Electronic device DMU2000 - DMU3000 - DMU3000 PLUS

Electronic device DMU2000 - DMU3000 - DMU3000 PLUS

THE POWER OF PERFORMANCE

3

. Printing DMU setting data

Once the work of checking/changing the data inside the DMU is completed, it is recommended to 

print the data relating to the personalization made and to insert the print in the technical handbook 

of the crane; such data may be useful in case you install a new DMU provided for replacement.

u

 

Display the screen related to the data

 

 to be printed;

u

 

Press the button 

PRINT

 on the key-

board.

The screen is stored by the computer.

u

 

Open  a  word  processor  such  as 

WORD - WORD PAD – and in the menu 

click the icon 

“Paste”.

u

 

Save this new file to print it later, or 

to insert it in a mail.

This  operation  is  to  be  run  for  all 

individual screens that you wish to print 

or send by e-mail.

It comes out from the content above that the electronic system automatically locks certain DMU move-

ments of the crane when the value set as the maximum performance is reached. 

On the cranes with the manual FPI device (which can be turned on / off by operating an electric switch 

on the radio transmitter), every time it is turned on, the data relating to pressures inside the lifting cyl-

inders are automatically reduced by a preset rate, which is equal to the increase in performance which 

is achieved by the crane.

In case of cranes with the DMU 3000 PLUS, the operation of the F.P.I device occurs gradually, just as the 

DMU gradually processes the pressure values inside the cylinders by reducing them. Therefore, start-

up of the operating stop is delayed.

Summary of Contents for DMU 2000

Page 1: ...THE POWER OF PERFORMANCE Cod MI00002GB_4 14 02 09 essebi bo TECHNICAL ASSISTANCE MANUAL DMU Suite 1 3 DATA MONITOR UNIT DMU3000 DMU2000 DMU3000PLUS...

Page 2: ...ia Bonazzi 12 14 Ph 39_ 0 51_4181211 Fax 39_ 0 51_701492 www effer it e mail info effer it The purpose of this manual is to provide all the workshops that are part of the assistance network of EFFER c...

Page 3: ...mmunication port setting 7 Explanation of various changeable parameters 8 Displaying changing available data in the software 9 Printing DMU setting data 10 Instructions for diagnostics 11 Adjusting an...

Page 4: ...ion is established N B If an expired password is typed in even by mistake to have access to the software the soft ware is automatically stopped In order to use the software again it is necessary to pe...

Page 5: ...lect a language with which you wish to dialogue with the software see section 5 F After setting the language an identical dialog box will ask for the password to access the software NOTE After install...

Page 6: ...5 Using the software a Software startup After connecting the computer to cranes as described in section 4 you can proceed to the activities permitted by the software following the instructions below...

Page 7: ...ith the software and the operator s code linked to the password will be stored in memory by DMU on which you will work The password has a time limit the date of expiry shall be communicated with the p...

Page 8: ...ge the dialogue language with the software already running u Click on the icon Options u Click on the icon User Level Settings and Language The window DMU settings appears u Click on the icon Language...

Page 9: ...Electronic device DMU2000 DMU3000 DMU3000 PLUS THE POWER OF PERFORMANCE c Quitting the software u Click on the icon File with the cursor You see a window click on the icon Quit to exit the soft ware...

Page 10: ...setup CD u Insert the CD in the computer NOTE In case there is no communication between the DMU and the computer the words ERROR 2 ap pear on the screen In this case you have to match the communicati...

Page 11: ...you may need to go through Perfor mances and Maintenance u In the Hardware menu click Device Manager u Select COM ports and LPT that you can find in the drop down menu After you open the sub menu the...

Page 12: ...e parameters To access the management part concerning change in certain performance parameters follow the path u CURRENT CRANE u DISPLAY CHANGE DMU DATA SHEET In the opening screen some setting values...

Page 13: ...al tests the load limiting device should be operated first by decreasing the value on this line 3 Pressure 100 basic crane 1st boom cylinder with Jib fitted The setting value shown on the second line...

Page 14: ...stability parameters 7 Cancel performance downgrading in B area If the installation of the crane does not require any identification of the area B related to performance downgrading if you select OFF...

Page 15: ...or a function of a crane jib to a bucket This solenoid valve is operated by means of an electric switch Each time you turn this switch a performance downgrading of the crane is operated already set at...

Page 16: ...oint related to jib opening is moved thus avoiding stopping crane operation without reason Note Please see page 33 for further information 13 Disabling stand by function On all the DMUs the stand by f...

Page 17: ...the box 15 Enabling angular sensor to detect 1st boom position As the anti bridge function is installed an angle sensor is fitted to the first boom and the function must be enabled otherwise the DMU r...

Page 18: ...plied to the hook In these specific cases you get crane good operation if ON ap pears next to such indication If off appears the crane is inoperative 18 Detecting pin load on winch enperno Depending o...

Page 19: ...the type of programming entered for the configuration of the jib H This code identifies the type of programming entered for the configuration of the jib if the jib is made of two part or is customised...

