INSTRUCTION SHEET     

U.S. Patent No. 3,735,078

EBR Receptacles with Interlocked Circuit Breaker:

Explosion-Proof, Dust-lgnition-Proof.

Weatherproof Spring Cover—30, 60 and 100 Amps at 600V A.C. Max.

Interlocked Circuit Breaker Safety Construction. Grounding thru Extra Pole and Shell

*CAUTION: To prevent Ignition of hazardous atmospheres, do not use in Class II,

Group F locations that contain electrically conductive dusts. Most coal dusts are not 

electrically conductive.

Class I, Div. 1 and 2 

Groups C, D

Class II, Div. 1 and 2

Groups F, G

Class III

Type 3R

NEMA 7CD, 9F*G  

WIRING

1. Conductors from Receptacle are connected to the circuit breaker  

 

as shown.

CIRCUIT BREAKER REPLACEMENT

1. Loosen the two screws #1 located on the mounting plate on the  

 

load side of the breaker.

  Note - only loosen enough for the mounting plate #2 to slide  

 

  from under the screw heads.

2. Remove the remaining two screw #3 that secure the mounting  

 

plate #2 in place.
3. Loosen the breaker screws #4 that connect the breaker phase  

 

locations to the conductors which are attached to the contact    
    block pins. Loosening of these screws will allow removal of the  

 

breaker and mounting plate assembly.
4. Loosen and remove the four breaker mounting screws #5 which  

 

secure the breaker to the mounting plate.
5. Discard the old breaker & four mounting screws #5. Insert the four  
new mounting screws #5 through the back of the new breaker.   
Fasten to the mounting plate #2 as shown. Cut off surplus length  

 

of screw protruding through the plate and fasten the mounting    
plate #2 to the inside of the cover #6 by reversing steps 1 to 3    
above, making sure to tighten all screws securely.

2 WIRE - 3 POLE

GREEN WIRE

GROUNDING 

STRIP

HALF MOON

CONFIGURATION

GREEN WIRE

GROUNDING 

STRIP

3 WIRE - 4 POLE

GREEN WIRE

GROUNDING 

STRIP

HALF MOON

CONFIGURATION

GREEN WIRE

GROUNDING 

STRIP

1

1

2

2

3

CONDUCTOR INSULATION BELOW THIS SURFACE

CONTACT SET SCREW

CONTACT BLOCK

GROUNDING 

STRAP

CIRCUIT

BREAKER

#5

(4) MOUNTING 

SCREWS

#6

COVER

#3

BREAKER SCREWS

#4
BREAKER WIRING SET SCREWS

FIELD WIRING

TERMINALS

#2

MOUNTING PLATE

#1

BREAKER SCREWS

MOUNTING PLATE

WEST BREAKER

GE BREAKER

LOWER SIDE
(LOAD SIDE OF BREAKER)

UPPER SIDE
(LINE SIDE OF BREAKER)