ECS DVD32FP3 Installation And Owner'S Manual Download Page 5

23552-1-0607

Page 5

REQUIREMENTS FOR MASSACHUSETTS

For all side wall horizontally vented gas fueled equipment 

installed  in  every  dwelling,  building  or  structure  used  in 

whole  or  in  part  for  residential  purposes,  including  those 

owned  or  operated  by  the  Commonwealth  and  where  the 

side wall exhaust vent termination is less than seven (7) feet 

above finished grade in the area of the venting, including but 

not limited to decks and porches, the following requirements 

shall be satisfied:

1.  INSTALLATION  OF  CARBON  MONOXIDE 

DETECTORS. At the time of installation of the side wall 

horizontal vented gas fueled equipment, the installing 

plumber  or  gasfitter  shall  observe  that  a  hard  wired 

carbon  monoxide  detector  with  an  alarm  and  battery 

back-up  is  installed  on  the  floor  level  where  the  gas 

equipment is to be installed. In addition, the installing 

plumber or gasfitter shall observe that a battery operated 

or hard wired carbon monoxide detector with an alarm 

is  installed  on  each  additional  level  of  the  dwelling, 

building or structure served by the side wall horizontal 

vented gas fueled equipment. It shall be the responsibility 

of the property owner to secure the services of qualified 

licensed professionals for the installation of hard wired 

carbon monoxide detectors

 

a.  In the event that the side wall horizontally vented 

gas fueled equipment is installed in a crawl space or 

an attic, the hard wired carbon monoxide detector 

with alarm and battery back-up may be installed on 

the next adjacent floor level.

 

b.  In the event that the requirements of this subdivision 

can  not  be  met  at  the  time  of  completion  of 

installation, the owner shall have a period of thirty 

(30) days to comply with the above requirements; 

provided, however, that during said thirty (30) day 

period, a battery operated carbon monoxide detector 

with an alarm shall be installed.

2.  APPROVED  CARBON  MONOXIDE  DETECTORS. 

Each carbon monoxide detector as required in accordance 

with the above provisions shall comply with NFPA 720 

and be ANSI/UL 2034 listed and IAS certified. 

3.  SIGNAGE. A metal or plastic identification plate shall be 

permanently mounted to the exterior of the building at a 

minimum height of eight (8) feet above grade directly in 

line with the exhaust vent terminal for the horizontally 

vented gas fueled heating appliance or equipment. The 

sign shall read, in print size no less than one-half (1/2) 

inch  in  size, 

“GAS  VENT  DIRECTLY  BELOW. 

KEEP CLEAR OF ALL OBSTRUCTIONS”.

4.  INSPECTION. The state or local gas inspector of the 

side wall horizontally vented gas fueled equipment shall 

not  approve  the  installation  unless,  upon  inspection, 

the inspector observes carbon monoxide detectors and 

signage installed in accordance with the provisions of 

248 CMR 5.08(2)(a) 1 through 4.

 

(b)  EXEMPTIONS:  The  following  equipment  is 

exempt from 248 CMR 5.08(2)(a)1 through 4: 

 

 

1.  The  equipment  listed  in  Chapter  10  entitled 

“Equipment Not Required To Be Vented” in the 

most current edition of NFPA 54 as adopted by 

the Board; and 

 

 

2.  Product Approved side wall horizontally vented 

gas  fueled  equipment  installed  in  a  room  or 

structure separate from the dwelling, building or 

structure used in whole or in part for residential 

purposes. 

 

(d)  MANUFACTURER  REQUIREMENTS  -  GAS 

EQUIPMENT  VENTING  SYSTEM  NOT 

PROVIDED. When the manufacturer of a Product 

Approved side wall horizontally vented gas fueled 

equipment does not provide the parts for venting the 

flue gases, but identifies “special venting systems”, 

the following requirements shall be satisfied by the 

manufacturer:

 

 

1.  The  referenced  “special  venting  system” 

instructions shall be included with the appliance 

or equipment installation instructions; and

 

 

2.  The “special venting systems” shall be Product 

Approved by the Board, and the instructions for 

that system shall include a parts list and detailed 

installation instruction.

 

(e)  A copy of all installation instructions for all Product 

Approved side wall horizontally vented gas fueled 

equipment,  all  venting  instructions,  all  parts  lists 

for venting instructions, and/or all venting design 

instructions  shall  remain  with  the  appliance  or 

equipment at the completion of the installation. 

Summary of Contents for DVD32FP3

Page 1: ...the type of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certi ed kit is used The Tahoe Direct Vent Zero Clearance Gas Fireplace Heater GAS FIR...

Page 2: ...DVVK 4F Flex Vent 30 Vertical Termination 31 32 Log Placement 33 34 Operating Instructions 35 36 Wiring Diagram Standing Pilot 37 Lighting Instructions Standing Pilot 38 Troubleshooting Standing Pilot...

Page 3: ...damagedin any way it should be replaced only with a complete glass frame assembly from Empire See parts list on Page 45 for ordering DONOTusethis replaceifanyparthasbeenunder water Immediatelycallaqua...

