INSTALLATION

EXTERNAL AIR INTAKE 

EXTERNAL AIR INTAKE 

In general, we suggest two ways to ensure a proper 
flow of combustion air.

Air intake without direct connection to the 
appliance

Install an intake at floor level with effective area (net of 
the mesh or other protective equipment) of at least 80 
cm2 (10 cm dia.).
To prevent draughts, we recommend installing the 
intake behind the fireplace or behind a radiator.
Installing it in front of the appliance will create 
unpleasant draughts.

Air intake with direct connection to the 
appliance

Install an air intake of effective area (net of the mesh or 
other protective equipment) at least equal to that of the 
air intake at the back of the product.
Connect the air intake to the appliance’s air intake 
with a tube (which may also be flexible).Increase the 
diameter of the pipe if it is not smooth: assess its load 
loss.

We recommend not exceeding a 1 m length and 
curving the tube at most one time, depending on the 
draw of the flue.
The air may be drawn from an adjacent room only if:
•  the flow is taken from permanent and unobstructed 

openings communicating with the outdoors;

•  the adjacent room is never in underpressure 

relative to the outdoors;

•  the adjacent room is not a garage. subject to fire 

hazard, a bathroom or bedroom

•  the adjacent room is not a shared room in the 

condominium

In Italy, UNI 10683 provides that ventilation is sufficient 
even if a pressure difference between the outdoors 
and indoors of no more than 4 PA is guaranteed (UNI 
EN 13384-1). The installer who issues the declaration 
of conformity is responsible for ensuring these 
conditions.

THE FLUE

THE FLUE

:

Further to the general prescriptions for the fumes duct 
and flue, the flue::
•  must serve solely to exhaust fumes
•  must be correctly sized to satisfy the requirements 

of fumes exhaust (EN 13384-1)

•  should preferably be insulated, in steel with a 

circular internal section. If rectangular, the corners 
must have a radius of not less than 20 mm, with a 
ratio of the internal dimensions of <1.5

•  must normally be at least 1.5 metres in vertical 

length

•  must have a constant cross section
•  must be waterproof and thermally insulated to 

ensure a good draw

•  must preferable have a collection chamber for
•  If pre-existing, must be clean, to prevent the fire 

hazard.

•  in general, we recommend fitting a tube inside the 

existing masonry chimney if its diameter is greater 
than 150 mm.

INTUBATED SYSTEM

INTUBATED SYSTEM

:

Further to the general prescriptions for the fumes duct 
and flue, the intubated system:
•  must operate in negative pressure;
•  must be open to inspection
•  must observe local regulations. 

THE CHIMNEY POT 

THE CHIMNEY POT 

•  must be windproof 
•  must have an internal cross section equivalent to 

that of the flue and a fumes outlet at least double 
that of the interior of the flue

•  for dual flues (which should be spaced at least 2 

m apart) the chimney pot receiving the fumes from 
the solid fuel appliance or that from the higher 
storey, must be at least 50 cm higher than the other

•  it must extend beyond the back flow zone (in Italy, 

refer to UNI 10683 point 6.5.8.)

•  it must allow for maintenance of the chimney

VENTILATION AIR EXCHANGE

VENTILATION AIR EXCHANGE

In addition to the combustion air inlet (which must 
draw air from the outside as described above), and 
the booster vents, an opening at least 10x10 cm is size 
must be made for the ventilation air exchange. This 
hole should be made in the cover.

Summary of Contents for 809530

Page 1: ...PELLKAMIN2 12 PELLET FIREPLACE UK Installation use and maintenance 809530 809550 809580 809560...

Page 2: ...version Fitting the components according to the version Pellet loading trapdoor 17 Pellet loading trapdoor 17 Ducted ventilation 18 Ducted ventilation 18 Frontal ventilation kit 21 Frontal ventilation...

Page 3: ...ted up for the first time commissioned by a qualified Edilkamin technician In Italy commissioning by an authorised technician is required by UNI 10683 and is recommended in all countries to ensure bes...

Page 4: ...THAN WOOD PELLETS IN THE HEARTH The product may be soiled the flue may catch fire and environmental damage may ensue cleaning the hearth when hot DO NOT CLEAN THE HEARTH WITH A VACUUM CLEANER WHILE IT...

Page 5: ...3 2 5 60 5 2 5 5 PELLKAMIN2 12 with frontal ventilation and a pellet loading drawer 8 cm smoke outlet 79 93 87 5 12 93 60 5 2 5 60 5 2 5 5 PELLKAMIN2 12 with ducted ventilation and a pellet loading dr...

Page 6: ...E hole for the vents Split Bent Origami Sharp F hole for ventilation air recovery a 10x10 cm hole in the side of the cladding 18 5 19 4 4 18 5 20 70 150 87 5 88 A F C C MEASUREMENTS cm OF HOLES ON PLA...

Page 7: ...ng cod 809530 218 kg cod 809560 271 kg cod 809550 249 kg cod 809580 273 kg kg Energy efficiency classes 2015 1186 Regulation A TECHNICAL DATA FOR RATING THE FLUE which must in any case satisfy the req...

Page 8: ...in a regulatory fashion CONTENTS OF PACKAGE The packaging varies according to the Pellkamin version The packages are described in the Packaging section The air outlet vents are not included in the ver...

Page 9: ...facilitate handling the PELLKAMIN2 12 is fitted with handles B Do not use the air intake or fumes outlet to handle the appliance This may lead to slight misalignments TO UNPACK THE PRODUCT undo screws...

Page 10: ...rround Pellkamin is available in four versions 1 with ducted ventilation and a pellet loading trapdoor see the fitting sections on Ducted Ventilation and Load ing Trapdoor 2 with frontal ventilation a...

Page 11: ...ontal ventilation kit Version 3 with frontal ventilation and pellet loading drawer One package 1 with the Pellkamin frame the two compensation vents the inlet surround One package 2 with the drawer an...

Page 12: ...Ducting for ventilation air Ducting for ventilation air always channel the ventilation warm air the 6 cm diam eter pipe to the outside INSTALLATION IN AN EXISTING FIREBOX INSTALLATION IN AN EXISTING...

Page 13: ...ng wind its safety equipment may switch the fireplace off Contact the authorised Edilkamin Technical Assistance Centre INSTALLATION FLUE SYSTEM FLUE SYSTEM Fumes duct flue and chimney pot Fumes duct f...

Page 14: ...tions THE FLUE THE FLUE Further to the general prescriptions for the fumes duct and flue the flue must serve solely to exhaust fumes must be correctly sized to satisfy the requirements of fumes exhaus...

Page 15: ...tion TERMINAL BOARDS The right side of the appliance seen from the front has a bracket with two terminal boards the upper terminal board low voltage has a pre wired cable for the reset button while th...

Page 16: ...ay that the plug is accessible once the installation is complete Secure the bottom of the base to the floor with 8 mm steel anchor bolts to prevent it from tipping over Position the top of the base 2...

Page 17: ...the plasterboard Secure the loading inlet A Screw A with B Open the loading inlet to reach the screws Insulate the loading tube and make sure that it does not touch the fumes duct The loading tube mu...

Page 18: ...luminium pipe extendible to 1 5 m for connection from the fire box to the fan kit 5 n 2 6 cm aluminium pipe extendible to 3 m for connection from the fan kit to the vent the flanges are incorporated i...

Page 19: ...a Please see the picture of an exemple with pellet loa ding hatch ding hatch E E and vent Label and vent Label F F The instructions for installing the vents are included with the vents themselves NOTE...

Page 20: ...door 2 remove the screws 3 remove the cover panel 4 rotate the fan taking care with the cables to be extracted 5 reinsert the fan 6 repeat the operations to reattach the door and ro tate the box Posi...

Page 21: ...ically connect the fan to the circuit board as shown on the high voltage terminal board to the side poles electrically connect the fan to the circuit board as shown on the high voltage terminal board...

Page 22: ...22 ENGLISH FRONTAL VENTILATION KIT 2 2 4 3 repeat on the other side 4 screws VERSION WITH FRONTAL VENTILATION AND TRAPDOOR LOADING 2...

Page 23: ...pe of installation also ducting or not during the first ignition The ventilation will not function properly if the technician does not adjust the parameters The ventilation will not function properly...

