Table 1 - Ratings and Capacities
Boiler
No.
(1)
Input
Mbh
(1)
Heating
Capacity Mbh
(2)
**
Net I=B=R
Rating Water
Mbh
No.
of
Burners
(3)
Recommended
Air Cushion
Tank
Water
Content
(Gals.)
High
Altitude
Input
50
50
42
37
1
15
2.4
45,000
75
75
63
55
2
15
4.0
67,500
100
100
83
72
2
30
4.0
90,000
125
125
104
90
3
30
5.6
112,500
150
150
124
108
3
30
5.6
135,000
175
175
143
124
4
30
7.2
157,000
200
200
165
143
4
30
7.2
180,000
250
250
205
178
5
30
8.8
225,000
300
299
243
214
6
60
10.4
270,000
EXPLANATORY NOTES
-- All boilers are design certifi ed for installation on noncombustible fl oor.
-- For installation on combustible fl oors use combustible fl oor kit.
-- Recommended chimney height 20 feet. In special cases where conditions permit, chimney height may be
reduced to 10 feet. Refer to the latest revision of NFGC part 11.
-- Electric service to be 120 Volts, 15 Amps, 60 Hz.
-- The MEA number for the this boiler is 19-79-E.
(1) Input rating for sea level to 2,000 ft. (610m) above sea level.
United States, over 2000 ft (610m) above sea level. Reduce input rate 4% for every 1000 ft (304m) above sea
•
level.
Canada, 2000 ft (610m) to 4500 (1350m) above sea level. Reduce input per table.
•
Canada, over 4500 ft (1350m) above sea level. Contact Provincial authority having jurisdiction.
•
(2) Net I=B=R Water Ratings shown based on piping and pickup allowance of 1.15. Consult manufacturer
before selecting boiler for installations having unusual piping and pickup requirements, such as
intermittent system operation, extensive piping systems, etc.
For forced hot water systems where boiler and all piping within area to be heated, boiler may be selected
on basis of its heating capacity.
(3) Tank sized for non-ferrous baseboard or radiant panel systems. Increase size for cast iron baseboard and
radiation.
STANDARD EQUIPMENT: Boiler Jacket, Cast Iron Boiler Battery, High Limit Control, Vent Damper Relay,
Theraltimeter Gauge, Circulator With Return Piping To Boiler, Main Gas Burners, Combination 24 Volt Gas Control
(Includes Automatic Gas Valve, Gas Pressure Regulator, Automatic Pilot, Safety Shutoff, Pilot Flow Adjustment, Pilot
Filter), A.S.M.E. Relief Valve, Drain Valve, Spill Switch, Rollout Switch, Automatic Vent Damper. Not Shown Are:
Wiring Harness, Thermocouple, Non-linting Safety Pilot.
OPTIONAL EQUIPMENT: Intermittent Electric Ignition Pilot System.
RATINGS & DATA - NATURAL GAS & PROPANE GAS