![ECR International UTICA BOILERS TRB4075 Installation, Operation & Maintenance Manual Download Page 51](http://html1.mh-extra.com/html/ecr-international/utica-boilers-trb4075/utica-boilers-trb4075_installation-operation-and-maintenance-manual_2356165051.webp)
51
Boiler
Model
Riello
Oil
Burner
Model
ECR Oil
Burner Part
Number
4075
40F3
550003548
4090
40F3
550004237
5100
40F5
550003551
Boiler
Model
Riello
Oil
Burner
Model
ECR Oil
Burner Part
Number
6130
40F5
550003554
7165
40F5
550003557
T
ABLE 15: RIELLO 40F CHIMNEY VENT PRELIMINARY BURNER SETTINGS
Boiler
Model
Head
Type
Insertion
Depth
Firing
Rate
[GPH]
Combustion
Liner
Nozzle
Mfr.
Nozzle
Type
Pump
Pressure
[PSI]
Head
Setting
Air
Setting
Rated
AFUE
Efficiency
[%]
4075
Reverse
2.75"
0.75
Oval
Delavan
0.65x60W
150
1
3.6
87.0
4090
Reverse
2.75"
0.90
Oval
Delavan
0.75x90B
140
2
3.5
86.0
5100
Standard
2.75"
1.00
None
Delavan
0.75x60B
175
1
2.4
87.0
6130
Standard
2.75"
1.30
V6
Delavan
1.00x45B
175
2
3.6
87.0
7165
Standard
2.75"
1.65
V7
Delavan
1.35x60B
150
4
8.0
87.0
Timings
Pre-purge
12 seconds
B
urner settings provided are for initial startup only. Final adjustments must be made using combustion test
instruments.
Table 15
- Riello
40F Chimney Vent Preliminary Burner Settings
17 - OIL BURNER, NOZZLE, & AIR SETTINGS
PN 240013278, Rev. A [12/31/2020]