background image

PM10D01KNXFI01010004.DOC 

 

 

Technical Specifications 

 
Data in compliance with EN 50470-1, EN 50470-3, EN 62053-23 and EN 62053-31 
 

 

General characteristics 

 

DIN 

 

• Housing

 

DIN 43880 

2 Module 

• Mounting

 

EN 60715 

35 mm 

DIN rail 

• Depth

 

 

mm 

70 

• Weight

 

 

175 

Operating features 

 

n° wires 

 

• Connection

 

to single-phase network 

• Storage of energy values and config.

 

Internal flash memory 

yes 

• Tariff

 

for active and reactive energy 

n° 2 

T1 / T2 

Measuring features (according to EN 50470-1, EN 50470-3) 

 

 

• Reference Voltage 

Un 

 

VAC 

230 

• Reference Curren

(Iref) 

 

• Minimum Current 

(Imin) 

 

0.25 

• Maximum Current 

(Imax) 

 

63 

• Starting Current 

(Ist) 

 

0.015 

• Reference Frequency 

(fn) 

 

Hz 

50 

• Number of phases (number of wires)

 

 

1 (2) 

• Accuracy

 

Active Energies (accor. to EN 

50470-3) and Active Powers 

Class 

  

Reactive Energies (accor. to EN 62053-

23) and Reactive Power 

Class 

 

Supply Voltage and Power Consumption 

 

 

• Operating Supply Voltage range

 

 

92 ... 276 

• Maximum Power Dissipation (Voltage circuit)

 

 

VA (W) 

<

2 (1) 

• Maximum VA 

burden (Current circuit) @ 

Imax 

VA 

<

• Voltage Input Waveform

 

 

AC 

• Voltage impedance

 

 

M

 

• Current impedance

 

 

m

 

<

20 

 

Overload capability 

 

VAC 

 

• Voltage

 

continuous 

276 

  

 

 

Temporary (1 s) 

VAC 

300 

 

• Current

 

continuous 

63 

  

 

 

 

Temporary (10 

ms) 

1890 

 

Measuring Features 

 

VAC 

 

• Voltage range

 

 

92 ... 276 

• Current range

 

 

0.015 ... 63 

• Frequency range

 

 

Hz 

45 ... 65 

• Measured Quantities

 

 

V, A, kWh, 

kVARh, 

  

 

   

  

 

PF, Hz, kW, 

kVAR 

 

Display features 

 

 

• Display type

 

LCD backlightet 

6.2 +3 

  

 

   

 

Energy digits 

dimension 

mm 

6 x 3 

 

• Active Energy

 

6  2 decimal digits 

min. max. 

kWh 

0.01 ... 

999999.99 

• Reactive Energy

 

6  2 decimal digits 

min. max. 

kvarh 

0.01 ... 

999999.99 

• Voltage

 

3  2 decimal digits 

92.00 ... 276.00 

• Current

 

2  2 decimal digits 

0.00 ... 63.00 

• Power factor

 

1  3 dec.  capac./induc. indic. 

0.000 ... 1.000 

• Frequency

 

2  2 decimal digits 

Hz 

45.00 ... 65.00 

• Active Power

 

2  2 decimal digits with sign 

kW 

0.00 ... 17.40 

• Reactive Power

 

2  2 decimal digits with sign 

kVAR 

0.00 ... 17.40 

• Running Tariff

 

1 digit 

T1 / T2 

• Display refresh period

 

 

Optical metrological LED 

 

p/kWh 

 

• Front mounted red LED (meter constant)

 proportional to active imp/exp Energy 

1000 

Safety 

 

Class 

 

• Protective class

 

 

II 

• AC voltage test (EN 50470

-3, 7.2) 

 

kV 

• Degree of pollution

 

 

• Operational voltage

 

 

300 

• Impulse voltage test

 

 

1.2/50 µs-

kV 

• Housing material flame resistance

 

UL 94 

Class 

V0 

Embedded communication 

 

 

• Physical interface

 

 

KNX terminal 

• Isolation class

 

 

SELV circuit 

Tariff 

 

 

• Tariff 1

 

 

open contact 

• Tariff 2

 

 

VAC 

230 ±20% 

• Input impedance

 

 

k

 

224 

Connection terminals 

 

POZIDRI

 

• Screwdriver for mains terminals

 

head with Z +/- 

PZ2 

• Screwdriver for tariff terminals

 

slotted head 

mm 

0.8 x 3.5 

• Terminal capacity main current paths

 solid wire min. (max) 

mm

1.65 (33) 

  

 

stranded wire with 

sleeve min. (max) 

mm

1.65 (33) 

 

• Terminal capacity for tariff

 

solid wire min. (max) 

mm

1 (4) 

  

 

stranded wire with 

sleeve min. (max) 

mm

1 (2.5) 

 

Environmental conditions (storage) 

 

°C 

 

• Temperature range

 

 

-25 ... +70 

Environmental conditions 

(operating) 

 

°C 

 

• Temperature range

 

 

-25 ... +55 

• Mechanical environment

 

 

M1 

• Electromagnetic environment

 

 

E2 

• Installation

 

Indoor 

yes 

• Altitude (max.)

