Operation
D397-53-880 Issue C
4
Operation
4.1
Profibus system information
The Profibus module is for connection to a Profibus DP network and operates as a V0 slave only.
The Profibus master requires a GSD file for each slave. The GSD file for this slave is contained on the CD supplied
with the unit and has the file name "EDW0C5F.GSD", which is registered with the Profibus Association.
When configuring your system the "ID" number will be 0C5F and the unit's description will be “Edwards_GXS/
CXS_Pump”.
Note:
The GSD file should not be altered.
4.2
Quick start set up instructions
1. Install the module and connect the cables as described in
2. Set the address switches on the Profibus module. See
.
3. Apply power (or power cycle the Profibus Module, for example by disconnecting then reconnecting the power
connector).
4. Load the GSD file into your Profibus system configurator.
5. Select "Edwards_GXS/CXS_Pump" as a slave and set the address to match the address switches.
6. Select Module 11 to provide on and off control of the pump and select Module 992 to monitor pump alert state.
Add other Profibus software modules as required.
4.3
Front panel display
Figure 6 - Profibus front panel display