U S E R M A N U A L E P S - D
Technical specifications and data are subject to change without any prior notice.
32
Specifications
Charger
:
Voltage
: 230 VAC +-10 %
Frequency
: 50Hz +-2 %
Protection
: Mains fuse/Battery fuse/Output fuse/Polarity protection for the
battery (Diode), DC Overvoltage & Deep discharge.
Battery Charge Current
: C/10 A/DC – automatically set through battery size.
Battery Voltage
: 24 Vdc
.
Battery voltage adjustment:
27.4 Vdc +-0.1% - adjustable through
potentiometer.
Low battery alarm:
22.0 Vdc (reset at 25.5 Vdc).
Under voltage shutdown, battery:
19 Vdc (reset at 24.2 Vdc).
Temperature compensation:
Checks and adjusts the charging voltage.
Inverter
:
Voltage
: 220/230/240VAC
Static Adjustment:
+-2% True RMS (Selected software) - 90 % of nominal
when low battery.
Dynamic Adjustment:
max 10% - return to nominal < 5 seconds
Frequency:
50 Hz +-0.1 %- own crystal – under mains fail50 Hz +-2% - when
mains present.
Slew rate:
0.1 Hz/second
Curve form:
Quasi (modulated square ) or sine.
Under voltage shutdown:
150 Vac.
Overload while Mains powered:
The rated size. EPS600D = 600 VA
Overload while battery powered:
180 W per size +50 W for own power (while
the out voltage exceeds 150 Vac) e.g. EPS750D =5x180+50=950 W.