4
The Small Systems range comprises 2 module sizes providing nominal capacities of 6, 12 and 18 kW. Units are available in downflow
with Top return and upflow with front and rear return options. Cooling media include direct expansion using air or water/glycol and
chilled water. The Small Systems Range Units are equipped with: Scroll Compressors, Electrode Steam Boiler Humidifiers, Stainless
Steel Tubular Finned Electric Reheat, EU4 Filtration, Belt Driven forward curved Centrifugal Fans, R407C Refrigerant and the latest
BES/BMS compatible range of Delta microprocessor controllers.
DIMENSIONS AND WEIGHTS
Dimensions
(
mm)
Model
06
12
18
Unit W x D
600 x 600
600 x 600
775 x 775
Height
1980
1980
1980
Weight ( kg )
Model
06
12
18
Air Cooled
305
320
340
Chilled Water
250
260
280
EQUIPMENT NOMENCLATURE
D
A
12
B
S
W
S
EC
NOMINAL CAPACITY
06 = 6 kW
12 = 12 kW
18 = 18 kW
A = AIR
C= CHILLED WATER
D = DOWNFLOW
S = DOWNFLOW
DISPLACEMENT
F = UPFLOW FRONT RETURN
B= UPFLOW BOTTOM
RETURN
R= UPFLOW REAR RETURN
VOLTAGE
B = 380-415/3/50
E = 220/3/60
H = 460/3/60
J = 380/3/60
S = STANDARD SCROLL
COMPRESSOR
X = CHILLED WATER
V= VARIABLE SPEED
COMPRESSOR
E = ECX OPTION
W = WITHOUT ECX
D = DUAL COOLING
S = STANDARD CONTROLS
G = GRAPHIC CONTROLS
EC = EC FAN OPTION