AIR COOLED UNITS - COOLING CAPACITIES 60Hz
Notes:
1. Capacities are based on R407C refrigerant.
2. For capacities at other conditions, please refer to the product selection program.
3. Units are also available for R134A applications, please contact the factory.
4. For R410A, please refer to the R410A catalogue or product selection program.
5. Cooling performances are gross. For nett capacities please deduct motor power as outlined on general engineering details page.
AIR COOLED UNITS – COOLING CAPACITIES 50Hz
Model
06
12
18
Air On: 22
o
C, 45% RH
Total Capacity
kW
7.2
13.0
17.4
Sensible Capacity
kW
6.8
12.3
16.3
Air On: 22
o
C, 50% RH
Total Capacity
kW
7.2
13.0
17.4
Sensible Capacity
kW
6.6
11.9
15.8
Air On: 24
o
C, 45% RH
Total Capacity
kW
7.5
13.6
18.1
Sensible Capacity
kW
6.8
12.1
16.3
Air On: 24
o
C, 50% RH
Total Capacity
kW
7.5
13.6
18.1
Sensible Capacity
kW
6.6
11.9
16.0
Scroll Compressor
-
ZR34
ZR61
ZR81
Compressor Input Power
kW
2.3
4.0
5.3
Airflow
m
3
/s
0.5
1.0
1.5
No. of Fans
No.
1
1
1
Fan Motor
kW
0.55
1.10
1.50
No. of Motors
No.
1
1
1
Electric Reheat
kW
6.0
6.0
9.6
No. of Steps
No.
2
2
2
Humidifier Capacity
kg/hr
2
2
3
Humidifier Power
kW
1.5
1.5
2.2
Model
06
12
18
Air On: 22
o
C, 45% RH
Total Capacity
kW
7.3
12.6
18.4
Sensible Capacity
kW
6.9
11.9
17.3
Air On: 22
o
C, 50% RH
Total Capacity
kW
7.3
12.6
18.4
Sensible Capacity
kW
6.7
11.5
16.7
Air On: 24
o
C, 45% RH
Total Capacity
kW
7.6
13.1
19.1
Sensible Capacity
kW
6.9
11.6
17.2
Air On: 24
o
C, 50% RH
Total Capacity
kW
7.6
13.1
19.1
Sensible Capacity
kW
6.7
11.5
16.9
Scroll Compressor
-
ZR28
ZR48
ZR72
Compressor Input Power
kW
2.4
3.8
5.6
Airflow
m
3
/s
1.5
1.0
1.5
No. of Fans
No.
1
1
1
Fan Motor
kW
0.55
1.10
1.50
No. of Motors
No.
1
1
1
Electric Reheat
kW
8.0
8.0
12.8
No. of Steps
No.
2
2
2
Humidifier Capacity
kg/hr
2
2
3
Humidifier Power
kW
1.5
1.5
2.9