P/N 3101917-EN • REV 02 • ISS 11DEC14
3 / 3
Calibrating the touch screens
After the touch screen controllers have been mapped, you can
calibrate the touch screens. For best results, we recommend that you
perform a 4-point calibration first and then the 25-point linearization.
Caution:
Equipment damage hazard. Only use your fingers to
calibrate the touch screen. Do not use a stylus, pencil, or any other
mechanical object that could damage the touch screen.
To calibrate the touch screens:
1. On the Settings tab, under Linearization Style, select 25 Points,
and then click Apply.
2. On the General tab, select the first USB Controller icon.
3. On the Tools tab, click the Clear and Calibrate button, and then
perform the 4-point calibration. See Figure 6.
Press each target point until it changes color and OK is displayed
on the screen.
4. On the Tools tab, click the Linearization button, and then perform
the 25-point linearization. See Figure 6.
5. If you are using two monitors, on the General tab, select the
second USB Controller icon, and then repeat steps 3 and 4 above.
Figure 6: Calibration target points
Specifications
Power supply
120 V, 60 Hz, 1.5 A 180 W max.
Power consumption
41 Watts (PF = 0.64)
Aspect ratio
16:10
Maximum resolution
1680 × 1050 at 60 Hz
Maximum color depth
32-bit
Dimensions (W × H × D)
20.2 × 15.9 × 8.7 in.
(51.3 × 40.4 × 22.1 cm)
Speakers (built-in)
2 W
Weight
15.3 lbs. (6.9 kg) with touch screen and
base
Regulatory information
FCC compliance
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.