34
APPENDIX A - CONTROL MODULE
A.6 Boiler High Limit Temperature Controller
• When water temperature reaches setpoint, controller
ends heating cycle.
• When water temperature drops below setpoint minus
differential, controller restarts heat cycle to re-heat
boiler water.
• If water temperature exceeds maximum allowed
temperature (220°F or 104°C), controller enters manual
reset lockout state.
• For models having reset capability, press any onboard
button or cycle power to reset.
Figure 18 - Basic Control Algorithm Example
A.7 Troubleshooting
• Following service procedures are provided as general
guide.
• On lockout and retry models, meter readings between
gas control and ignition module must be taken within
trial for ignition period. Once ignition module shuts
off, lockout models must be reset through key buttons
and display. On retry models, wait for retry or reset at
thermostat.
• Check for correct installation and wiring before replacing
any component.
• Control module cannot be repaired. If it malfunctions, it
must be replaced.
• Use only quali
fi
ed service agent to service ignition
systems.
1.
Perform checkout as
fi
rst step in troubleshooting.
2.
Check troubleshooting guide to pinpoint cause of
problem. See Table 8 , page 35.
3.
If troubleshooting indicates ignition problem, see
Ignition System Checks to isolate and correct the
problem.
4.
Perform checkout procedure following troubleshooting
guide again to verify system is operating normally.
A.8 Troubleshooting Error Codes
Integrated boiler control uses advanced diagnostic
capability to assist in troubleshooting error conditions.
Table 8 shows codes that could arise on integrated display
during fault.
Suggestions are provided in Table 8 for servicing these
potential errors.
Summary of Contents for PENNCO FSB 3 Series
Page 23: ...23 WIRING DIAGRAMS Figure 12 Control Module Damper is not an option ...
Page 37: ...Date Service Performed Company Name Tech Initials Company Address Phone ...
Page 38: ...NOTES ...
Page 39: ...Date Service Performed Company Name Tech Initials Company Address Phone ...
Page 40: ...PENNCO BOILERS 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com ...