Edge MTP Tap Module Installation And Testing Download Page 4

Standard Recommended Procedure 003-128 | Issue 4 | September 2018 | Page 4 of 13

6. 

Installing EDGE™ MTP Tap Modules

 

EDGE MTP Tap modules are installed just like their normal EDGE module counterparts. Refer to the Installation 

chapter in SRP-003-794, 

EDGE Solution

, for complete instructions. This chapter covers module installation, 

trouble shooting, and other module-related topics as well.

7. 

Referencing the Test Equipment for an MTP Tap Module

NOTE: 

If using Fluke DTX tester, testing live-to-tap-out, use REMOTE END SETUP (FAR END SOURCE). 

7.1 

Start by powering on the source and meter and allowing a minimum of 5 minutes for them to warm 

up and stabilize. This referencing procedure is if both outputs are being tested at the same time as shown in 

Figures 16 and 17. If the LIVE and TAP portions of the network will be tested at different times, only reference 

one source to a meter (7.2, Steps 1-3 and 6-7). 
 

For multimode systems: 

set the unit to the 850 nm wavelength.

 

For single mode systems: 

Set the unit to the operating wavelength of the system, either 1310  

 

 

 

 

    or 1550 nm. 

To reference the source and two meters:

Step 1: 

Clean and insert the SC-end of   

the SC to LC jumper (Reference Jumper no. 1, 

or 

RJ1

) into the output of the light source.

Step 2: 

Clean and insert the LC end of 

RJ1

 jumper 

into the LC port adapter of  Meter no. 1 (

M1

(Figure 6). 

For multimode only: Wrap the jumper 5 times and       

secure it in a 22 mm mandrel with tape (standard 50 

µm multimode procedure). 

 

Figure 6

Step 3: 

Verify that RJ1 and the light source have an acceptable power level at your system’s wavelength(s) and 

reference this power to 0.00 dB. See the test equipment manufacturer’s instructions for acceptable 

power output of the source.

Step 4: 

Disconnect and move the meter-end LC of 

RJ1

 to Meter no. 2 (

M2

) and repeat step 3. Disconnect M2 

after this step.

Step 5: 

Clean and insert the LC end of 

RJ1

 into a single-mode LC adapter. 

Step 6: 

Clean and install an LC to LC  

jumper- Reference Jumper  

no. 2 (

RJ2

) into 

M1

 and the LC adapter 

(Figure 7)

 

 

 

Figure 7

Light Source

      (Tx)

  Do NOT 

disconnect

   

HPA-0758

    Meter no. 1

          (RX)

          

    

    Meter no. 2

         (RX)

          

 M2

    

0.00

Launch Conditioner for multimode 

only

 Reference 

Jumper no.1

      

RJ1

M1

  Do NOT 

disconnect

  Do NOT 

disconnect

HPA-0759         

   

         LC

    adapter      

   

0.15 dB

multimode only

 RJ1

 Reference 

Jumper no. 2

       

RJ2

M1

 Light 

Source

Summary of Contents for MTP Tap Module

Page 1: ... port to a monitoring device which filters the data and sends it to various software tools for analysis where it is then viewed in application layer software for security threats performance issues or system optimization IMPORTANT Please note that Tap module systems have two outputs for each input which may require two power meters and depending on the system configuration possibly require an addi...

Page 2: ...d Materials The following tools and materials are required for this procedure Two 2 power meters with LC port adapters Two 2 LC LC jumpers One 1 SC LC jumper for the light source Three 3 LC LC single mode adapters Light source with SC port adapter At least one MTP to LC harness with Universal Polarity Wiring Multimode module harness p n H750512TE8 KW003F Single mode module harness p n H900412GE8 K...

Page 3: ... modules must be tested with directionality in mind The source must be always connected to the input of the splitter and a meter must be connected to at least one of the outputs of the splitter Connecting a source to the output of a splitter will result in high attenuation Likewise connecting network transmitters to the output of a splitter can result in damage to the receiver port Thus it is impo...

Page 4: ...either 1310 or 1550 nm To reference the source and two meters Step 1 Clean and insert the SC end of the SC to LC jumper Reference Jumper no 1 or RJ1 into the output of the light source Step 2 Clean and insert the LC end of RJ1 jumper into the LC port adapter of Meter no 1 M1 Figure 6 For multimode only Wrap the jumper 5 times and secure it in a 22 mm mandrel with tape standard 50 µm multimode proc...

