15
GB-031C_f.625
FaulT FInDInG
symptom
Reason
Procedure
The indicators and LCD display
on the front panel are off
No power to the boiler
Check electricity mains power supply
Main over heat stat cut-out
Check the temperature safety cut-out investigate cause
- possibly fault / return sensors or power board
The „A” indicator flickering
Insufficient water pressure
Check water pressure in display panel and increase to 1.5 bar
Pressure Sensor failure
Check water pressure in display panel and if display shows
„- -” then replace Pressure Sensor
The „H” indicator flickering
Pump is blocked
Free Pump by setting the Pump on the highest gearing – See
Figure 3 then unscrew the screw on the Pump housing –
See Figure 2. Move Pump rotor manually.
Water is not circulating through the
Boiler
Vent the system: Radiators, Pump and Boiler
Pump not running
Check power available at Pump head, if power available
replace as necessary. If power not available check fuse on
Controller Module and replace if necessary
Flow sensor not operating
Check the flow sensor and replace as necessary
„G” indicator is flashing but
boiler digital display operating
„NA” connection open circuit
Ensure „NA” connection is closed or if using external con-
trol (e.g. Shower Sensor) that this is working correctly
„G” indicator flashing
„NA” connection open circuit
Check „NA” connection - should be closed
„K” indicator flickers
Failure of inlet temp sensor
Replace inlet temp sensor
„L” indicator flickers
Failure of outlet temp sensor
Replace outlet temp sensor
„G” „H” & „K” Indicators lit but
boiler not heating
No supply to heating coils from
Power Board.
Check outputs „G1” „G2” & „G3” on Power Board if
230Volts not present to all replace Power Board
„G” „H” & „K” Indicators lit but
boiler only partially heating
One or more heating coils have no
voltage supply from Power Board
Check outputs „G1” „G2” & „G3” on Power Board if
230Volts not present to all replace Power Board
TEChnICal sPECIFICaTIOns
Boiler range
Fusion Comet 6kW
(EHCCOM6KW)
Fusion Comet 9kW
(EHCCOM9KW)
Fusion Comet 12kW
(EHCCOM12KW)
Fusion Comet
14.4kW
(EHCCOM15KW)
Fusion Comet 24kW
(EHCCOM24KW)
Pipe entry from boilers
Bottom
Bottom
Bottom
Bottom
Bottom
Central heating flow & return pipes
22 mm
Min water pressure
1 bar
Max water pressure
3 bar
Expansion vessel
6 lt.
Maximum system water volume about 60 litres at initial system pressure 1,5 bar
Vessel charge pressure
1,5 bar
Safety Class
IP22
Dry weight
25kg
Electrical supply
230V 1ph 50Hz
415V 3ph 50Hz
Load/current
26,0 Amp.
39,1 Amp.
52,2 Amp.
62,6 Amp.
3 x 34,8 Amp.
Minimum permitted cable diameter
6mm
10mm
16mm
10mm
Heating output
20484Btu
30726 Btu
40968 Btu
49161 Btu
81936 Btu
Temp setting (factory set)
85°C
Min temp setting
20 - 40°C
Overheat Protection
100°C
Pump included
Yes
Recommended Pump settings
Set to max
Protection
32 Amp.
50 Amp.
63 Amp.
80 Amp.
3 x 40 Amp.
The maximum allowed network impedance
0,39 Ω
0,32 Ω
0,24 Ω
0,22 Ω