Page 4: ...odorant in escaped gas can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas ma...

Page 5: ...hall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certi ed 3 SIGNAGE Ametalorplasticidenti cationplateshallbe permanently mounted to the exterior of the building at a minimum height of eigh...

Page 6: ...local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 Natural Gas and Propane Installation Code or CSA B149 1 in Canada Available from the American National Standards Institute Inc 11 West...

Page 7: ...p vent kit HORZ 4 to 6 114 3mm to 152mm wall thickness DVVK 4T Top vent kit horz 8 to 12 203mm to 305mm wall thickness DVVK 4R Rear vent kit horz 5 to 7 127mm to 178mm wall thickness DVVK 4V Vertical...

Page 8: ...d the front edge of the appliance Figure 2 Combustible Material No greeting cards stockings or ornamentation of any type should be placed on or attached to the replace The ow of heat can ignite combus...

Page 9: ...ss than 1 2 psig 3 5kPa Attention If one of the procedures results in pressures in excess of 1 2 psig 14 w c 3 5 kPa on the replace gas valve it will result in a hazardous condition Checking Manifold...

Page 10: ...ver plate located on the back of the replace These will be used to close the top ue and inlet openings 3 Insert the insulation retainer bracket and insulation into the top ue pipe before reinstalling...

Page 11: ...wall strip and then screw into pre drilled holes on replace side Measure from face of replace to face of drywall strip to determine nal depth Figure 8 Vent Pipe Clearance Note Maintain one inch 1 of c...

Page 12: ...se joints are not required to be sealed Only non combustible material using 300 F minimum adhesive if needed can be applied as facing to the replace surround Flush Mount Mantel Installation Figure 10...

Page 13: ...A at hard combustible burnable surface 2 A raised wooden platform 3 Four 4 corner supports Example Four 4 concrete masonry blocks These supports must be positioned so they contact all four 4 perimeter...

Page 14: ...10 1 2 229mm to 267mm n a VENT CAP A PIPE LENGTH WALL FIRESTOP THIMBLE A B Models 6 5 1 8 to 6 1 2 130mm to 165mm DVD 32 36 42 48 9 8 1 8 to 9 1 2 206mm to 241mm DVD 32 36 42 12 11 1 8 to 12 1 2 283mm...

Page 15: ...stalled in the horizontal run the length of the horizontal run MUSTbe reduced by 18 45cm This does not apply if the 45 degree elbows are installed on the vertical part of the vent system Reduce 3 for...

Page 16: ...to 7 178mm below grade level The 7 178mm is measured from the center of the horizontal vent pipe as it penetrates through the wall Ensure the sidewall venting clearances are observed If venting system...

Page 17: ...ation See Figure 23 When locating the hole it must be noted that the bottom of the cap must be 12 305mm above the ground level and top of the cap must be no less than 18 457mm below a combustible proj...

Page 18: ...23552 1 0607 Page 18 Figure 26 Figure 27 Figure 28 24 24 MINIMUM CLEARANCE TO COMBUSTIBLES EXAMPLES TOP VENT RUN...

Page 19: ...3 for every 90 elbow Example According to the chart the maximum horizontal vent length is 20 and if two 45 degree elbows are required in the horizontal vent it must be reduced to 17 The maximum numbe...

Page 20: ...0607 Page 20 Figure 30 Figure 31 Figure 32 Figure 33 Model Maximum Pipe Length H1 DVD32 24 DVD36 24 DVD42 18 DVD48 N A Model Maximum Pipe Length H1 DVD32 24 DVD36 24 DVD42 24 DVD48 6 EXAMPLES REAR VE...

Page 21: ...that minimizes the number of offsets and horizontal vent length Since it is very important that the venting system maintain its balance between the combustion air intake and the ue gas exhaust certain...

Page 22: ...ter line of the regulator I clearance to service regulator vent outlet 6 feet 1 8m minimum J clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance...

Page 23: ...at each succeeding vent component is securely tted and locked into the preceding component in the vent system Figure 36 WALL THIMBLE MAXIMUM OF THREE 90 ELBOWS MAXIMUM OF TWO 90 ELBOWS Special Venting...

Page 24: ...s of the 10 inch x 10 inch hole previously cut Secure with nails or screws The heat shields of the restops MUST BE placed towards the top of the hole Continue the vent run through the restops See Figu...

Page 25: ...23552 1 0607 Page 25 Figure 39 Figure 41 See Horizontal Termination Page 26 and Vertical Termination Pages 31 32 Figure 40 FRAMING AND FINISHING continued...

Page 26: ...l the vinyl siding standoff SD 950 Vinyl siding standoff SD 950 will be installed between the vent terminationandtheexteriorwall SeeFigure42 Thishorizontalvent terminationboltsontothe atportionofthevi...

Page 27: ...etermine whether or not the extension thimble is to be used If the combustible wall depth is over 5 3 8 137mm then the extension thimble should be used Figure 1 3 Installthewallthimbleassemblythrought...

