iCITE
®
DA-Data Aggregator
®
DA-400™
and
iCITE
®
Installation Manual
Eberle Design Inc.
Page
42
b. Verify the SDLC connector chosen has been enabled in the controller if it is a
“secondary” SDLC that has been installed for “future” use but not activated.
Configuration will vary by manufacturer.
c. Verify the wiring connection is not broken, frayed or degraded with a visual
inspection.
d. Verify pin-to-pin continuity on the SDLC cable.
5.9 NO BLUETOOTH TRAVEL TIME INFORMATION
NOTE: – Bluetooth connectivity requires the installation of a USB dongle to establish
connectivity.
a. If travel time data is not displaying in the application, verify the correct connector
on the 5-band antenna (labeled Bluetooth) is properly connected to the USB
dongle input on the face of the unit and that it is fully seated and engaged to
contact the internal pins on the unit.
b. Verify the wiring connection is not broken, frayed or degraded with a visual
inspection.
c. Do not over tighten the connector.
5.10 UNABLE TO CONNECT TO DATA AGGREGATOR VIA ETHERNET CONNECTION
a. Verify the Ethernet cable is not a crossover cable.
b. Verify the Ethernet Cable is not broken, frayed or degraded with a visual
inspection.
c. Check the Ethernet adaptor configuration of your laptop and ensure you have
assigned an IP address in the correct range (192.168.1.xxx).
i. Do not use the same IP address you have selected for the Data
Aggregator (192.168.1.xxx).
d. Open Command Line Interface (CLI) and ping the IP address of the Data
Aggregator to verify connectivity. If unable to ping, connectivity has not been
established.
e. Sometimes a computer needs to be re-booted when the IP configuration has
changed.
f.
Verify the Ethernet Interface is correctly configured with the IPCONFIG command
from the Command Line Interface (CLI). You should see a response of
192.168.1.xxx. (xxx = any value < .100)
g. Configure the default gateway using the Data Aggregator IP address of
192.168.1.20 if needed to force all traffic to assigned IP address.