background image

IMPORTANT:  Failure to follow full cleaning instructions could result

in damage to this smoke alarm.

DO NOT remove all alarms at the same time for cleaning

.

1. Turn off electrical power to the alarm.

2. Twist the alarm counter-clockwise to remove it from its mounting plate.

3. Unplug the connector from the back of the alarm.  Do not remove the wire

connection; leave the connection for your replacement alarm or jumper

plug.  Remove the battery.

4. Select three (3) standard size wash buckets and fill them each with one

gallon of normal tap water (

distilled or de-ionized treated water is rec-

ommended as a final rinse

 

if water is extremely hard in your area

).

5. Add 1/8 cup of Ivory dishwashing liquid to the first bucket of water and

allow it to mix thoroughly, then place one dirty alarm into the soap water

mixture until it becomes completely covered or submerged.

NOTE:  If the alarms are exceptionally dirty, you may wish to first wipe off any

excess dirt before washing alarm so as not to dirty the wash water too quickly.
DO NOT open alarm for cleaning.
WARNING:    ONLY  IVORY  DISHWASHING  LIQUID  IS  TO  BE  USED.

OTHER BRANDS ARE NOT RECOMMENDED AND MAY CAUSE YOUR

ALARM TO MALFUNCTION.

6. Allow alarm to soak for approximately 10 minutes (longer if extremely

dirty).  Then agitate for 5 or 10 seconds to flush out any remaining dirt left

inside alarm’s housing.

7. Remove alarm from wash water and transfer directly to one of the first

rinse buckets containing clear water.  Again, allow alarm to become com-

pletely submerged, agitate once more for 5 or 10 seconds to remove soap

residue.

8. Finally, transfer alarm to your second and final rinse bucket, repeating

method found in Step 7, then remove alarm to a clean dry area for a

LIMITED WARRANTY

Providing Purchaser or Distributor notifies us promptly if within two (2) years from date of
shipment from Edwards Company, equipment or parts manufactured by us fail to function
properly under normal use because of defects in material or workmanship demonstrated
to our satisfaction to have existed at the time of delivery or because examination proves
them not to be operating within the specified limit of calibration, the Company, reserving
the right to either inspect them in your hands or request their return to us, will at our
option repair or replace at our expense F.O.B. shipping point, such equipment or parts
determined by us to be defective, if returned transportation prepaid by Purchaser.  Specific
products may carry a greater or lesser warranty but if so they will be so identified.

Replacement parts and factory repairs are warranted for a period of ninety (90) days from
date of shipment from the Edwards Company.

The foregoing shall not apply to equipment that shall have been altered or repaired after
shipment to you by anyone except our authorized employees or agents and the Company
will not be liable in any event for alterations or repairs except those made with its written
consent.  Purchaser shall be solely responsible for determining suitability for use and the

Company shall in no event be liable in this respect.  The equipment or parts manufactured
by others but furnished by us will be repaired or replaced only to the extent of the original
manufacturer's guarantee.  No guarantee whatsoever is given as to electronic tubes, and
the Company shall have no repair or replacement obligations as to these.  Our obligations
and liaibilities hereunder shall not be enforceable until such equipment has been fully paid
for.  Purchaser agrees that if the products sold hereunder are resold by purchaser, he will
include in the contract for resale, provisions which limit recoveries against us in accordance
with this section.  THE FOREGOING OBLIGATIONS ARE IN LIEU OF ALL OTHER OBLIGATIONS
AND LIABILITIES INCLUDING NEGLIGENCE AND ALL WARRANTIES OF MERCHANTABILITY
OR OTHERWISE, EXPRESS OR IMPLIED IN FACT OR BY LAW, AND STATE OUR ENTIRE AND
EXCLUSIVE LIABILITY AND BUYER'S EXCLUSIVE REMEDY FOR ANY CLAIM OF DAMAGES
AND IN CONNECTION WITH THE SALE OR FURNISHING OF GOODS OR PARTS, THEIR DESIGN,
SUITABILITY FOR USE, INSTALLATION OR OPERATION.  WE WILL IN NO EVENT BE LIABLE
FOR ANY DIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES WHATSOEVER, AND OUR
LIABILITY UNDER NO CIRCUMSTANCES WILL EXCEED THE CONTRACT PRICE FOR THE
GOODS FOR WHICH LIABILITY IS CLAIMED.

Edwards Signaling

90 Fieldstone Court, Cheshire, CT  06410

Phone:  1-203-699-3300

period of 48 hours to allow it to thoroughly dry.

WARNING:  SMOKE ALARMS ARE TO BE AIR DRIED ONLY.  DO NOT

PLACE ALARM IN OVEN, MICROWAVE OR USE A HOT AIR BLOWER

TO ACCELERATE DRYING TIME.  THIS COULD RESULT IN DAMAGE

TO YOUR SMOKE ALARM.
IMPORTANT:  IT IS RECOMMENDED TO CHANGE WASH AND RINSE

WATER AFTER FIVE (5) ALARMS.  IF YOUR ALARMS ARE EXTREMELY

DIRTY, WATER SHOULD BE CHANGED MORE FREQUENTLY.

In the event you experience difficulty in the cleaning of your smoke alarm or if

you have any questions, please contact Edwards or your local distributor.

WARNING:

If the smoke alarm does not work properly, do not try and fix it yourself.  This

will void your warranty.  DO NOT TRY TO FIX IT YOURSELF.

IMPORTANT:  Edwards recommends alarms be tested a minimum of once

a week.

WARNING:  Never use an open flame of any kind to test your alarm.  You

may ignite and damage the alarm as well as your home.  The test feature of

your alarm accurately simulates smoke conditions and test the alarm’s func-

tions as required by Underwriters Laboratories.

WARNING:  Do not cover, tape, or otherwise block the openings of your

smoke alarm.  These openings are designed to allow air to pass through your

smoke alarm, thus sampling the air around the alarm.

  FAILURE TO REGULARLY CLEAN THIS SMOKE ALARM WILL RESULT

IN FALSE ALARMS.  A BUILD UP OF DUST CREATES AN OBSCURA-

TION THAT SIMULATES SMOKE.  THIS MEANS THE UNIT WILL GO INTO

ALARM WITHOUT A FIRE CONDITION.