Page 5: ... Figure 8 Step 10 Verify that the RJ1 RJ3 mated pair are acceptable with a loss 0 10 dB for multimode and 0 20 dB for single mode Step 11 Disconnect RJ1 s LC connector from the LC adapter and protect it with a clean dust cap Step 12 Leave the LC adapter on the end of RJ3 for the remainder of this procedure since it will be required for mating to theTAP port test harness 7 3 Referencing is now comp...

Page 6: ...ized 50µm 850 nm Bend improved single mode 1310 nm Component Loss max dB 1 Loss max dB 1 MTP mated pair loss 0 35 0 75 LC mated pair loss 0 15 0 25 Splitter 50 50 dB 3 7 3 5 Splitter 70 30 dB 2 4 5 8 2 1 5 8 Fiber attenuation 2 8 dB km 0 4 dB km 1 Insertion loss specifications when mated to other system components of a like performance specification Tap Module A TPA 6133 Near end Budget loss for a...

Page 7: ...tep 1 Install the Light Source RJ1 LC connector adapter on the LC number 2 of a test harness plugged into the front mounted LIVE Port of the MTPTap module Step 2 Install RJ2 s LC connector into the number 1 port of the Edge module Module B in Figure 10 Figure 10 Light Source Test harness M1 RJ2 RJ1 and adapter Do NOT disconnect Do NOT disconnect 0 00 dB Pretium EDGE Module B B 2 3 B 1 2 1 A TPA 61...

Page 8: ...r on the number 1 LC connector of the harness plugged into the LIVE Port of the MTPTap module Figure 11 8 7 Note that steps 8 4 and 8 6 can be combined if using an optical test set with both a source and a meter on one unit This will test two fibers at a time because there will be two sources and meters It is important that the source is always plugged into the transmit even fibers and that the me...

Page 9: ...ystem loss for theTAP system add the loss values of the components that are in the system as illustrated in Figures 12 and 13 Figure 12 Figure 13 Tap Module A TPA 6136 Budget loss for a Tap multimode system using OM4 fiber and 50 50 splitters 0 35 0 35 0 15 3 7 50 50 splitter MTP mated pair MTP mated pair 0 15 0 35 3 7 0 35 0 15 4 7 dB LC mated pair 0 15 LC mated pair Tap port test harness Tap por...

Page 10: ...t Sequence 9 4 To begin testing theTAP portion of the MTPTap module from the A LIVE Port harness to the module TAP port test harness Figure 14 Step 1 Install the Light Source RJ1 LC connector adapter onto the LC number 2 connector of a test harness plugged into the LIVE port of the MTPTap module Step 2 Install RJ2 s LC connector adapter onto the LC number 1 connector of a harness plugged into the ...

Page 11: ...Install the Light Source RJ1 LC connector into LC number 2 port of the Edge module B at the Far End Step 2 Install RJ2 s LC connector adapter onto LC number 2 of the harness plugged into theTAP port of the MTPTap module Module A Figure 15 9 7 Note steps 9 4 and 9 6 CANNOT be combined if using an optical test set with both a source and a meter in one unit TAP port test harness M1 RJ1 Do NOT disconn...

Page 12: ...ource RJ1 LC connector into the number 2 port of the Edge module Module B Step 2 Install Meter 1 RJ2 s LC connector adapter onto LC number 1 of the harness plugged into the front mounted LIVE Port of the MTPTap module Step 3 Install Meter 2 RJ3 s LC connector adapter onto LC number 2 of the harness plugged into theTAP port of the MTPTap module Step 4 Continue testing through on the even fibers of ...

Page 13: ...ll the Light Source RJ1 LC connector adapter onto LC number 2 of the harness plugged into the LIVE Port of the MTPTap module Step 2 Install Meter 1 RJ2 s LC connector into the number 1 port of the Edge module Module B Step 3 Install Meter 2 RJ3 s LC connector adapter onto LC number 1 of the harness plugged into the TAP port of the MTPTap module Step 4 Continue testing through on the even fibers of...

Reviews: