Figure 1: Heat sink assembly installation 

 

 

Installing a monitor module  

Caution: 

Eq

uipment damage hazard. This product is sensitive to 

electrostatic discharge (ESD). To avoid damage, follow accepted ESD 

handling procedures. 

To install a monitor module: 

1.  Plug the cable harness and ribbon cable into the monitor module 

as shown in Figure 2. Ensure the cable connections are secure. 

2.  For a power supply monitor module, align the module to the guide 

posts on slot 3 of the rail chassis.  

 

For a booster supply monitor module, align the module to the 

guide posts on slot 3 or slot 5 of the rail chassis, whichever is 

closest to the heat sink assembly. 

3. 

Route the cable harness over and behind the bottom rail and 

connect it to P2 on the heat sink assembly. Push in until the 

connector clicks. 

4. 

Route the ribbon

 cable under the bottom rail and connect it to P3 

on the heat sink assembly. 

5.  Plug the module into the rail connectors and lock it into place using 

the snap rivet fasteners. 

Figure 2: Power supply to monitor module cable connections 

 

 
Figure 3 shows a primary power supply and booster power supply 

installed in a chassis before they are wired. 

Figure 3: Primary and booster power supplies installed in a 

chassis 

 

 

Wiring 

Install and wire these power supplies in accordance with applicable 

national and local codes, ordinances, and regulations. 

Mains power wiring 

Connect the mains power wiring after all power supplies have been 

installed. No more than one primary power supply and three booster 

supplies may be connected to a single mains AC circuit. All mains 

power wiring must be double insulated. 

WARNING: 

Electrocution hazard. To avoid personal injury or death 

from electrocution, remove all sources of power and allow stored 

energy to discharge before installing or removing equipment. Ensure 

that the mains power cannot be inadvertently switched on. 

#8-32 lock nut

(4 places) 

#6-32 x 3/4 threaded standoff

(2 places)

#6-32 x 1/2 pan head screw

#6 lock washer

#6 flat washer

(2 places)

J8

J9

J10

J11

Right mounting area for installing

booster power supply

P2

TB1

H

120 VAC

G

N

P3

TB2

P2

+BATTERY-

MON

TEMP

P2

J4

P3

P6

Cable harness

(P/N 250187)

Ribbon cable

P/N 250189 (primary monitor module)

P/N 250188 (booster monitor module)

P3

P3

TB2

MON

TEMP

J8

J9

J10

J11