Edwards Signaling SuperDuct ESD-4WJ Technical Bulletin Download Page 2

 

 

 

 

Technical Bulletin  

 

SuperDuct Four-Wire Duct Smoke Detector 

Related documents 

In addition to this document, important information regarding 
the proper installation and maintenance of duct smoke 
detectors is provided in the following standards: 

• NFPA 

70 

National Electrical Code

 

• NFPA 

72 

National Fire Alarm Code

 

• NFPA 

90A 

Installation of Air Conditioning and 

Ventilating Systems

 

• UL 

268A 

Smoke Detectors for Duct Applications

 

• ULC 

529 

Smoke Detectors for Fire Alarm Systems

 

• NEMA

 Guide for Proper Use of Smoke Detectors in Duct 

Applications

 

Duct smoke detector limitations 

SuperDuct duct smoke detectors will not operate without 
electrical power. 

SuperDuct duct smoke detectors will not operate as designed 
outside of the listed electrical and environmental 
specifications. 

SuperDuct duct smoke detectors will not sense smoke unless 
the ventilation system is operating and the sensor’s cover is 
properly installed. 

SuperDuct duct smoke detectors may not operate as designed 
unless the duct detector is installed in accordance with these 
instructions and all applicable national and local codes as 
determined by the local authority having jurisdiction. 

Product description 

Overview 

The SuperDuct Four-Wire Duct Smoke Detector is used to 
detect smoke under extended temperature ranges in self-
contained commercial HVAC units, such as those typically 
found on building rooftops. In self-contained commercial 
HVAC units, the HVAC equipment is enclosed in a single 
package to protect the internal components (compressor, 
condensing unit, heating coils, etc.) from adverse 
environmental conditions. Hinged or removable service panels 
provide access to the equipment. 

WARNING: 

The SuperDuct duct smoke detector is not 

intended as a substitute for open area protection. 

The SuperDuct duct smoke detector (see Figure 1) comprises a 
controller and one or two sensors. Its primary function is to 
provide early warning of an impending fire and shut down the 
HVAC unit in order to prevent smoke from circulating 

throughout the building. It is typically used to detect smoke in 
the supply side of the HVAC system but can provide 
supervision of the return side as well.  

Note: 

Install supply-side sensors at a point downstream from 

the supply fan and air filters and return-side sensors at a point 
before the return air is diluted by outside air.  

Fan

Fan

FACP

Outside

air

Smoke

sensor

CO

sensor

2

Return

air

Exhaust

Smoke
sensor

Supply

air

Filter

Coil

HVAC

controls

Test/reset

station

Next controller

CO sensor output

Sensor

controller

Damper

Power

distribution

panel

Rooftop HVAC unit

 

Figure 1: Duct smoke detector application diagram 

The controller is designed for multiple operating voltages and 
provides relay contacts for connection to fire alarm systems, 
HVAC controls, and other auxiliary functions. It can be 
attached to a sensor and installed as a single unit or it can be 
installed separate from the sensor. In installations where the 
duct smoke detector’s controls and indicators are hidden from 
view, a remote test/reset station can be connected to the 
controller to provide these functions. 

Note: 

In installations using two sensors, the duct smoke 

detector does not differentiate which sensor signals an alarm 
or trouble condition. 

The sensor uses a process called differential sensing to prevent 
gradual environmental changes from triggering false alarms. A 
rapid change in environmental conditions, such as smoke from 
a fire, causes the sensor to signal an alarm state but dust and 
debris accumulated over time does not. When the sensor’s 
ability to compensate for environmental changes has reached 
its limit (100% dirty), the sensor signals a trouble condition.  

Air is introduced to the duct smoke detector’s sensing 
chamber through a sampling tube that extends into the HVAC 
duct and is directed back into the ventilation system through 
an exhaust tube. The difference in air pressure between the 

Summary of Contents for SuperDuct ESD-4WJ

Page 1: ...schedule 9 Sensor tests 9 Controller tests 10 Remote test reset station tests 10 Troubleshooting 11 Cleaning the duct smoke sensor 11 Introduction This document provides technical information for the...

Page 2: ...ensors Its primary function is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from circulating throughout the building It is typically used to dete...

Page 3: ...amount of condensation to which the sensor is exposed Sensor description The sensor see Figure 2 comprises a plastic housing a printed circuit board a clear plastic cover an exhaust tube and a samplin...

Page 4: ...ampling tube can be installed with or without the cover in place and can be rotated in 45 degree increments to ensure proper alignment with duct airflow Alarm Trouble Dirty and Power status LEDs Stand...

Page 5: ...th accessories Supply voltage Standby current Alarm current 24 Vdc 77 9 mA 124 3 mA 24 V at 50 Hz 215 3 mA 307 0 mA 24 V at 60 Hz 220 0 mA 316 5 mA 120 V at 50 Hz 91 0 mA 89 0 mA 120 V at 60 Hz 79 0 m...

Page 6: ...normal state the Power LED on both the sensor and the controller are on and all other LEDs are off Alarm state The SuperDuct duct smoke detector enters the alarm state when the amount of smoke partic...

Page 7: ...uns to ensure proper connection supervision Run all field wiring to the controller through the knockouts located at the bottom of the controller housing Maintain a 1 4 inch separation between power li...

Page 8: ...Sampling tubes are ordered separately Installing the sampling tube from the front of the detector The sampling tube can also be installed from the front of the detector as shown in Figure 7 This metho...

Page 9: ...M 16 AUX 1 Contact NC 7 AUX 2 Contact NO 17 AUX 1 Contact NO 8 AUX 2 Contact NC 18 AUX 2 Contact COM 9 24V AC DC In 19 18 Vdc Output 10 24V AC DC In 20 18 Vdc Output N AC neutral TB3 1 CO2 Output L AC...

Page 10: ...reset the sensor by pressing the test reset switch for two seconds Verify that the controller s Alarm LED turns off Controller dirty test The controller dirty test checks the controller s ability to i...

Page 11: ...ose or missing secure the cover to the sensor housing 3 Replace sensor assembly Sensor s Power LED is off 1 Check the controller s Power LED If it is off determine why the controller does not have pow...

Page 12: ...and a lint free cloth to remove dirt and other contaminants from the gasket on the sensor s cover 3 Squeeze the retainer clips on both sides of the optic housing then lift the housing away from the pr...

Page 13: ...Technical Bulletin SuperDuct Four Wire Duct Smoke Detector 13 8 706 7 750 8 150 2 275 5 450 5 400 1 375 2 275 5 450 5 800 6 200 6 756 1 900 1 900 1 100 3 250 Figure 12 Mechanical dimensions...

Page 14: ...Technical Bulletin 14 SuperDuct Four Wire Duct Smoke Detector 5 400 1 375 1 900 13 55 13 95 14 51 2 72 5 45 Figure 12 Mechanical dimensions continued...

Page 15: ...JP1 when the controller is connected to two sensors 2 Alarm initiation contacts shown in normal condition Contacts close on alarm 3 Supervision relay contacts shown in normal condition Contacts chang...

Page 16: ...Technical Bulletin 16 SuperDuct Four Wire Duct Smoke Detector...

Reviews: