exposed heatsink fins at the top and bottom.

  The AAC-161B-4XT is equipped with a built-in vertical condensate drip 

pan.  Once installed the drain hoses must be attached to the brass fittings located in the bottom of the cold side cover 
(inside the enclosure) and routed outside the enclosure.  See Fig. 2.1. 

Mounting the unit vertically and turned 90 degrees on the side of an enclosure (with the exposed heat sink fins 

facing  the  top  and  bottom),  will  cause  condensate  to  drip  in  an  uncontrolled  manner,  possibly  damaging  electronic 
equipment within the enclosure.  If this orientation is the only possible configuration, contact the Engineering Dept. at 
EIC for a custom solution.   

 

Horizontally  mounted  3500  Btu  units

 

always  require  a  factory  installed  drip  pan  (part  #  DP-161H)  to 

prevent dripping condensate from damaging electronic equipment.

  (Fig. 2.2)   

 

In  either  orientation,  issues  regarding  access  should  be  considered  and  minimum  clearances  must  be 

maintained as outlined in Section 2.1 of this manual.  

 

 

 

 

 

 

 

Summary of Contents for AAC-161B Series

Page 1: ...lectric Air conditioner installation and operation manual FOR 3500 Btu MODEL S AAC 161B 4XT AAC 161B 4XT HC AAC 161B XXXXX Cooling Solutions for Cooling Solutions for Cooling Solutions for Cooling Solutions for Mission Mission Mission Mission Critical Electronics Critical Electronics Critical Electronics Critical Electronics ...

Page 2: ...R 6 2 5 INSTALL THE DRAIN LINES 8 2 6 APPLY POWER 9 3 OPERATION 3 1 THERMOSTAT SET POINTS AND HEATING COOLING UNITS 10 3 2 MAINTENANCE 10 4 SPECIFICATIONS 4 1 STANDARD SPECIFICATIONS 11 EIC SOLUTIONS INC EIC SOLUTIONS INC EIC SOLUTIONS INC EIC SOLUTIONS INC 700 VETERANS WAY SUITE 200 WARMINSTER PA 18974 PHONE 1 215 443 5190 or 1 800 497 4524 FAX 215 443 9564 EMAIL info eicsolutions com VISIT US ON...

Page 3: ...e practical for real world applications and are now found in everything from consumer goods to spacecraft Your EIC Solutions Thermoelectric Air Conditioner operates on this principle so there is no compressor and no expensive ozone depleting CFC s EIC s air conditioners use Thermoelectric modules sandwiched between high performance aluminum heat sinks high CFM axial fans and a patented electronic ...

Page 4: ...losure See Figure 2 1 and 2 2 Vertically mounted mounted on the side of an enclosure 3500 BTU units are always mounted with the exposed heatsink fins facing left and right Fig 2 1 The unit cannot be mounted vertically and turned 90 degrees with the exposed heatsink fins at the top and bottom The AAC 161B 4XT is equipped with a built in vertical condensate drip pan Once installed the drain hoses mu...

Page 5: ...5 5 5 5 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 FIGURE 2 1 FIGURE 2 2 ...

Page 6: ... punch or other method mark the exact center point of each mounting hole on the enclosure 5 Using the jigsaw cut the opening in the enclosure 6 Using the 29 drill bit drill a hole at each of the marks you made earlier 7 Using the 8 32 tap tap each of the holes you have drilled 2 4 INSTALLING THE AIR CONDITIONER INSTALL THE AIR CONDITIONER 1 Lay the air conditioner down with the cold side side with...

Page 7: ...7 7 7 7 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 FIG 2 3 ...

Page 8: ...ded with the AC unit Review the Fig 2 4 below for suggested drain line configurations FIG 2 4 YOU MUST USE THE FACTORY INSTALLED HORIZONTAL DRIP PAN IF YOU INSTALL THE AIR CONDITIONER HORIZONTALLY FIG 2 2 ON THE TOP OF YOUR ENCLOSURE FAILURE TO DO SO MAY ALLOW CONDENSATE TO DRIP IN AN UNCONTROLLED MANNER CAUSING DAMAGE TO YOUR EQUIPMENT ...

Page 9: ...ors are as follows Black or Brown line White or Blue line neutral Green or Green Yellow ground Amperage for 220 VAC unit is 8 9 amps Upon applying power to the air conditioner the fans on the cold side inside the enclosure will come on The hot side fans outside the enclosure may also run depending on where the thermostat is set The cold side fans always run to circulate air within your enclosure t...

Page 10: ...C Thermoelectric Air Conditioners are virtually maintenance free The only time maintenance is required is when a unit is installed in an extremely dirty environment In these cases the hot side heat sinks outside the enclosure should be inspected regularly for a build up of dust or dirt If a build up is present on the heat sink fins it can be easily removed as follows 1 Disconnect the power from th...

Page 11: ...ut Voltage Range 180 264 V Current 8 9 A Heating Capability HC Units Only 2700 BTU hr 800 W Weight 43 kg 94 lbs NEMA Rating 4X Cold Side Airflow 220 cfm 375 m3 hr Hot Side Airflow 360 cfm 610 m3 hr Sound Level at 1 meter 73 dBA Operating Temperature Range 4 to 140 F 20 to 60 C Storage Temperature Range 4 to 185 F 20 to 85 C Cooling Thermostat Accuracy 1 0 F 0 6 C ...

Reviews: