Single-phase Digital Energy meters - Direct connection 63A  

 

Product and Applications description 

 

• This

 Energy-meter provides the essential measurement capabilities required to monitor a 

single phase electrical installation. 
 

• 0.25

-5 (63) A, Class B, 230 VAC 50 Hz, -25 °C ... +55 °C, 4 Quadrants, 2 Tariffs. 

• Active Energy Class B (according to EN

-50470) and Reactive Energy Class 2 (according 

to IEC 62053-23) 

• Direct connected (up to 63 A)

 

• LCD display and 3 push

-button keys (to read Energies, V, I, PF, F, P, Q and to configure 

some parameters) 

• 1 push botton and 1 LED dedicated to KNX.

 

• Display with 8 

digits. 

• Self supplied (by the input voltage itself).

 

 

Device is intended to be installed on DIN rail. 

 

Display 

 

 

 

 

Energy value 

 

kWh / kvarh display 

 

Running tarif,called tarif 

 

Energy export (received)  
Energy import (delivered) 

 

Energy value “Partial”

 

 

Push botton and LED dedicatet to KNX 

 

Metrological LED 

 

Commands 

 

 

Scroll Key: This key is used to scroll pages and to modify 
parameters value. Its pushing is accepted only if it is 
shorter than 1.5 second.. 

 

OK key: This key is used alone to enable a new menu 
function or to confirm a parameter value during its 
modification. Its pushing is accepted only if shorter than 
1.5 seconds  

 

ESC key: This key is used alone to exit from a sub-menu, 
to cancel a parameter modification or to go back to the 
main page. In these cases, its pushing is accepted only 
<1.5 seconds  

 

A long pushing (>1.5 seconds) of the “ESC key” is used in 

the Partial Energy Registers Pages to reset their values.  

 

A long pushing (>5 seconds) is used in the Main Energy 
Registers Pages to reset their values 

 

Device Switch-on and Main Page 

 

 

Main Page: 
This page appears not only at device switch on, but also in case for 30 seconds no key is 
pushed. The value is the sum of 2 registers: 
 
Imported Act. Energy Tariff T1 + Imported Act. Energy Tariff T2. (or, alternatively, the sum of 
the Exported ones). 

 

Main Menu 

 

 

 

Tariff 1-2 Energy Register List   Instantaneous Measurement List 
 

 

 

 

 

Energy Register Reset Procedure 

 

 

Diagnostic Message 

 

 

Error Condition 

If the display shows these messages, 
the meters has got a malfunction and 
must be replaced. 

 
 

Wiring Diagram 

 

 

(*) This fuse is recommended if Neutral is not earthed 

 

Service and Maintenance 

 
It should not be necessary to recalibrate device during its lifetime as it is an electronic meter 
with no moving parts with electronics and voltage and current sensors that do not naturally 
degrade or change with time under specified environmental conditions. If a degradation in 
the performance is observed the device has probably been partly damaged and should be 
sent  for  repair  or  exchanged.  If  the  meter  is  dirty  and  needs  to  be  cleaned,  use  lightly 
moistened tissue with a water based mild detergent. 
Make sure no liquid goes into the meter as this could damage the meter. 

Summary of Contents for PM10D01KNX

Page 1: ...eriore a 1 5 secondi Una pressione lunga 1 5 secondi del tasto ESC viene utilizzata per resettare i valori dei contatori parziali d Energia Una pressione lunga 5 secondi viene utilizzata per resettare i valori dei contatori dell Energia totale Accensione dispositivo e pagina principale Pagina principale Questa pagina appare non solo all accensione del dispositivo ma anche nel caso in cui per 30 se...

Page 2: ...Tariff 2 VAC 230 20 Input impedance kΩ 224 Connection terminals POZIDRI V Screwdriver for mains terminals head with Z PZ2 Screwdriver for tariff terminals slotted head mm 0 8 x 3 5 Terminal capacity main current paths solid wire min max mm2 1 65 33 stranded wire with sleeve min max mm2 1 65 33 Terminal capacity for tariff solid wire min max mm2 1 4 stranded wire with sleeve min max mm2 1 2 5 Envir...

Page 3: ...modification or to go back to the main page In these cases its pushing is accepted only 1 5 seconds A long pushing 1 5 seconds of the ESC key is used in the Partial Energy Registers Pages to reset their values A long pushing 5 seconds is used in the Main Energy Registers Pages to reset their values Device Switch on and Main Page Main Page This page appears not only at device switch on but also in ...

Page 4: ...olation class SELV circuit Tariff Tariff 1 open contact Tariff 2 VAC 230 20 Input impedance kΩ 224 Connection terminals POZIDRI V Screwdriver for mains terminals head with Z PZ2 Screwdriver for tariff terminals slotted head mm 0 8 x 3 5 Terminal capacity main current paths solid wire min max mm2 1 65 33 stranded wire with sleeve min max mm2 1 65 33 Terminal capacity for tariff solid wire min max m...

Reviews: