20
100/115/125/150
Vent
Type
Vent Size
Vent
Material
Intake
(L1)
Exhaust
(L2)
Combined Vent
(L1+L2)
Max
Min
Max
Min
Max
Min
Twin
Pipe
2"
(60 mm)
Polypropylene
85 ft
(25.9 m)
6 ft
(1.8 m)
85 ft
(25.9 m)
6 ft
(1.8 m)
170 ft
(51.8 m)
12 ft
(3.6 m)
3"
(80 mm)
Polypropylene
49 ft
(15 m)
6 ft
(1.8 m)
147 ft
(45 m)
6 ft
(1.8 m)
196 ft
(60 m)
12 ft
(3.6 m)
Flexible
Exhaust* w/
Rigid 3" PP
Intake
CPVC**
(PVC optional
on intake
ONLY)
Coaxial
Vent Size
Material
Natalini
DuraVent
Centrotherm
Max
Min
Max
Min
Max
Min
2"/4"
(60 mm/100 mm)
Polypropylene
32.8 ft
(10 m)
6 ft
(1.8 m)
27.88 ft
(8.5 m)
6 ft
(1.8 m)
24.60 ft
(8.5 m)
6 ft
(1.8 m)
3"/5"
(80 mm/128 mm)
*For vertical runs only
**In Canada ULC S636 and in the USA UL1738 schedule 40 CPVC are the only approved Vent Material to be used as
an alternative to Polypropylene venting for the exhaust pipe.
5 - COMBUSTION AIR AND VENT PIPING
VENT MATERIAL OPTIONS
(Maximum Equivalent Vent Length Shown)
165/205
Vent
Type
Vent Size
Vent
Material
Intake
(L1)
Exhaust
(L2)
Combined Vent
(L1+L2)
Max
Min
Max
Min
Max
Min
Twin
Pipe
2"
(60 mm)
Polypropylene
85 ft
(25.9 m)
6 ft
(1.8 m)
85 ft
(25.9 m)
6 ft
(1.8 m)
170 ft
(51.8 m)
12 ft
(3.6 m)
3"
(80 mm)
Polypropylene
100 ft
(30.5 m)
6 ft
(1.8 m)
100 ft
(30.5 m)
6 ft
(1.8 m)
200 ft
(60.9 m)
12 ft
(3.6 m)
Flexible
Exhaust* w/
Rigid 3" PP
Intake
CPVC**
(PVC optional
on intake
ONLY)
Coaxial
Vent Size
Material
Natalini
DuraVent
Centrotherm
Max
Min
Max
Min
Max
Min
2"/4"
(60 mm/100 mm)
Polypropylene
3"/5"
(80 mm/128 mm)
32.8 ft
(10 m)
6 ft
(1.8 m)
32.8 ft
(10 m)
6 ft
(1.8 m)
32.8 ft
(10 m)
6 ft
(1.8 m)
*For vertical runs only
**In Canada ULC S636 and in the USA UL1738 schedule 40 CPVC are the only approved Vent Material to be used as
an alternative to Polypropylene venting for the exhaust pipe
240013354 REV A [07/01/2021]
Summary of Contents for Utica Boilers MAC-115
Page 2: ...MAC 205...
Page 4: ...MAH 165...
Page 77: ...73 APPENDIX A WIRING DIAGRAMS A 2 MODEL 125 Heat Only 240013354 REV A 07 01 2021...
Page 78: ...74 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013354 REV A 07 01 2021...
Page 79: ...75 APPENDIX A WIRING DIAGRAMS A 1 MODEL 115 Combi 240013354 REV A 07 01 2021...
Page 80: ...76 APPENDIX A WIRING DIAGRAMS A 4 MODEL 150 Combi 240013354 REV A 07 01 2021...
Page 81: ...77 APPENDIX A WIRING DIAGRAMS A 5 MODEL 205 Combi 240013354 REV A 07 01 2021...
Page 117: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Page 118: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Page 119: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Combi PN 240011430 REV O 07 01 2021...
Page 120: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Page 121: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240011430 REV O 07 01 2021...
Page 126: ...43 Low Water Cutoff Detail LOW WATER CUTOFF NO NO YES PN 240011430 REV O 07 01 2021...
Page 131: ...48 3 FAULT SOLUTION SECTIONS PN 240011430 REV O 07 01 2021...