7
LOCATING THE BOILER
Locating the Boiler
1.
Select level location as centralized with piping system,
and as near chimney as possible.
2.
Place crated boiler at selected location. Remove all
crate material. Please recycle responsibly.
WARNING
Fire hazard. Do not install boiler on combustible
flooring or carpeting. Failure to follow these
instructions could result in death or serious injury.
!
3.
FOR INSTALLATION ON NON-COMBUSTIBLE
FLOORS ONLY -
For installation on combustible
flooring special base shall be used. Please refer to
(Combustible Floor Addendum) included in literature
envelope provided with boiler and outlined in
National
Fuel Gas Code
, ANSI Z223.1/NFPA 54.
Do Not Install
Boiler on carpeting.
4.
Use metal shims under boiler base legs for final leveling
if needed.
5.
Install boiler in location that permits satisfactory
combustion of gas, proper venting, and maintenance
of ambient temperature at safe limits under normal
conditions of use. Boiler location should not interfere
with proper circulation of air. Introduce outside air
if normal infiltration does not provide necessary
air.“Fresh Air for Combustion” on page 12.
6.
Notify owner to keep air passages free of obstruction.
Ventilating and combustion air must enter boiler room
without restrictions.
7.
Install boiler so automatic gas ignition system
components are protected from water (dripping,
spraying, rain, etc.) during appliance operation and
service.
Draft Hood Installation
WARNING
Asphyxiation, carbon monoxide hazard. Failure to
follow these instructions could result in improper
combustion and possible leakage of combustion
products into the living space.
!
Table 2 -
Minimum Clearance Dimensions
Top
6"
Rear
6"
Control Side
7"
Opposite Side
6"
Front
Alcove
Flue/Vent
Connector
6"
Follow directions given in Figure 7, Mount vent damper. See
"Connecting Vent Damper and Vent Connector" page 15.
See Wiring Diagrams page 26.
PN 14683003 Rev. O [10/01/2021]