Page 28: ...1 1 2 screws Ensure upward slope 11 From inside Attach the inlet tube to the collar on the back of the replace or the rigid venting system using 3 self tapping screws 12 Seal the 4 102mm diameter ue o...

Page 29: ...high temperature sealant to the opposite end of the tube on the inside of the tube The end with the gasket will attach to the back of the unit Continue with Step 13 Connecting to Rigid Vent System If...

Page 30: ...e fireplace flue with a minimum of two screws provided See Figure C 11 Attach the Outer Vent pipe to the 7 dia Collar on the fireplace with a large band clamp provided Sealant may also be used on the...

Page 31: ...ks and in extreme cases holes These components should immediately be replaced 2 Remove the cap and shine a ashlight down the vent Remove any bird nests or other foreign material 3 Check for evidence o...

Page 32: ...ventadaptoron replaceineither the vertical or horizontal position replace horizontal and vertical pipe lengths elbows and horizontal or vertical termination kit Allventsystemcomponentslockintoplacebys...

Page 33: ...n burner pan ATTENTION Do not place decorative rock on logs or burner The decorative rock should only be placed on the replace oor EMBER MATERIAL PLACEMENT ON BURNER 10 After all logs are positioned p...

Page 34: ...ove glass frame spring assembly 5 Place front logs 1 2 and 3 between grates and main burner Align notches on front logs with locator tabs in base 6 Place middle log 4 between front and rear loop of bu...

Page 35: ...erate an additional one 1 to two 2 minutes before you turn the gas control knob from the PILOT position to the ON position This time period allows the millivolts electrical current to build up to a su...

Page 36: ...in the remote and immediate heat is desired turn the REMOTE OFF ON switch from the REMOTE position to the ON position Electric 120 volt Operated Remote Control FREC Connectthegreenandred strippedandb...

Page 37: ...23552 1 0607 Page 37 Figure 57 OPTIONAL THERMOSTAT OPTIONAL WALL SWITCH STANDING PILOT WIRING DIAGRAM...

Page 38: ...TO FIREPLACE FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a re or explosion may result causing property damage personal injury or loss of life A This a...

Page 39: ...ame Be sure the wire connections from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket Check the thermopile with a millivolt meter Take t...

Page 40: ...nsuccessful ignition trials 3 Flashes Main burner ame failed 4 times during a single heating cycle 4 Flashes Interrupt power for 5 seconds to reset control Steady Flash Flame detected out of sequence...

Page 41: ...Use only the wall switch or remote control switch to turn the gascontrolon off Anyattemptedrepairsoradjustmentsshould beperformedbyaquali edservicetechnician Applyingforce or attempted repair may res...

Page 42: ...onnector for shorts Replace spark electrode assembly c Refer to installation instructions troubleshooting guide for issues such as venting Repair as required The conversion shall be carried out in acc...

Page 43: ...onto burner assembly 18 Loosen screw and attach a manometer or pressure gauge to the outlet pressure tap of the control valve 19 Turn on the gas supply Turn on the electrical supply to the appliance C...

Page 44: ...other airborne particles to cling to the glass surface Also initial paint curing may deposit a slight lm on the glass It is therefore recommended that the glass be cleaned two or three times with a n...

Page 45: ...27 N A N A R 7599 R 7599 FRONT Y LOG 28 R 7580 R 7537 R 7695 R 7695 BURNER TUBE 29 17235 17235 21260 21260 LOG LOCATOR BRACKET 30 17185 17158 17208 17208 BURNER BASE PLATE ASSEMBLY 31 R 7624 R 7624 R...

Page 46: ...3 42 30 33 34 35 41a 31 36 37a 38 52 40a 52 22 23 24 26 27 22 25 26 29 28 14 13 13 13 13 8 9 10 11 12 16 19 20 21 17 18 DIRECT IGNITION BURNER ASSEMBLY MILLIVOLT BURNER ASSEMBLY 5 PIECE LOG ASSEMBLY 4...

Page 47: ...speed blower assembly is completed Wiring The appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code A...

Page 48: ...10 VOLT AC JUNCTION BOX WHITE SPEED CONTROL FAN SWITCH GROUND BLACK FAN 1 FBB4 BLOWER ASSEMBLY COMPLETE 2 R7649 FAN CONTROL 3 R4192 SPEED CONTROL KNOB 4 R4186 SPEED CONTROL FBB4 OPTIONAL VARIABLE SPEE...

Page 49: ...ed with full brick pattern at the bottom Move side panels rearward until the back edge meets the rear brick panel Slide side brick panels down so they rest on rebox bottom and brick joints match up wi...

Page 50: ...HERRINGBONE DVP1SH DVD32 DVP2SH DVD36 DVP3SH DVD42 DVP4SH DVD48 Simulated Brick Panels The simulated brick panels were designed to enhance the appearance of your replace imitating the look of authent...

Page 51: ...ne the Part Number not the Index Number and the Description of each part from the following appropriate illustration and list Be sure to give all this information Fireplace Number Part Description Fir...

Page 52: ...2 1 0607 Page 52 SERVICE NOTES Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empirecomfort...

Reviews: