38
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
fire department.
!
!
NOTICE
Use of CSA approved corrugated, semi-rigid
stainless steel tubing with polyethylene jacketing
is approved for use with boilers following tubing
manufacturer's instructions.
Use of flexible
"appliance whip"
gas tubing is not
allowed per NFPA 54.
WARNING
Fire, explosion, asphyxiation and burn hazard.
Boiler piping and gas connections shall be leak
tested before placing boiler in operation. Failure
to follow these instructions and or improper
installation could result in death or serious injury.
!
Required Gas Supply Pressure
at Maximum Firing Rate
Natural Gas
Liquid Propane
Min.
Max.
Min.
Max.
3.5" w.c. 10.5" w.c.
8.0" w.c.
13.0" w.c.
(0.87 kPa) (2.61 kPa)
(1.99 kPa)
(3.23 kPa)
DANGER
Fire Hazard. Do not use matches, candles, open
flames, or other methods providing ignition
source. Failure to comply will result in death or
serious injury.
!
7 - GAS SUPPLY PIPING
NOTICE
If overheating occurs or gas supply fails to shut
off, do not turn off or disconnect electrical supply
to pump. Shut off gas supply at location external
to the boiler.
• Install boiler so that gas ignition system components
are protected from water (dripping, spraying,rain,
etc.) during appliance operation and service
(circulator replacement, condensate trap, control
replacement, etc.).
• Gas meter and supply pipes must be capable of
delivering the listed quantity of gas in addition to
demand from any other appliances in the house.
Boiler requires a minimum 3/4” (19.5 mm) gas
supply pipe.
• Support piping with hooks, straps, bands, brackets,
hangers, or building structure components to prevent
or dampen excessive vibrations and prevent strain on
gas connection. Boiler will not support piping weight.
• Use thread (joint) compound (pipe dope) suitable for
liquefied petroleum gas.
• Leak test boiler and gas line connections before
placing boiler into operation.
7.1 General
• Use piping materials and joining methods acceptable
to authority having jurisdiction. In absence of such
requirements:
• USA - National Fuel Gas Code, ANSI Z223.1/
NFPA 54.
• Canada - Natural Gas and Propane Installation
Code, CAN/CSA B149.1
•
Install external field sourced manual main gas
shutoff valve, ground joint union, and sediment trap
upstream of gas controls in accordance with state
and local requirements. See Figure 7-1.
• Size and install gas piping system to provide
sufficient gas supply to meet maximum input at not
less than minimum supply pressure.
• Boiler shall be isolated from the gas supply piping
system by closing its individual manual shutoff valve
during any pressure testing of gas supply piping
system at test pressures equal to or less than 1/2 psi
(3.40 kPa - 34.47 mbar).
GAS SUPPLY REQUIRED:
MODEL
NATURAL GAS (A)
LIQUID PROPANE (E)
MAHF-75
92
ft
3
/h
(
2.60
m
3
/h)
38 ft
3
/h
(
2.61
m
3
/h)
MAHF-100
MACF-115
114
ft
3
/h
(
3.22
m
3
/h)
47 ft
3
/h (1.32 m
3
/h)
MAHF-125
118 ft
3
/h (3.30 m
3
/h)
51 ft
3
/h (1.48 m
3
/h)
MACF-150
143 ft
3
/h (4.00 m
3
/h)
61 ft
3
/h (1.72 m
3
/h)
MAHF-165
153 ft
3
/h (4.30 m
3
/h)
66 ft
3
/h (1.85 m
3
/h)
MAHF-205
191 ft
3
/h (5.40 m
3
/h)
82 ft
3
/h (2.30 m
3
/h)
240013503 REV A, [03/15/2022]
Summary of Contents for UTICA BOILERS MACF-115
Page 2: ...MACF 150...
Page 4: ...MAHF 125...
Page 77: ...73 A 1 MODEL 75 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 78: ...74 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 79: ...75 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013503 REV A 03 15 2022...
Page 80: ...76 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013503 REV A 03 15 2022...
Page 81: ...77 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 82: ...78 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 117: ...33 PN 240012875 REV D 03 15 2022 MODEL 75 100 HEAT ONLY 75 100 HEAT ONLY WIRING DIAGRAM...
Page 118: ...34 PN 240012875 REV D 03 15 2022 MODEL 125 HEAT ONLY 125 HEAT ONLY WIRING DIAGRAM...
Page 119: ...35 PN 240012875 REV D 03 15 2022 MODEL 165 HEAT ONLY 165 HEAT ONLY WIRING DIAGRAM...
Page 120: ...36 PN 240012875 REV D 03 15 2022 115 COMBI WIRING DIAGRAM MODEL 115 COMBI...
Page 121: ...37 PN 240012875 REV D 03 15 2022 MODEL 150 COMBI 150 COMBI WIRING DIAGRAM...
Page 122: ...38 PN 240012875 REV D 03 15 2022 MODEL 205 COMBI 205 COMBI WIRING DIAGRAM...
Page 128: ...44 PN 240012875 REV D 03 15 2022 LOW WATER CUTOFF LOW WATER CUTOFF DETAIL NO NO YES...
Page 133: ...49 PN 240012875 REV D 03 15 2022 3 FAULT SOLUTION SECTIONS...