PM10D01KNXFI01010004.DOC
Technical Specifications
Data in compliance with EN 50470-1, EN 50470-3, EN 62053-23 and EN 62053-31
General characteristics
DIN
• Housing
DIN 43880
2 Module
• Mounting
EN 60715
35 mm
DIN rail
• Depth
mm
70
• Weight
g
175
Operating features
n° wires
• Connection
to single-phase network
2
• Storage of energy values and config.
Internal flash memory
-
yes
• Tariff
for active and reactive energy
n° 2
T1 / T2
Measuring features (according to EN 50470-1, EN 50470-3)
• Reference Voltage
Un
VAC
230
• Reference Curren
t
(Iref)
A
5
• Minimum Current
(Imin)
A
0.25
• Maximum Current
(Imax)
A
63
• Starting Current
(Ist)
A
0.015
• Reference Frequency
(fn)
Hz
50
• Number of phases (number of wires)
-
1 (2)
• Accuracy
Active Energies (accor. to EN
50470-3) and Active Powers
Class
B
Reactive Energies (accor. to EN 62053-
23) and Reactive Power
Class
2
Supply Voltage and Power Consumption
V
• Operating Supply Voltage range
92 ... 276
• Maximum Power Dissipation (Voltage circuit)
VA (W)
<
2 (1)
• Maximum VA
burden (Current circuit) @
Imax
VA
<
1
• Voltage Input Waveform
-
AC
• Voltage impedance
M
Ω
1
• Current impedance
m
Ω
<
20
Overload capability
VAC
• Voltage
continuous
276
Temporary (1 s)
VAC
300
• Current
continuous
A
63
Temporary (10
ms)
A
1890
Measuring Features
VAC
• Voltage range
92 ... 276
• Current range
A
0.015 ... 63
• Frequency range
Hz
45 ... 65
• Measured Quantities
-
V, A, kWh,
kVARh,
PF, Hz, kW,
kVAR
Display features
-
• Display type
LCD backlightet
6.2 +3
Energy digits
dimension
mm
6 x 3
• Active Energy
6 2 decimal digits
min. max.
kWh
0.01 ...
999999.99
• Reactive Energy
6 2 decimal digits
min. max.
kvarh
0.01 ...
999999.99
• Voltage
3 2 decimal digits
V
92.00 ... 276.00
• Current
2 2 decimal digits
A
0.00 ... 63.00
• Power factor
1 3 dec. capac./induc. indic.
-
0.000 ... 1.000
• Frequency
2 2 decimal digits
Hz
45.00 ... 65.00
• Active Power
2 2 decimal digits with sign
kW
0.00 ... 17.40
• Reactive Power
2 2 decimal digits with sign
kVAR
0.00 ... 17.40
• Running Tariff
1 digit
-
T1 / T2
• Display refresh period
s
1
Optical metrological LED
p/kWh
• Front mounted red LED (meter constant)
proportional to active imp/exp Energy
1000
Safety
Class
• Protective class
II
• AC voltage test (EN 50470
-3, 7.2)
kV
4
• Degree of pollution
-
2
• Operational voltage
V
300
• Impulse voltage test
1.2/50 µs-
kV
6
• Housing material flame resistance
UL 94
Class
V0
Embedded communication
-
• Physical interface
KNX terminal
• Isolation class
-
SELV circuit
Tariff
-
• Tariff 1
open contact
• Tariff 2
VAC
230 ±20%
• Input impedance
k
Ω
224
Connection terminals
POZIDRI
V
• Screwdriver for mains terminals
head with Z +/-
PZ2
• Screwdriver for tariff terminals
slotted head
mm
0.8 x 3.5
• Terminal capacity main current paths
solid wire min. (max)
mm
2
1.65 (33)
stranded wire with
sleeve min. (max)
mm
2
1.65 (33)
• Terminal capacity for tariff
solid wire min. (max)
mm
2
1 (4)
stranded wire with
sleeve min. (max)
mm
2
1 (2.5)
Environmental conditions (storage)
°C
• Temperature range
-25 ... +70
Environmental conditions
(operating)
°C
• Temperature range
-25 ... +55
• Mechanical environment
-
M1
• Electromagnetic environment
-
E2
• Installation
Indoor
-
yes
• Altitude (max.)
meter
<
2000
• Humidity
yearly average, not condensing
-
<
75%
on 30 days per
year (not
condensing)
-
<
95%
• IP rating
-
IP51(
*
)/IP40
(*) The metering equipment must be installed inside a cabinet with IP rating
IP51 or better.
Installation instructions
WARNING
Device must be installed keeping a minimum distance of 4mm between electrical
power line (mains - 230V) and red / black bus connector or bus cable.
x
Device may be used for indoor installations in dry locations.
x
Device must be mounted by an authorised installer.
x
Device must be installed in a location that is accessible only to qualified installers
x
The applicable safety and accident prevention regulations must be observed.
x
Device must not be opened. Any faulty device should be returned to manufacturer.
x
For planning and construction of electric installations, the relevant guidelines, regulations
and standards of the respective country are to be considered.
x
KNX bus allows you to remotely send commands to the system actuators. Always make
sure that the execution of remote commands do not lead to hazardous situations, and
that the user always has a warning about which commands can be activated remotely.
DISPOSAL
The crossed-out bin symbol on the equipment or packaging means the product must not be included with
other general waste at the end of its working life. The user must take the worn product to a sorted waste
centre, or return it to the retailer when purchasing a new one. An efficient sorted waste collection of the
environmentally friendly disposal of the used device, or its subsequent recycling, helps avoid the potential
negative effects on the environment and people’s health, and encour
ages the re-use and/or recycling of the
construction materials.
Eelectron spa
Via Monteverdi 6
I-20025 Legnano (MI) - Italia
Tel: +39 0331 500802 Fax: +39 0331 564826
Email: [email protected] Web: www.eelectron.com