Page 20: ...front of the cab first boom downgrading in B area the setting value that appears is the value resulting from the application of the crane to the truck which is the minimum possible in respect of the...

Page 21: ...d line is still highlighted u Type the desired value in the box N B The value does not exceed the maximum value allowed as stated on the previous screen other wise the system does not accept it i e ev...

Page 22: ...the DMU Further confirmation of your change in the data is given by the dialog box that appears after the comparison of data sent and those stored u CLICK OK While carrying out a change in the values...

Page 23: ...t it in a mail This operation is to be run for all individual screens that you wish to print or send by e mail It comes out from the content above that the electronic system automatically locks certai...

Page 24: ...so possible to print the diagnostic test that you carry out u Click on the icon Tools a First Menu Diagnostics of Sensors and DMU hard ware u Click on the icon Diagnostics of Sensors and DMU hardware...

Page 25: ...2 Hardware DMU The indication of a fault next to one of these errors requires a check as shown in chapter 16 a3 Pressure Bar ist Indicates the instant pressure value inside the various lifting cylinde...

Page 26: ...pears 2nd Boom alpha 2 If cranes are built in the basic crane configuration with the second boom without uplifting the value that appears on the side of this line is 0 and it is not to be considered o...

Page 27: ...he control bank lever is not operated there is a fault in a con necting electrical cable or in an electric microswitch fitted to the hydraulic con trol bank By operating the individual control levers...

Page 28: ...sence of 1 next to the single description The crane is fully or partially stopped d Fourth Menu Digital input diagnostics u Click on the icon Digital input lever diagnostics Digitalinputleverdiagnosti...

Page 29: ...d by The hours of work made with the oil filter clogged are reset automatically when the filter clogging sen sor works for about 30 min without receiving clogging indications The hours of work made fr...

Page 30: ...s operation if it is in a position above under the horizontal line This distinction is indicated in the menu with 0 when the booms are under the critical angle and 1 when they are above The explanatio...

Page 31: ...above you must intervene mechanically on fastening of the sensor to jib crane b BASIC CRANE WITH THE SECOND BOOM THAT DOES NOT UPLIFTS BUT EQUIPPED WITH ADDITIONAL JIB ANALOG ANGLE SENSOR ON BOTH SEC...

Page 32: ...he crane booms when you reach configurations at safety limits a typical example is to avoid going beyond the crane verticality following an opening manoeuvre of boom handling cylinders Adjusting type...

Page 33: ...decrease each attempt by 5 points u send a data sheet to DMU u run a test after a minute from the transfer of data The electronic stop position of the jib opening movement is advanced u Reduce the val...

Page 34: ...g path Current Crane self learning programming you have access to the screen below u Click on the icon Current Crane u Click on the icon Self learning programming Self learning programming window appe...

Page 35: ...changed an additional jib is added a winch is fitted or the device is changed for replacement you must enter the new setting param eters within the DMU fitted to the crane Note if any device is elimi...

Page 36: ...E DMU In addition to the DMU spare device it is necessary to have the file delivered by Sol Ge preferably by e mail or on CD also containing the crane identification data u Save the file on PC desktop...

Page 37: ...a match the desired data Model Serial number Revision of the data sheet change the desired parameters and store them on DMU by following the instructions given in Chapter 7 c LOADING DATA FROM AN E MA...

Page 38: ...r of the stabilizers if fitted move the lever of rotation in one direction than in the opposite direction continue with the other levers up to that of basic crane extensions a continuous beep is opera...

Page 39: ...the DMU again You can now move the crane and if necessary reset the PIN code following the instructions on the DMU manual A PIN code can be stored as a safety anti theft device for the crane see DMU i...

Page 40: ...ook at the lights that light up on the DMU main panel see which ones are flashing and observe how they flash and the sound emitted Here are some indications from main panel relating to faults The fina...

Page 41: ...operated in one direction FAILURE ANALYSIS If the computer is connected to crane tools control bank lever diagnostics conditions and errors the error state is displayed 1 appears next to lever not in...

Page 42: ...cted to crane tools control bank lever diagnostics conditions and errors the error status is displayed 1 appears next to lever not in neutral position when DMU is started On the same page the indicati...

Page 43: ...S If the computer is connected to crane tools control bank lever diagnostics conditions and errors three errors are displayed 1 appears next to lever sensor disconnected contrasting manoevres 1 appear...

Page 44: ...ontrol bank lever diagnostics conditions and errors the error state is displayed The indication 1 next to the words lever not in neutral position when DMU is started appears The indication 1 appears o...

Page 45: ...ever diagnostics conditions and errors three errors are displayed 1 appears next to lever sensor disconnected contrasting manoevres 1 appears next to lever not in neutral position when DMU is started...

Page 46: ...heck is equiva lent to connecting a new transducer electrically only without inserting it into cylinder and you should read a pressure value of 0 bar SOLUTION 1 Replace the pressure transducer FAILURE...

Page 47: ...is displayed 1 appears next to pressure sensor damaged 0 bar CHECK Check that the error state disappears and a pressure value of about 135 appears on computer when carrying out the electric by pass on...