 

 

meter 

<

2000 

• Humidity

 

yearly average, not condensing 

<

75% 

  

 

on 30 days per 

year (not 

condensing) 

<

95% 

 

• IP rating

 

 

IP51(

*

)/IP40 

(*) The metering equipment must be installed inside a cabinet with IP rating 
IP51 or better. 

 

 

 

 

 

 

Installation instructions 

 

WARNING 
 
Device must be installed keeping a minimum distance of 4mm between electrical 
power line (mains - 230V) and red / black bus connector or bus cable. 
 

x

  Device may be used for indoor installations in dry locations. 

x

  Device must be mounted by an authorised  installer. 

x

  Device must be installed in a location that is accessible only to qualified installers 

x

  The applicable safety and accident prevention regulations must be observed. 

x

  Device must not be opened. Any faulty device should be returned to manufacturer. 

x

  For planning and construction of electric installations, the relevant guidelines, regulations 

and standards of the respective country are to be considered. 

x

  KNX bus allows you to remotely send commands to the system actuators. Always make 

sure  that  the  execution  of remote  commands  do  not  lead  to  hazardous  situations,  and 
that the user always has a warning  about which commands can be activated remotely. 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

DISPOSAL 

The  crossed-out  bin  symbol  on  the  equipment  or  packaging  means  the  product  must  not  be  included  with 
other  general  waste  at  the  end  of  its  working  life.  The  user  must  take  the  worn  product  to  a  sorted  waste 
centre,  or  return  it  to  the  retailer  when  purchasing  a  new  one.  An  efficient  sorted  waste  collection  of  the 
environmentally  friendly  disposal  of  the  used  device,  or  its  subsequent  recycling,  helps  avoid  the  potential 

negative effects on the environment and people’s health, and encour

ages the re-use and/or recycling of the 

construction materials. 

 

 

 

Eelectron spa 
 

Via Monteverdi 6 
I-20025 Legnano (MI) - Italia 
Tel: +39 0331 500802 Fax: +39 0331 564826 
Email: [email protected] Web: www.eelectron.com 
 

Summary of Contents for PM10D01KNX

Page 1: ...eriore a 1 5 secondi Una pressione lunga 1 5 secondi del tasto ESC viene utilizzata per resettare i valori dei contatori parziali d Energia Una pressione lunga 5 secondi viene utilizzata per resettare i valori dei contatori dell Energia totale Accensione dispositivo e pagina principale Pagina principale Questa pagina appare non solo all accensione del dispositivo ma anche nel caso in cui per 30 se...

Page 2: ...Tariff 2 VAC 230 20 Input impedance kΩ 224 Connection terminals POZIDRI V Screwdriver for mains terminals head with Z PZ2 Screwdriver for tariff terminals slotted head mm 0 8 x 3 5 Terminal capacity main current paths solid wire min max mm2 1 65 33 stranded wire with sleeve min max mm2 1 65 33 Terminal capacity for tariff solid wire min max mm2 1 4 stranded wire with sleeve min max mm2 1 2 5 Envir...

Page 3: ...modification or to go back to the main page In these cases its pushing is accepted only 1 5 seconds A long pushing 1 5 seconds of the ESC key is used in the Partial Energy Registers Pages to reset their values A long pushing 5 seconds is used in the Main Energy Registers Pages to reset their values Device Switch on and Main Page Main Page This page appears not only at device switch on but also in ...

Page 4: ...olation class SELV circuit Tariff Tariff 1 open contact Tariff 2 VAC 230 20 Input impedance kΩ 224 Connection terminals POZIDRI V Screwdriver for mains terminals head with Z PZ2 Screwdriver for tariff terminals slotted head mm 0 8 x 3 5 Terminal capacity main current paths solid wire min max mm2 1 65 33 stranded wire with sleeve min max mm2 1 65 33 Terminal capacity for tariff solid wire min max m...

Reviews: