background image

LMD222 and LMD224 Series 

Operations Manual 

Eberle Design Inc. 

Page 5 

2.2.4 MINIMUM PRESENCE TIME 

When the diode  (1N4148WS) labeled OPT4  is  installed, the LMD Series will limit the 
minimum presence time to 100 milliseconds.  

2.2.5 PULSE MODE (P) 

The Pulse mode will provide a 125 ms ± 25ms width output pulse for each vehicle entering 
the loop. 

2.2.6 CALL MODE (C) 

The Call mode will set the channel output to the Call state (True). This mode can be used 
to provide a continuous Call state to the Controller Unit regardless of the state of the 
detection zone. Loop fault conditions are ignored in this mode. 

2.2.7 OFF MODE (-) 

The Off mode will set the channel output to the No Call state (False).  This mode can be 
used if the channel is not used or not connected to a loop. Loop fault conditions are ignored 
in this mode. 

2.3 SET THE FREQUENCY 

Pressing the FREQ button once will display the Frequency 
Level (1 –  4)  without changing the setting. After pressing 
the  FREQ button  to display the current Frequency Level, 
the setting can then be changed by pressing the FREQ 
button  again. The display will automatically return to the 
normal display after several seconds. 

The  Frequency  level  needs to be changed only if 
interference occurs between adjacent loops connected to different sensor units. 
Interference or crosstalk may manifest itself as chattering of the call output or a detect call 
occurring at the same time as an adjacent unit when there is no vehicle present. If crosstalk 
is suspected, try to separate the frequencies of the channels causing the problem. A 
minimum of 5 KHz separation is recommended. Four frequency levels  are available on 
each channel to assist in alleviating interference affecting more than two units. 

Changing the Frequency Level will cause the channel to retune.  

2.3.1 DISPLAYING THE LOOP FREQUENCY 

The current loop frequency is  displayed by after pressing the FREQ button  to display the 
current Frequency Level. The frequency is shown in KHz with a “-“ symbol displayed both 
before and after the numeric digits shown on the DEFLECTOMETER

®

For example, after pressing the FREQ button once the display sequence might show: 

 

“3”  

  “-“  

  “2”  

  “7”  

  “-“ 

This sequence would indicate Frequency Level “3”  and a loop reference frequency of 27 
KHz. 

2.4 MISCELLANEOUS 

2.4.1 CHANNEL OFF 

If a channel is not to be used, it may be switched off (disabled) by setting the Operational 
Mode to OFF. See section 2.2.6. 

Frequency 

Level 4 

High 

Level 3 

Medium High 

Level 2 

Medium Low 

Level 1 

Low 

Summary of Contents for LMD222

Page 1: ...IS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE LMD222 LMD224 and LMD222 R SERIES INDUCTIVE LOOP MONITOR REVISION AUGUST 2015 pn 888 0222 003 LMD222 and LMD224 Inductive Loop Monitor Operations Manua...

Page 2: ...01 2008 REGISTERED COMPANY INFORMATION CONTAINED HEREIN IS PROPRIETARY TECHNICAL INFORMATION OF EBERLE DESIGN INC PUBLICATION REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS A...

Page 3: ...ff Mode 5 2 3 Set the Frequency 5 2 3 1 Displaying the Loop Frequency 5 2 4 Miscellaneous 5 2 4 1 Channel Off 5 2 4 2 Retune or Reset a Channel 6 2 4 3 Factory Default Settings 6 2 5 Loop Fault Monito...

Page 4: ...ept to the inductive loop detector field that revolutionizes the process of installing and programming a loop detector The new user interface of the LMD Series provides the feedback necessary to the s...

Page 5: ...rle Design Inc Page 2 The unit will detect inductance changes as small as 0 010 L L Each channel is sequentially energized and sampled so as to negate the possibility of crosstalk between loops connec...

Page 6: ...ading 5 This is done by pressing the front panel SENS down button twice If a mid size vehicle located over the roadway loop causes the value 2 to be displayed on the DEFLECTOMETER the sensitivity shou...

Page 7: ...hree seconds Pressing the SENS or SENS button during this interval will modify the Sensitivity Level as described in section 2 1 1 with the DEFLECTOMETER display remaining in the Call Strength mode Pr...

Page 8: ...several seconds The Frequency level needs to be changed only if interference occurs between adjacent loops connected to different sensor units Interference or crosstalk may manifest itself as chatteri...

Page 9: ...cuit loops shorted loops or sudden changes in inductance exceeding 25 of the nominal inductance 2 5 1 CURRENT FAULT If a fault is detected both the DET Red and FLT Yellow LEDs continuously emit a sequ...

Page 10: ...in the vicinity of the saw slot should also be removed so that it is not accidentally pushed back in As a general rule loops with circumference lengths less than 12 feet require 5 turns of wire 12 to...

Page 11: ...to the bottom of the slot and completely encase the loop wire The wire should not be able to move when the sealant has set Ensure that there is enough sealant to completely fill the slot if possible...

Page 12: ...he tuning range of 20 to 2500 microHenry with a Q factor greater than 5 4 4 2 ENVIRONMENTAL TRACKING The detector automatically and continuously compensates for component drift and environmental effec...

Page 13: ...nnel 1 Redundant Loop Input E Channel 1 Loop Input 5 Channel 1 Redundant Loop Input F Channel 1 Output 6 Reserved H Channel 1 Output 7 Reserved J Channel 2 Loop Input 8 Channel 2 Redundant Loop Input...

Page 14: ...eserved N Reserved 12 Reserved P Channel 3 Loop Input 13 Channel 3 Redundant Loop Input R Channel 3 Loop Input 14 Channel 3 Redundant Loop Input S Channel 3 Output 15 Reserved T Channel 3 Output 16 Re...

Reviews: