6 FUNCTIONS
6.2 VOLTAGE PRESENCE DETECTION UNIT
2.1 DESCRIPTION
The voltage presence detection unit (VPD) processes the voltage analog inputs to asses the presence of
voltage on the line. This is done by the comparison with a configurable threshold, as a percentage of the
configurable nominal voltage.
The VPD also signals the event of “phase open/fail” which signals that the voltage on one or two lines is
below the threshold (no signaling is done when there is no voltage on any phase, as this usually means
the main circuit breaker is open, and is of no indication of phase failure).
The VPD also doubles as a dip/surge detector. The maximum deviation from nominal voltage can be
programmed to activate a signal when the voltage is out of nominal range.
The signals “Voltage Presence Signal” and “Phase Open/Fail Signal” are programmable timed alarms
originated from the after-mentioned algorithms.
2.2 SIGNALS
OUTPUTS
Voltage Presence A
Voltage on line A is above threshold
Voltage Presence B
Voltage on line B is above threshold
Voltage Presence C
Voltage on line C is above threshold
Voltage Presence
Voltage on line A/B/C is above threshold
Phase Open/Fail
There is no voltage presence on one or two phases
Voltage Presence Signal
Timed version of “Voltage Presence” signal.
Phase Open/Fail Signal
Timed version of “Voltage Presence Signal”
Swell Voltage Start/Peak/End A
Shows the Start, peak and end values of the swell voltage
on line A.
Sag Voltage Start/Peak/End A
Shows the Start, peak and end values of the sag voltage
on line A.
Swell Voltage Start/Peak/End B
Shows the Start, peak and end values of the swell voltage
on line B.
Sag Voltage Start/Peak/End B
Shows the Start, peak and end values of the sag voltage
on line B.
Swell Voltage Start/Peak/End C
Shows the Start, peak and end values of the swell voltage
on line C.
Sag Voltage Start/Peak/End C
Shows the Start, peak and end values of the sag voltage
on line C.
Table 16: VPD signals.
00110E4
24
Summary of Contents for SGC Series
Page 31: ...6 FUNCTIONS 00110E4 EDP 26 Illustration 8 VPD unit logic diagram ...
Page 53: ...10 SCHEMATICS 10 SCHEMATICS 00110E4 EDP 48 ...
Page 54: ...SGC 49 EDP 00110E4 ...
Page 55: ...10 SCHEMATICS 00110E4 EDP 50 Illustration 13 Connection diagram ...
Page 56: ...SGC Illustration 14 SGC195 Connection diagram 51 EDP 00110E4 ...
Page 58: ...SGC 11 SIZE 53 EDP 00110E4 Drawing 1 Front and side views of SGC180 and SGC195 devices ...
Page 59: ...11 SIZE Drawing 2 Top and bottom view of SGC180 device 00110E4 EDP 54 ...
Page 60: ...SGC Drawing 3 Top and bottom view of SGC195 device 55 EDP 00110E4 ...