5 - COMBUSTION AIR AND VENT PIPING
5.10 (3" / 80 mm Only) Flexible Vent System
Flexible Pipe Minimum & Maximum Vent Lengths
3” [80 mm]
Diameter Pipe
100/115/125/150
165/205
Min
Max
Min
Max
Natalini
Exhaust
6 ft
[1.8 m]
75 ft
[22.8 m]
6 ft
[1.8 m]
50 ft
[15.2 m]
Intake
6 ft
[1.8 m]
50 ft
[15.2 m]
6 ft
[1.8 m]
50 ft
[15.2 m]
DuraVent
®
Exhaust
6 ft
[1.8 m]
82 ft
[24.9 m]
6 ft
[1.8 m]
50 ft
[15.2 m]
Intake
6 ft
[1.8 m]
50 ft
[15.2 m]
6 ft
[1.8 m]
50 ft
[15.2 m]
Centrotherm
Exhaust
6 ft
[1.8 m]
52 ft
[15.8 m]
6 ft
[1.8 m]
50 ft
[15.2 m]
Intake
6 ft
[1.8 m]
50 ft
[15.2 m]
6 ft
[1.8 m]
50 ft
[15.2 m]
Z-Dens
Exhaust
NA
6 ft
[1.8 m]
50 ft
[15.2 m]
Intake
Single Wall Elbows - Equivalent Length
3" [80 mm]
45° bend
0.82 ft [0.25 m]
90° bend
1.64 ft [0.50 m]
• Maximum vent lengths based on equivalent straight
runs only. Include rigid pipe and fittings in overall
equivalent length calculations.
• Flexible venting installations use single wall
polypropylene to pass flue gasses to base of chimney,
then flexible venting to get them to termination at the
top.
• Combustion air is not supplied through masonry
chimney. Combustion air must be from outside using 3"
[80 mm] single wall polypropylene.
• Position boiler to use minimum of rigid single wall
polypropylene venting to the chimney.
• Follow venting manufacturer's instructions on assembly
and clearances to maintain.
•
Avoid sharp bends in flexible venting.
FIGURE 5-24 - (3" / 80 mm Only) Flexible Venting
System CAN BE USED ON ALL SIZES
Combustion
Air
Vent Terminal
Flexible Vent
Note
Flexible vent systems shall only be run vertical.
Horizontal runs before adapting to flexible must
be rigid pipe.
Rigid Vent
240013354 REV A [07/01/2021]
Summary of Contents for Utica Boilers MAC-115
Page 2: ...MAC 205...
Page 4: ...MAH 165...
Page 77: ...73 APPENDIX A WIRING DIAGRAMS A 2 MODEL 125 Heat Only 240013354 REV A 07 01 2021...
Page 78: ...74 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013354 REV A 07 01 2021...
Page 79: ...75 APPENDIX A WIRING DIAGRAMS A 1 MODEL 115 Combi 240013354 REV A 07 01 2021...
Page 80: ...76 APPENDIX A WIRING DIAGRAMS A 4 MODEL 150 Combi 240013354 REV A 07 01 2021...
Page 81: ...77 APPENDIX A WIRING DIAGRAMS A 5 MODEL 205 Combi 240013354 REV A 07 01 2021...
Page 117: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Page 118: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Page 119: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Combi PN 240011430 REV O 07 01 2021...
Page 120: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Page 121: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Page 126: ...43 Low Water Cutoff Detail LOW WATER CUTOFF NO NO YES PN 240011430 REV O 07 01 2021...
Page 131: ...48 3 FAULT SOLUTION SECTIONS PN 240011430 REV O 07 01 2021...