Page 24: ...screw the ceramic front panel to the frame with its support 3 There are 5 screws in all two on each side and one in the centre one in the centre 3 3 replace the metal cover with the drawer Kit 2 and...

Page 25: ...LOADING DRAWER 2 3 Figure 12 Drawer fitted Connecting the pipes for ducting hot air Connecting the pipes for ducting hot air 2 3 repeat on the other side 4 screws VERSION WITH DUCTED VENTILATION AND D...

Page 26: ...the high voltage terminal board to the side poles electrically connect the fan to the circuit board as shown on the high voltage terminal board to the side poles 7 8 9 Line Earth Neutral respectively...

Page 27: ...t operation it is essential that the technician adjusts the parameters according to To ensure correct operation it is essential that the technician adjusts the parameters according to the type of inst...

Page 28: ...e ventilation kit an additional opening of at least 10x10 cm in size is available in one side of the cover for ventilation air recovery any wooden beams are insulated and not resting against the metal...

Page 29: ...the surround on to its supports secure it with the four grub screws included for the side versions fasten it to the bracket with a nut D For versions 2 with frontal ventilation and pellet loading tra...

Page 30: ...onmental compatibility DO NOT burn plastic painted wood coal bark or other such materials in the stove Do not use the product as an incinerator Caution Using fuels other than those specified can damag...

Page 31: ...s ON Flame ignites and grows stable This is the result of manual ignition with ignition button request from Crono power request during stand by request from external contact Ignition has a variable du...

Page 32: ...the type of batteries and the intensity of use Edilkamin and the reseller will not consider claims for battery life under any circumstances If the battery charge is low a warning displays at the top l...

Page 33: ...lay shows figure 4 1 the current time 2 the current room temperature 3 the room temperature setting or manual mode 4 the power level represented by the flames 5 the fan level represented by the fillin...

Page 34: ...3 and displayed as positions 2 and 3 see below The two fans can be adjusted separately First adjust fan 2 and then fan 3 as described below Ventilation setting Press OK once The fan setting displays...

Page 35: ...temperature setpoint is reached To access the function from the main menu as indicated in the Menu section above press the M button Scroll using the buttons and select the function by pressing OK Use...

Page 36: ...ress the M button LOAD PELLETS STAND BY CRONO NIGHT DATE TIME DISPLAY LANGUAGE BEEP INFO TECHNICAL MENU scroll buttons OK button to confirm The following screen will appear Scroll to ENABLE underlined...

Page 37: ...buttons Press the OK button to confirm and select SET Press the M button to go back to the previous screen press the OK button to enter the SET function ENABLE TEMP CHANGE SET scroll buttons OK button...

Page 38: ...ckly Press the OK button to confirm and go to the temperature selection T1 T2 or T3 Press the buttons to switch between the temperatures To continue with other changes press the OK button To choose be...

Page 39: ...n during commissioning Available only in the OFF state If you attempt to activate the function in other states access is not granted To access the function from the main menu as indicated in the Menu...

Page 40: ...Confirm by pressing the OK button for 2 seconds Beep Allows you to enable disable the beep To access the function from the main menu as indicated in the Menu section above press the M button Scroll u...

Page 41: ...N B Any unauthorised modification is forbidden Use spare parts recommended by the manufacturer The use of counterfeit parts results in the guarantee becoming null and void MAINTENANCE Never vacuum ho...

Page 42: ...tray 3 and grate into a non flammable container the ashes may still contain embers and or hot parts Vacuum out the interior of the hearth the bed and the compartment around the grate into which the as...

Page 43: ...nd inspect the system there is an increased risk of the chimney pot catching fire SUMMER SHUTDOWN During the period of disuse keep the fireplaces doors hatches and lids closed We recommend emptying ou...

Page 44: ...sufficient quantity of combustion air Check that the firebox door is closed Check that the grate and fume discharge are clean Check that the external air inlet is free i e the grilles are not obstruct...

Page 45: ...cian MESSAGE PROBLEM SOLUTION H07 Shutdown due to exceeding maximum fumes temperature Check the type of pellet contact the technician if in doubt Contact the technician H08 Shutdown due to overheating...

Page 46: ......

Page 47: ......

Page 48: ...cod 942077 GB 04 19 A 942077 GB w w w e d i l k a m i n c o m...

Reviews: