9
9
9
9
1
-800-497-4524 EIC SOLUTIONS, INC
.
215-443-5190
INSTALL THE DRIP PAN
1.
Two hose fittings were provided with the drip pan, a right angle and a straight one. Choose
one and install it on the drip pan. Be sure if you use the right angle fitting it is facing the
desired direction prior to installing the drip pan.
2.
There are three mounting holes in the drip pan, match these with the long mounting screws
protruding into the enclosure at the bottom of the AC unit. Push the drip pan onto these
screws.
3.
Using the three 8-32 keps nuts provided, attach the drip pan to the air conditioner.
4.
Attach the supplied PVC drain tube to the hose fitting on the drip pan. This tube should be
routed to the bottom of the enclosure and fed through a 3/8” hole to the outside.
APPLY POWER
Once the air conditioner is mounted, check the serial label and confirm the voltage required
and then apply appropriate power as outlined below.
The unit is intended to be permanently connected. Attach the wires to an appropriate
power source using standard safe wiring methods. Wire colors are as follows:
Black or Brown – line
White or Blue – line/neutral
Green or Green/Yellow – ground
A wiring diagram is shown in Fig. 2.3.
Amperage for a 120 VAC unit is 6.3 amps;
amperage for a 220 VAC unit is 4.6 amps.
Figure 2.3
Upon applying power to the air conditioner the fans on the cold side (inside the enclosure) will
come on. The hot side fans (outside the enclosure) may also run depending on where the
thermostat is set. The cold side fan always runs to circulate air within your enclosure thereby
eliminating any “hot spots”. The hot side fans will only run when the air conditioner is cooling –
they are “pumping” the heat from the inside of your enclosure to the outside air.