Page 48: ...ucer FAILURE ANALYSIS If the computer is connected to crane tools sensor diagnostics DMU hardware the error state is displayed 1 appears next to pressure sensor damaged 0 bar CHECK Check that the erro...

Page 49: ...CHECK Check that the error state disappears and a pressure value of about 135 appears on computer when carrying out the electric by pass on transducer connecting cable as outlined in Chapter 17 This c...

Page 50: ...FAILURE ANALYSIS If the computer is connected to crane tools sensor diagnostics DMU hardware the error state is displayed 1 appears next to pressure sensors disconnected CHECK Check that the error st...

Page 51: ...sensor diagnostics DMU hardware the error state is displayed 1 appears next to second boom angular sensor damaged A clearly anomalous angle value appears CHECK Check that the error state disappears o...

Page 52: ...econd boom above critical angle If the error state continues the angular sensor electric connection is damaged SOLUTION Restore electric connection between DMU and angular sensor FAILURE ANALYSIS If t...

Page 53: ...nsors disconnected CHECK Check that the error state disappears and a pressure value of about 135 appears on computer when carrying out the electric by pass on transducer connecting cable as outlined i...

Page 54: ...sducer FAILURE ANALYSIS If the computer is connected to crane tools sensor diagnostics DMU hardware the error state is displayed 1 appears next to pressure sensors disconnected CHECK Check that the er...

Page 55: ...LYSIS If the computer is connected to crane tools sensor diagnostics DMU hardware the error state is displayed 1 appears next to jib angular sensor damaged CHECK Check that the error state disappears...

Page 56: ...FAILURE ANALYSIS If the computer is connected to crane tools sensor diagnostics DMU hardware the error state is displayed 1 appears next to jib angular sensor damaged the electric cable connecting th...

Page 57: ...ILURE ANALYSIS If the computer is connected to crane tools sensor diagnostics DMU hardware two error states are displayed 1 appears next to pressure sensors disconnected 1 appears next to jib angular...

Page 58: ...ctly crane with jib the electronic card is damaged SOLUTION Replace the electronic card 4 7 1 3 2 P The jib load limiting device comes into operation though a jib load lower than the load allowed by t...

Page 59: ...the solenoid valve fitted to the crane HSS main discharge first boom discharge FAILURE ANALYSIS If the computer is connected to crane tools sensor diagnostics DMU hardware the two error states are di...

Page 60: ...led lights on the proximity switches relating to the management of the slewing angles CHECK A lighted led is placed on each proximity switch if you keep the crane boom positioned within the work angl...

Page 61: ...ating to the management of the slewing angles CHECK A lighted led is placed on each proximity switch if you keep the crane boom positioned within the work angle of the crane maximum capacity proximity...

Page 62: ...nsor reads an uncorrect value out of range CHECK Check electric cable integrity of the rotary sensor SOLUTION If fault can not be found out get in touch with an EFFER authorized workshop immediately 4...

Page 63: ...d an intermittent quick acoustic alarm is emitted Bip Bip Bip Bip CAUSE 1 Pin battery low 2 Error of communication between DMU and pin 3 Error of radio communication between pin and its receiver CHECK...

Page 64: ...alarm is emitted The CAUSE is the inclusion of the PIN code see user manual SOLUTION 1 enter the PIN code to have the crane operating SOLUTION 2 if you do not know the PIN code you can cancel it with...

Page 65: ...te with the speed reductions provided for the specific project g One or several warning lights 1 2 3 is turned on intermittently and an acoustic alarm of the intermittent quick type is emitted Bip Bip...

Page 66: ...INCE JANUARY 2005 after 30 minutes of work time measured since a control bank lever is operated for a time of two minutes a sound made up of a series of four beeps is emitted Bip Bip Bip Bip Bip Bip B...

Page 67: ...nk pressure sensors angular sensors To determine if the fault is located in pressure sensors or angular sensors rather than in the wiring you must use a 2k2 Ohm 2200 Ohm heated wire of at least 3 Watt...

Page 68: ...be checked electrically 1 Fit a 2k2 Ohm 2200 Ohm heated wire of at least 3 Watt to the angular sensor connecting cable 2 Connect the computer to crane 3 1 is displayed next to 2nd boom above critical...

Page 69: ...DRIVE BQ5 WINCH DRIVE BQ6 X19 CS1 SUPPL CONTROL DRIVE BQ7 X20 CS2 SUPPL CONTROL DRIVE WIRE MARKING CRANE FUNCTION ITEM CODE PRINTED ON THE LOWER SIDE OF THE DMU MAIN BOX BQ1 CRANE SLEWING DRIVE BQ2 1...

Page 70: ...1 CRANE SLEWING DRIVE BQ2 1ST BOOM DRIVE BQ3 2ND BOOM DRIVE BQ4 STANDARD CRANE EXTENSION DRIVE BQ5 WINCH DRIVE BQ6 CS1 SUPPL CONTROL DRIVE BQ7 CS2 SUPPL CONTROL DRIVE WIRE MARKING CRANE FUNCTION CONTR...

Page 71: ......