III. ELECTRICAL HOOK-UP
WARNING
BEFORE DOING ANY WORK ON THE UNIT BE SURE THE
BREAKER IS
“OFF”
TO AVOID ANY DANGER OF SHOCK.
“Eemax ProAdvantage” heaters are manufactured to the following specifications:
The L1, L2, or N should be connected to the slots in the contactor marked L1 and L2.
(see Fig 2b). The ground lead must be connected to the stud marked GND.
GROUND MUST BE BROUGHT TO THE “GROUND” AT THE CIRCUIT BREAKER PANEL.
Use a dedicated circuit with appropriate wiring and circuit breaker configuration which is
dictated by the power requirements of the unit. (see Table 1 and Fig 3)
DANGER
FAILURE TO GROUND THE SYSTEM MAY RESULT IN DEATH OR SERIOUS INJURY.
MODEL TYPE
Voltage
kW output
AMPERAGE
PA004120T
1f 120
V
3.5
29
PA008208T
1f 208
V
8.3
40
PA005240T
1f 240
V
4.8
20
PA007240T
1f 240
V
6.5
27
PA010240T
1f 240
V
9.5
40
PA012240T
1f 240
V
11.5
48
PA008277T
1f 277
V
8.0
29
PA010277T
1f 277
V
10.0
36
Table 1
7
Figure 3
Dedicated
Single Pole (120/277 Volts)
or
Double Pole (208/240 Volts)
Circuit
ON
OF
F
or
Circuit Breaker Panel
ON
ON
OF
F
OF
F