20
5 - COMBUSTION AIR AND VENT PIPING
75/100/115/125/150
Vent
Type
Vent Size
Vent
Material
Intake
(L1***)
Exhaust
(L2***)
Combined Vent
(L1+L2)
Max
Min
Max
Min
Max
Min
Twin
Pipe
2"
(60 mm)
Polypropylene
85 ft
(25.9 m)
6 ft
(1.8 m)
85 ft
(25.9 m)
6 ft
(1.8 m)
170 ft
(51.8 m)
12 ft
(3.6 m)
3"
(80 mm)
Polypropylene
49 ft
(15 m)
6 ft
(1.8 m)
147 ft
(45 m)
6 ft
(1.8 m)
196 ft
(60 m)
12 ft
(3.6 m)
Flexible
Exhaust* w/
Rigid 3" PP
Intake
CPVC**
(PVC optional
on intake
ONLY)
Coaxial
Vent Size
Material
Natalini
DuraVent
Centrotherm
Max
Min
Max
Min
Max
Min
2"/4"
(60 mm/100 mm)
Polypropylene
32.8 ft
(10 m)
6 ft
(1.8 m)
27.88 ft
(8.5 m)
6 ft
(1.8 m)
24.60 ft
(8.5 m)
6 ft
(1.8 m)
3"/5"
(80 mm/128 mm)
*For vertical runs only
**In Canada ULC S636 and in the USA UL1738 schedule 40 CPVC are the only approved Vent Material to be used as
an alternative to Polypropylene venting for the exhaust pipe.
*** See Figures 5-8 to 5-10 for L1 & L2 details.
VENT MATERIAL OPTIONS
(Maximum Equivalent Vent Length Shown)
165/205
Vent
Type
Vent Size
Vent
Material
Intake
(L1***)
Exhaust
(L2***)
Combined Vent
(L1+L2)
Max
Min
Max
Min
Max
Min
Twin
Pipe
2"
(60 mm)
Polypropylene
85 ft
(25.9 m)
6 ft
(1.8 m)
85 ft
(25.9 m)
6 ft
(1.8 m)
170 ft
(51.8 m)
12 ft
(3.6 m)
3"
(80 mm)
Polypropylene
100 ft
(30.5 m)
6 ft
(1.8 m)
100 ft
(30.5 m)
6 ft
(1.8 m)
200 ft
(60.9 m)
12 ft
(3.6 m)
Flexible
Exhaust* w/
Rigid 3" PP
Intake
CPVC**
(PVC optional
on intake
ONLY)
Coaxial
Vent Size
Material
Natalini
DuraVent
Centrotherm
Max
Min
Max
Min
Max
Min
2"/4"
(60 mm/100 mm)
Polypropylene
3"/5"
(80 mm/128 mm)
32.8 ft
(10 m)
6 ft
(1.8 m)
32.8 ft
(10 m)
6 ft
(1.8 m)
32.8 ft
(10 m)
6 ft
(1.8 m)
*For vertical runs only
**In Canada ULC S636 and in the USA UL1738 schedule 40 CPVC are the only approved Vent Material to be used as
an alternative to Polypropylene venting for the exhaust pipe.
***See Figures 5-8 to 5-10 for L1 & L2 details.
240013503 REV A, [03/15/2022]
Summary of Contents for UTICA BOILERS MACF-115
Page 2: ...MACF 150...
Page 4: ...MAHF 125...
Page 77: ...73 A 1 MODEL 75 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 78: ...74 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 79: ...75 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013503 REV A 03 15 2022...
Page 80: ...76 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013503 REV A 03 15 2022...
Page 81: ...77 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 82: ...78 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 117: ...33 PN 240012875 REV D 03 15 2022 MODEL 75 100 HEAT ONLY 75 100 HEAT ONLY WIRING DIAGRAM...
Page 118: ...34 PN 240012875 REV D 03 15 2022 MODEL 125 HEAT ONLY 125 HEAT ONLY WIRING DIAGRAM...
Page 119: ...35 PN 240012875 REV D 03 15 2022 MODEL 165 HEAT ONLY 165 HEAT ONLY WIRING DIAGRAM...
Page 120: ...36 PN 240012875 REV D 03 15 2022 115 COMBI WIRING DIAGRAM MODEL 115 COMBI...
Page 121: ...37 PN 240012875 REV D 03 15 2022 MODEL 150 COMBI 150 COMBI WIRING DIAGRAM...
Page 122: ...38 PN 240012875 REV D 03 15 2022 MODEL 205 COMBI 205 COMBI WIRING DIAGRAM...
Page 128: ...44 PN 240012875 REV D 03 15 2022 LOW WATER CUTOFF LOW WATER CUTOFF DETAIL NO NO YES...
Page 133: ...49 PN 240012875 REV D 03 15 2022 3 FAULT SOLUTION SECTIONS...