background image

In family living units with more than one bedroom area or with bedrooms

on more than one floor, more than one smoke alarm will be needed, as

shown in Figure 2.

In  addition  to  smoke  alarms  outside  of  the  sleeping  areas,  NFPA  72

requires the installation of a smoke alarm on each additional story of the

family living unit, including the basement.  These installations are shown in

Figure 3.  The living area smoke alarms should be installed in the living

room or near the stairway to the upper level, or in both locations.  The

basement smoke alarm should be installed in close proximity to the stair-

way leading to the floor above.  When installed on an open joisted ceiling,

the alarm should be placed on the bottom of the joists.  The alarm should

be  positioned  relative  to  the  stairway  so  as  to  intercept  smoke  coming

from a fire in the basement before the smoke enters the stairway.

IMPORTANT CONSIDERATION

We recommend replacing your alarm(s) every ten (10) years; why:

·

Dust, dirt, and other environmental contaminants can affect your alarm over

a prolonged period.

·

Fast changing industry consensus standards and codes on all alarms

make  it  advisable  to  periodically  upgrade  your  alarm  to  maximize  life

safety.

·

Assurance that your smoke alarm needs are kept abreast with the con-

stantly improving electronic technology.

·

Smoke alarms are recognized as one of the lowest cost ways to protect

dwelling inhabitants against the danger of fire(s).  It makes good com-

mon  sense  to  periodically  replace  and  update  your  smoke  alarm  that

contributes so much to life safety.

MOUNTING LOCATION

This smoke alarm can be mounted on a ceiling or wall with equal effi-

ciency in either location.

·

Ceiling location—alarm should be mounted as close as possible to the

center of a hallway or room.  If this is not possible, the edge of the alarm

should be at least 4 inches from any wall.

·

Wall location—locate the top of the alarm at least 4 inches and not more

than 12 inches from the ceiling.

Figure 4:  RECOMMENDED SMOKE ALARM MOUNTING LOCATIONS

Figure 1:  A SMOKE ALARM SHOULD BE LOCATED BETWEEN THE SLEEP-

ING AREA  AND THE REST OF THE FAMILY LIVING UNIT.

Where  to  Locate  the  Required  Smoke  Alarms  in  New  Construction.

All  of  the  smoke  alarms  specified  for  existing  construction  are  required,

and, in addition, a smoke alarm is required in each bedroom.

Are More Smoke Detectors Desirable?  

The required number of smoke

alarms may not provide reliable early warning protection for those areas

separated by a door from the areas protected by the required smoke alarms.

For this reason, it is recommended that the householder consider the use

of additional smoke alarms for those areas for increased protection.  The

additional areas include: basement, bedrooms, dining room, furnace room,

utility room and hallways not protected by the required smoke alarms.  The

installation of smoke alarms in kitchens, attics (finished or unfinished), or

garages  is  not  normally  recommended,  as  these  locations  occasionally

experience conditions that can result in improper operation.

Figure 2:  IN FAMILY LIVING UNITS WITH MORE THAN ONE SLEEPING

AREA, A SMOKE ALARM SHOULD BE PROVIDED TO PROTECT EACH

SLEEPING AREA IN ADDITION TO ALARMS REQUIRED IN BEDROOMS.

Figure 3:  A SMOKE ALARM SHOULD BE LOCATED ON EACH STORY.

Figure 5:  RECOMMENDED SMOKE ALARM LOCATION IN ROOMS WITH

SLOPED, GABLED, OR PEAKED CEILINGS.

The placement of the alarm is critical if maximum speed of fire detec-

tion is desired.  Thus, a logical location for an alarm is the center of the

ceiling.  At this location, the alarm is closest to all areas of the room.

WHERE SMOKE ALARMS SHOULD BE PUT IN

MOBILE HOMES

In mobile homes built after about 1978 that were designed and insu-

lated to be energy-efficient, smoke alarms should be installed as described

in the section above.

In  older  mobile  homes  that  have  little  or  no  insulation  compared  to

today’s standards, uninsulated metal outside walls and roofs can transfer

heat and cold from outdoors, making the air right next to them hotter or

colder than the rest of the inside air.  These layers of hotter or colder air

can prevent smoke from reaching a smoke alarm.  Therefore, put smoke

alarms in such units only on inside walls, between 4 and 12 inches (10

and 30 cm) from the ceiling.  If you are not sure about the insulation level

in your mobile home, or if you notice that the walls or ceiling are unusually

hot or cold, put the alarm on an inside wall.

Summary of Contents for 517TH Series

Page 1: ...iode and sound its alarm horn all other units will sound the alarm horn with red indicator light emitting diodes remaining off The test knob of your alarm simulates actual smoke conditions FIRE PROTECTION PLAN This Smoke Alarm can quickly alert you to the presence of smoke it cannot prevent fire Please note that there are hazards against which smoke detection may not be effective such as smoking i...

Page 2: ...ther living unit is tested IMPORTANT NOTE WHAT SMOKE ALARMS CANNOT DO Smoke alarms will not work without power Battery operated alarms will not work without batteries with dead batteries or if the batter ies are not installed properly AC powered alarms will not work if their AC power supply is cut off by an electrical fire an open fuse or circuit breaker or for any other reason If you are concerne...

Page 3: ... OF THE FAMILY LIVING UNIT Where to Locate the Required Smoke Alarms in New Construction All of the smoke alarms specified for existing construction are required and in addition a smoke alarm is required in each bedroom Are More Smoke Detectors Desirable The required number of smoke alarms may not provide reliable early warning protection for those areas separated by a door from the areas protecte...

Page 4: ...as or next to bathrooms with showers The moisture in humid air can enter the sensing chamber as water vapor then cool and condense into droplets that cause a nuisance alarm Install alarms at least 10 feet 3 meters away from bath rooms In very cold or very hot environments or in unheated buildings or outdoor rooms where the temperature can go below or above the operating range of the alarm Temperat...

Page 5: ...ce no closer than 12 inches from the smoke alarm MAINTENANCE After your alarm has been in operation for a period of time or if it was in stalled prior to the completion of all building construction your alarm may have become more sensitive due to dirt build up in the alarm s optic sensing cham ber which could cause nuisance alarms or could cause activation from small amounts of smoke build up If t...

Page 6: ...EATES AN OBSCURATION THAT SIMULATES SMOKE THIS MEANS THE UNIT WILL GO INTO ALARM WITHOUT A FIRE CONDI TION LIMITED WARRANTY Providing Purchaser or Distributor notifies us promptly if within two 2 years from date of shipment from Edwards Company equipment or parts manufactured by us fail to function properly under normal use because of defects in material or workmanship demonstrated to our satisfac...

Reviews: