PRODUCT MANUAL
“FUNCTION” DIP switches four and five are used to specify the baud rate of the
serial input. The options are shown in Table 1 below.
‘FUNCTION’ DIP SWITCH
SW5
SW4
BAUD RATE
OFF
OFF
1200
OFF
ON
2400
ON
OFF
4800
ON
ON
9600
Table 1
“FUNCTION” DIP switches seven and eight are not used an should be left in the
‘OFF’ position.
“FUNCTION” DIP switch number six determines whether this display is to be
used for ‘normal’ serial messages or as the output display for Electronic Displays
Analog-to-Digital converter. If “FUNCTION” DIP switch number six is in the OFF
position, the “ADDRESS” DIP switch specifies the display address as shown in
Tables 2 and 3 below. If “FUNCTION” DIP switch number six is in the ON
position, the “ADDRESS” DIP switch specifies what digits to display as shown in
the section entitled “
“ADDRESS” Switch for Analog-to-Digital converter
Displays:
” below.
“ADDRESS” Switch for Serial Input Displays:
“FUNCTION” DIP switch number six must be in the ‘OFF’ position (see above).
The “ADDRESS” DIP switches are used in binary fashion to generate an address
number. If the address number is zero (all switches in the ‘OFF’ position) or if
the address number is larger than 198, the display uses non-addressable ‘flex’
protocol. If the address number is from 1 to 99 (see samples in Table 2 below),
the display uses 2-digit addressable ‘flex’ protocol. If the address number is from
100 to 198 (see samples in Table 3 on the next page), the display uses 2-digit
addressable protocol.
‘ADDRESS’ DIP SWITCHES
SW8
SW7
SW6
SW5
SW4
SW3
SW2
SW1
ADDRESS
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
01
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
02
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
03
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
04
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
05
OFF
OFF
OFF
OFF
ON
ON
ON
ON
15
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
16
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
17
OFF
OFF
OFF
ON
ON
ON
ON
ON
31
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
32