6 FUNCTIONS
OUTPUTS
Enabled
Automatism is enabled
Disabled
Automatism is disabled
Blocked
Automatism blocked
Open command
Automatism has commanded CB open operation.
LCB open
Command for CB opening
LCB close
Command for CB closing
COMMANDS
LCB open command
Remotely command the unit to issue the CB opening.
LCB close command
Remotely command the unit to issue the CB closing.
Enable automatism
Automatism enable
Disable automatism
Automatism disable
Table 18: Sectionaliser signals.
3.3 SETTINGS
The sectionaliser algorithm can be configured to work with up to 100 reclosing of fixed time.
NAME
RANGE
STEP
OTHER
Enabled
ON/OFF
Recloser count
1-100
1
Reclosing time
1-500 s
0,5 s
Command time
0,1-15 s
0,1 s
Switchgear name
12 char alphanumeric
Name of associated
switchgear
Table 19: Sectionaliser settings